HomeMy WebLinkAboutBLD2015-00058 - SPECS CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 /\--) (6)O $ 1 �v , . .. Fize. stItthefilLE# systrm s VII Vst S 6. fel l' A ,4 FIRE SPRINKLER EQUIPMENT SUBMITTAL FOR Camp Parsons 970 Bee Mill Road Brinnon, WA 98320 COLUMBIA FIRE Job #1406073 1 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TABLE OF CONTENTS Section 2.1 - Pipe and Fittings 1. Allied Schedule-10 black steel pipe 21/2"Grooved 2. Allied Schedule-40 black steel pipe 1/2"-2"Threaded 3. Ductile Iron Threaded Fittings 4. Grooved Fittings, Couplings & Mechanical Tees —Victaulic 5. 6x4 Cement linked, Flanged Reducing 90° Elbow 6. EZ Flex, Flex drop — Victaulic Section 2.2 - Fire Sprinklers 1. Extended Coverage, Dry Horz. Sidewall, K=11.2,SR,155°,16'x20'—Tyco Model TY5339 2. Globe GL5615, STD, BR, SSU , 1/2" 5.6K, 155° 3. Globe GL5615, STD, BR, SSU , 1/2" 5.6K, 200° 4. Globe GL5606 concealed SSP BR/White 1/2" 5.6K, 155° 5. Globe GL5606 concealed SSP BR/White 1/2" 5.6K, 200° 6. Globe Dry Pendant 7. Globe Dry Horizontal Sidewall Section 2.3 - Valves and Accessories 1. FDC 4"X 21/2"X 2'/2"— FPPI Straight Model# 09-000 2. W/P 4 IPS Auto Sprinkler Red ALU - FPPI 3. Backflow — Wilkins 350A BGVIC 4. 4"Grooved to Grooved Swing Check Valve 5. 4"Tyco #513 Riser Manifold Section 2.5 —Automatic Drain Device 1. Automatic Drain (Ball Drip) valve Model# F789 Hangers and Sway Bracing 1. Hanger Ring —Tolco Fig. 200 2. Sammy Screws — Vertical, Horizontal & X-Press (Wood) 3. Earthquake Pipe Clamps —Tolco Fig. 4 & 4A 4. Earthquake Fast clamps —Tolco 1001 5. Tolo Fig. 980 Earthquake attachments 6. Tolco Fig. 906 Sway Brace Multi fastener adapter Supervisory Devices 1. 10" Electric Bell - Potter Electric PB Series 2 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 SECTION 2 . 1 PIPE & FITTINGS 3 Schedule 10 / Schedule 40 M-COAT Fully Listed and FM Approved Sprinkler Pipe When you specify Allied Schedule-10/Schedule-40-M-COAT sprinkler pipe you get a UL listed and FM approved product.Although these products do not require separate approvals,Schedule-10/Schedule-40-M-COAT gives you the extra quality assurance you demand.Our Sch-10(11/4"-8")pipe and Sch-4 (1"-21")pipe have passed the same thorough lab testing as our other listed pipe products,and receive periodic mill inspections from both UL and FM agents to ensure consistent quality. ® Galvanized Pipe Sch-40 ASTM A735/A795 M-COAT Specifications Schedule-10/Schedule-40-M-COAT product can NPS Nominal Nominal I.D. Nominal Wt. Wt.(1120 Filled) CRