HomeMy WebLinkAbout613151000 Noise Study AZ Office CA Office
4960 S. Gilbert Rd, Suite 1-461 1197 Los Angeles Ave, Suite C-256
Chandler, AZ 85249 Simi Valley, CA 93065
p. (602) 774-1950 p. (805) 426-4477
www.mdacoustics.com | www.ebiconsulting.com
MD Acoustics, LLC | EBI Consulting, Inc. 1
JN: 04601923_Letter Report
EBI JN: 6219001518
May 10, 2019
AT&T C/O General Dynamics
6664 South Dateland Dr, Ste B
Tempe, AZ 85283
C/O EBI Consulting
Subject: AT&T – 10049045 Fullerton Road Generator Add – Noise Review Letter – Forks, WA
MD Acoustics, LLC (MD) has completed a noise assessment for the 10049045 Fullerton Road Generator
Add project located at 7048 Oil City Road, Forks, WA. The site plan utilized for the project is located in
Exhibit A (page 3 of this report). The project was assessed with regard to the future emergency generator
(Kohler 20kw Diesel Generator) noise level projections to the nearest sensitive receptors and compared
to the County’s applicable noise limits as outlined in the County’s Noise Ordinance. The project proposes
to install Kohler 20kw Diesel Generator with subbase fuel tank on new concrete pad. A glossary of
acoustical terms is located in Appendix A.
1.0 Acoustics Requirements
The County has outlined the noise limit for residential districts within the county of Jefferson County.
Chapter 173 Maximum Environmental Noise Levels Section 60-040 from the Washington Administrative
Code (WAC) provides the exterior noise limits associated with different land uses and is provided in
Appendix B. Table 1 below gives the maximum permitted noise levels, unless otherwise specifically
indicated, which shall apply to all receiving properties within a designated noise zone for establishing
noise level limits.
Table 1: Maximum Permitted Noise Levels
Per WAC 173-60-040 (b) between the hours of 10:00 PM and 7:00 AM the noise limitations of the
foregoing table shall be reduced 10 dBA for receiving property within Class A EDNAs. Therefore, this
study evaluates the telecommunications worst-case noise levels and compares the results to the
County’s nighttime (10PM – 7AM) residential noise standard of 45 dBA.
10049045 Fullerton Road Generator Add
Noise Impact Study
Forks, WA
MD Acoustics, LLC | EBI Consulting, Inc. 2
JN: 04601923_Letter Report
EBI JN: 6219001518
2.0 Study Method and Procedure
The future telecommunication equipment noise level was modeled using SoundPlan 3D (SP) acoustic
modeling software. SP is capable of evaluating stationary noise sources (e.g. point sources such as fans,
exhaust from generators) at various receptor locations. SP’s software utilizes algorithms (based on
inverse square law and reference equipment noise level data) to calculate the noise projections. The
software allows the user to input specific noise sources, spectral content, sound barriers, building
placement, topography and noise sensitive receptors. Appendix C provides the model’s inputs and
outputs.
3.0 Findings
A total of one (1) receptors were modeled to accurately evaluate the future operational noise levels at
and/or adjacent to the project site. A receptor is denoted by a yellow dot. The dot represents either a
property line, a sensitive receptor such as an outdoor sensitive area/building facade or a calibration point
(point where sound pressure levels are confirmed to match manufacturer’s noise data). The nearest
property line from the project site is approximately 2 miles away, therefore Receptor 1 represents the
worst case nearest sensitive receptor 500 feet from the project’s property line. It should also be noted
that the baseline noise level will only change under a power loss (emergency) situation or during
routine maintenance.
Exhibit B provides the future noise level projections based on the proposed project design (page 4 of this
report). The noise levels at the worst case nearest sensitive receptor 500 feet from the project’s property
line will be 33.0 dBA which is below the County’s 45 dBA nighttime residential standard.
Exhibit C illustrates the noise contours at the project site and illustrates how the noise will propagate
(page 5 of this report).
No additional noise mitigation is required as the project will comply with the County’s nighttime
residential noise limit of 45 dBA.
4.0 Conclusion
MD is pleased to provide this noise review for this project. The project will comply with the County’s
applicable noise allowable limits based on the proposed design. If you have any questions regarding this
letter, please call our office at (602) 774-1950.
Sincerely,
MD Acoustics, LLC
Mike Dickerson, INCE Robert Pearson
Principal Acoustical Consultant
10049045 Fullerton Road Generator Add
Noise Impact Study
Forks, WA
MD Acoustics, LLC | EBI Consulting, Inc. 3
JN: 04601923_Letter Report
EBI JN: 6219001518
Exhibit A
Site Plan
10049045 Fullerton Road Generator Add
Noise Impact Study
Forks, WA
MD Acoustics, LLC | EBI Consulting, Inc. 4
JN: 04601923_Letter Report
EBI JN: 6219001518
Exhibit B
Future Operational Noise Level
10049045 Fullerton Road Generator Add
Noise Impact Study
Forks, WA
MD Acoustics, LLC | EBI Consulting, Inc. 5
JN: 04601923_Letter Report
EBI JN: 6219001518
Exhibit C
Future Operational Noise Level
MD Acoustics, LLC | EBI Consulting, Inc.
JN: 04601923_Letter Report
Appendix A
Glossary of Acoustical Terms
MD Acoustics, LLC | EBI Consulting, Inc.
JN: 04601923_Letter Report
Glossary of Terms
A-Weighted Sound Level: The sound pressure level in decibels as measured on a sound level meter using
the A-weighted filter network. The A-weighting filter de-emphasizes the very low and very high frequency
components of the sound in a manner similar to the response of the human ear. A numerical method of
rating human judgment of loudness.
Ambient or Background Noise Level: The composite of noise from all sources, near and far. In this context,
the ambient noise level constitutes the normal or existing level of environmental noise at a given location.
Decibel (dB): A unit for measuring the amplitude of a sound, equal to 20 times the logarithm to the base
10 of the ratio of the pressure of the sound measured to the reference pressure, which is 20 micro-pascals.
dB(A): A-weighted sound level (see definition above).
Equivalent Sound Level (LEQ): The sound level corresponding to a steady noise level over a given sample
period with the same amount of acoustic energy as the actual time varying noise level. The energy average
noise level during the sample period.
Field Sound Transmission Class (FSTC): The field sound transmission class (FSTC) rating is used for in situ
wall and floor/ceiling sound isolation performance assessment. The standard requires the measurement
of sound transmission loss and includes required procedure to show that the FSTC rating, as it has been
determined by the test procedure, was not influenced by flanking of sound around the partition intended
to be tested. Sound transmission class and FSTC ratings are intended by standard to be equivalent;
however, practical experience indicates that FSTC ratings tend to be up to five ratings points less than
laboratory-measured STC ratings.
Day-Night Level (LDN or DNL): LDN is the average noise level over a 24-hour period. The noise between
the hours of 10PM to 7AM is artificially increased by 10 dB. This noise is weighted to take into account the
decrease in community background noise of 10 dB during this period.
Noise: Any unwanted sound or sound which is undesirable because it interferes with speech and hearing,
or is intense enough to damage hearing, or is otherwise annoying. The State Noise Control Act defines
noise as "...excessive undesirable sound...".
Noise Isolation Class (NIC): The noise isolation class (NIC) rating is similar to STC and FSTC. However, the
standard STC rating contour is applied to the one-third octave band noise reduction measured in a field
situation, rather than the transmission losses measured in the field. No correction to the measured noise
reduction data is made to account for partition size, receiving room absorption, or sound flanking. Like the
STC and FSTC ratings, the field measured NIC rating of a noise reduction spectrum is equal to the value of
the contour crossing at 500 Hz. In the absences of sound flanking, the NIC is generally within five points of
the laboratory STC rating for typical building partition constructions. The NIC rating is used to assess the
sound isolation performance of in situ partition construction, especially complicated ones that involve
MD Acoustics, LLC | EBI Consulting, Inc.
JN: 04601923_Letter Report
multiple sound transmission paths that are not suited for laboratory testing. The NIC rating is often used
in lieu of STC and FSTC.
Normalized Noise Isolation Class (NNIC): The normalized noise isolation class (NNIC) is the same as the
NIC rating except the receiving room absorption is normalized to correspond to a 0.5-s reverberation time.
Sound Level (Noise Level): The weighted sound pressure level obtained by use of a sound level meter
having a standard frequency-filter for attenuating part of the sound spectrum.
Sound Level Meter: An instrument, including a microphone, an amplifier, an output meter, and frequency
weighting networks for the measurement and determination of noise and sound levels.
Sound Transmission Class (STC): To quantify STC, a Transmission Loss (TL) measurement is performed
in a laboratory over a range of 16 third-octave bands between 125 – 4,000 Hertz (Hz). The average human
voice creates sound within the 125 – 4,000 Hz 1/3rd octave bands.
STC is a single-number rating given to a particular material or assembly. The STC rating measures the
ability of a material or an assembly to resist airborne sound transfer over the specified frequencies (see
ASTM International Classification E413 and E90). In general, a higher STC rating corresponds with a
greater reduction of noise transmitting through a partition.
STC is highly dependent on the construction of the partition. The STC of a partition can be increased by:
adding mass, increasing or adding air space, adding absorptive materials within the assembly. The STC
rating does not assess low frequency sound transfer (e.g. sounds less than 125 Hz). Special consideration
must be given to spaces where the noise transfer concern has lower frequencies than speech, such as
mechanical equipment and or/or music. The STC rating is a lab test that does not take into consideration
weak points, penetrations, or flanking paths.
Even with a high STC rating, any penetration, air-gap, or “flanking path can seriously degrade the
isolation quality of a wall. Flanking paths are the means for sound to transfer from one space to another
other than through the wall. Sound can flank over, under, or around a wall. Sound can also travel through
common ductwork, plumbing or corridors. Noise will travel between spaces at the weakest points.
Typically, there is no reason to spend money or effort to improve the walls until all weak points are
controlled first.
MD Acoustics, LLC | EBI Consulting, Inc.
JN: 04601923_Letter Report
Appendix B
Washington Administrative Code (WAC)
Noise Ordinance
5/9/2019 WAC 173-60-040:
https://app.leg.wa.gov/wac/default.aspx?cite=173-60-040 1/1
WAC 173-60-040WAC 173-60-040
Maximum permissible environmental noise levels.Maximum permissible environmental noise levels.
(1) No person shall cause or permit noise to intrude into the property of another person which(1) No person shall cause or permit noise to intrude into the property of another person which
noise exceeds the maximum permissible noise levels set forth below in this section.noise exceeds the maximum permissible noise levels set forth below in this section.
(2)(a) The noise limitations established are as set forth in the following table after any applicable(2)(a) The noise limitations established are as set forth in the following table after any applicable
adjustments provided for herein are applied.adjustments provided for herein are applied.
Class AClass A Class BClass B Class CClass C
55 dBA55 dBA 57 dBA57 dBA 60 dBA60 dBA
5757 6060 6565
6060 6565 7070
(b) Between the hours of 10:00 p.m. and 7:00 a.m. the noise limitations of the foregoing table(b) Between the hours of 10:00 p.m. and 7:00 a.m. the noise limitations of the foregoing table
shall be reduced by 10 dBA for receiving property within Class A EDNAs.shall be reduced by 10 dBA for receiving property within Class A EDNAs.
(c) At any hour of the day or night the applicable noise limitations in (a) and (b) above may be(c) At any hour of the day or night the applicable noise limitations in (a) and (b) above may be
exceeded for any receiving property by no more than:exceeded for any receiving property by no more than:
(i) 5 dBA for a total of 15 minutes in any one-hour period; or(i) 5 dBA for a total of 15 minutes in any one-hour period; or
(ii) 10 dBA for a total of 5 minutes in any one-hour period; or(ii) 10 dBA for a total of 5 minutes in any one-hour period; or
(iii) 15 dBA for a total of 1.5 minutes in any one-hour period.(iii) 15 dBA for a total of 1.5 minutes in any one-hour period.
[Order 74-32, § 173-60-040, filed 4/22/75, effective 9/1/75.][Order 74-32, § 173-60-040, filed 4/22/75, effective 9/1/75.]
MD Acoustics, LLC | EBI Consulting, Inc.
JN: 04601923_Letter Report
Appendix C
SoundPlan Input/Output
Frequency spectrum [dB(A)]Corrections
Source name Reference Level 63 125 250 500 1 2 4 8 16 Cwall CI CT
dB(A)Hz Hz Hz Hz kHz kHz kHz kHz kHz dB(A)dB(A)dB(A)
1 Lw/unit Day 95.0 68.8 78.6 90.4 90.4 87.8 84.0 76.3 67.7 54.4 ---
Night -------------
Noise emissions of industry sources
MD Acoustics 1197 E Los Angeles Ave,Unit C 256 Simi Valley, CA 93065 USA
Level w/o NP Level w NP
Source name Day Night Day Night
dB(A)dB(A)
2 GF 33.0 33.0 0.0 0.0
1 33.0 33.0 0.0 0.0
Contribution levels of the receivers
MD Acoustics 1197 E Los Angeles Ave,Unit C 256 Simi Valley, CA 93065 USA
MD Acoustics, LLC | EBI Consulting, Inc.
JN: 04601923_Letter Report
Appendix D
Manufacturers Cut Sheet
KD20U
Engine type 3029DFS29
Alternator type KH00404T
Performance class G3
GENERAL CHARACTERISTICS
Frequency (Hz)
Voltage (V)
Standard control panel
Optional control panel
Optional control panel
POWER
ESP PRPVoltagekWekVAkWekVA Standby Amps
480/277 20 25 18.2 22.7 30
440/254 20 25 18.2 22.7 33
220/127 20 25 18.2 22.7 66
208/120 18.4 23 16.7 20.9 64
DIMENSIONS COMPACT VERSION
Length (mm)1700
Width (mm)896
Height (mm)1221
Dry weight (kg)709
Tank capacity (L)100
DIMENSIONS SOUNDPROOFED VERSION
Commercial reference of the enclosure M127
Length (mm)2080
Width (mm)960
Height (mm)1415
Dry weight (kg)930
Tank capacity (L)100
Acoustic pressure level @1m in dB(A) 78
Sound power level guaranteed (Lwa) -
DESCRIPTIVE
Kohler Co. Provides one-source responsibility for the
generating system and accessories
The generator set and its components are prototype-
tested, factory-built, and production-tested
A one-year limited warranty covers all systems and components
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed
TERMS OF USE
According to the standard, the nominal power assigned by the genset is given for 25°C Air Intlet Temperature, of a barometric pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels depend on the installation conditions, it is not possible to specify the ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-03012 (KD20U) 06/17
Acoustic pressure level @7m in dB(A) 68
60
480/277
APM303
DEC4000
M80
Mechanic governor
Mechanically welded chassis with antivibration
suspension
Main line circuit breaker
Radiator for core temperature of 48/50°C max with
mechanical fan
Protective grille for fan and rotating parts (CE option)
9 dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
12 V charge alternator and starter
Delivered with oil and coolant -30°C
Manual for use and installation
KD20U
ENGINE CHARACTERISTICS
JOHN DEERE
3029DFS29
Athmo
L
3
2.91
-
106 x 110
17.2 : 1
1800
6.6
35
+/- 2.5%
8.7
GENERAL ENGINE DATA
Engine model
Engine type
Air inlet
Cylinders arrangement
Number of cylinders
Displacement (L)
Charge Air coolant
Bore (mm) x Stroke (mm)
Compression ratio
Speed (RPM)
Pistons speed (m/s)
Maximum stand-by power at rated
RPM (kW)
Frequency regulation (%)
BMEP (bar)
Governor type Mechanical
COOLING SYSTEM
Radiator & Engine capacity (L)16.1
Max water temperature (°C)-
Outlet water temperature (°C)-
Fan power (kW)1.2
2.22
20
Fan air flow w/o restriction (m3/s)
Available restriction on air flow (mm
H2O)
Type of coolant Glycol-Ethylene
Thermostat modulating range HT (°C) -
-
-
-
EMISSIONS
Emission PM (g/kWh)
Emission CO (g/kWh)
Emission HC+NOx (g/kWh)
Emission HC (mg/Nm3) 5% O2 30
570
102
EXHAUST
Exhaust gas temperature @ ESP 60Hz (°C)
Exhaust gas flow @ ESP 60Hz (L/s)
Max. exhaust back pressure (mm H2O)625
9
8
6.5
4.4
FUEL
Fuel consumption 110% load (L/h)
Fuel consumption 100% load (L/h)
Fuel consumption 75% (L/h)
Fuel consumption 50% (L/h)
Maximum fuel pump flow (L/h)108
6
1
5
0.2
OIL
Oil capacity (L)
Min. oil pressure (bar)
Max. oil pressure (bar)
Oil consumption 100% load (L/h)
Oil sump capacity (L)5.3
31
7
HEAT BALANCE
Heat rejection to exhaust (kW)
Radiated heat to ambient (kW)
Heat rejection to coolant (kW)20
300
AIR INTAKE
Max. intake restriction (mm H2O)
Intake air flow (L/s)36
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-03012 (KD20U) 06/17
KD20U
ALTERNATOR CHARACTERISTICS
GENERAL DATA
Alternator type KH00404T
Number of Phase Three phase
Power factor (Cos Phi)0.8
Altitude (m)0 to 1000
Overspeed (rpm)2250
Number of pole 4
Capacity for maintaining short circuit at
3 ln for 10 s Yes
Insulation class H
T° class, continuous 40°C H / 125°K
T° class, standby 27°C H / 163°K
AVR Regulation Yes
Total Harmonic Distortion in no-load
DHT (%)3.6
Total Harmonic Distortion, on load DHT
(%)2
Wave form : NEMA=TIF <45
Wave form : CEI=FHT <2
Number of bearing 1
Coupling Direct
1
200
Voltage regulation at established rating
(+/- %)
Recovery time (Delta U = 20%
transient) (ms)
Protection class IP 23
Technology Without collar or
brush
OTHER DATA
Continuous Nominal Rating 40°C (kVA)24
Standby Rating 27°C (kVA)25.8
Efficiencies 100% of load (%)89.5
Air flow (m3/s)0.097
Short circuit ratio (Kcc)0.62
Direct axis synchro reactance unsaturated (Xd) (%)184.5
Quadrature-axis synchro reactance unsaturated (Xq)
(%)
Open circuit time constant (T'do) (ms)850
Direct axis transient reactance saturated (X'd) (%)14.6
44
8.4
14
19.2
10
Zero sequence reactance unsaturated (Xo) (%)3.38
Negative sequence reactance saturated (X2) (%)12.5
Armature time constant (Ta) (ms)12
No load excitation current (io) (A)0.5
Full load excitation current (ic) (A)1.5
15.9
76
Full load excitation voltage (uc) (V)
Engine start (Delta U = 20% perm. or 50% trans.)
(kVA)
Transient dip (4/4 load) - PF : 0,8 AR (%)14.1
No load losses (W)569
Heat rejection (W)2253
DIMENSIONS
Dimensions soundproofed version
Commercial reference of the enclosure M127
Length (mm)2080
Width (mm)960
Height (mm)1415
Dry weight (kg)930
Tank capacity (L)100
Acoustic pressure level @1m in dB(A) 78
Sound power level guaranteed (Lwa) -
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-03012 (KD20U) 06/17
Acoustic pressure level @7m in dB(A) 68
80
Short circuit transient time constant (T'd) (ms)
Direct axis subtransient reactance saturated (X''d) (%)
Subtransient time constant (T"d) (ms)
Quadrature-axis subtranscient reactance saturated
(X"q) (%)
Subtransient time constant (T"q) (ms)
Unbalanced load acceptance ratio (%)100
Dimensions DW compact version
-
2160
966
1388
891
230-
-
Commercial reference of the enclosure
Length (mm)
Width (mm)
Height (mm)
Dry weight (kg)
Tank capacity (L)
Acoustic pressure level @1m in dB(A)
Sound power level guaranteed (Lwa)
Acoustic pressure level @7m in dB(A) -
Dimensions DW soundproofed version
M127 DW
2160
966
1582
1120
230
78
-
Commercial reference of the enclosure
Length (mm)
Width (mm)
Height (mm)
Dry weight (kg)
Tank capacity (L)
Acoustic pressure level @1m in dB(A)
Sound power level guaranteed (Lwa)
Acoustic pressure level @7m in dB(A) 68
Dimensions DW 48h soundproofed version
M127 DW48
2160
966
1631
1124420
78-
Commercial reference of the enclosure
Length (mm)
Width (mm)
Height (mm)
Dry weight (kg)
Tank capacity (L)
Acoustic pressure level @1m in dB(A)
Sound power level guaranteed (Lwa)
Acoustic pressure level @7m in dB(A) 68
KD20U
CONTROL PANEL
APM303, comprehensive and simple
The APM303 is a versatile unit which can be operated in
manual or automatic mode. Equipped with an LCD screen,
the user-friendly APM303 offers high-quality basic functions
to guarantee simple, reliable operation and supervision of
your generating set. It offers the following features:
Measurements:
phase-to-neutral and phase-to-phase voltages, active power
currents, effective power, power factors, Kw/h energy meter
Fuel, oil pressure and coolant temperature levels
Supervision:
Modbus RTU communication on RS485
Reports:
2 configurable reports
Safety features:
Overspeed, oil pressure
Coolant temperatures
Minimum and maximum voltage
Minimum and maximum frequency
Maximum current
Maximum active power
Phase sequence
Traceability:
Stack of 12 stored events
For further information, please refer to the data sheet for the
APM303.
DEC4000, ergonomic and user-friendly
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-03012 (KD20U) 06/17
The highly versatile DEC4000 control unit is complex yet
accessible, thanks to the particular attention paid to
optimising its ergonomics and ease of use. With its large
display screen, buttons and scroll wheel, it places the
accent on simplicity and communication.
The DEC4000 offers the following functions:
Electrical measurements: voltmeter, frequency meter,
ammeter.
Engine parameters: working hours counter, oil pressure,
coolant temperature, fuel level, engine speed, battery
voltage.
Alarms and faults: oil pressure, coolant temperature, failure
to start, overspeed, alternator min./max., battery voltage
min./max., emergency stop, fuel level.
Ergonomics: wheel for navigating around the various
menus.
Communication: remote control and operation software,
USB connections, PC connection.
For more information on the product and its options, please
refer to the sales documentation.
The control unit can be used as a basic terminal block for
connecting a control box.
Offers the following functions:
emergency stop button, customer connection terminal
block, CE.
Basic terminal block
KD20U
CONTROL PANEL
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-03012 (KD20U) 0/17
M80, transfer of information
The M80 is a dual-function control unit. It can be used as a
basic terminal block for connecting a control box and as an
instrument panel with a direct read facility, with displays
giving a global view of your generating set's basic
parameters.
Offers the following functions:
Engine parameters: tachometer, working hours counter,
coolant temperature indicator, oil pressure indicator,
emergency stop button, customer connection terminal
block, CE.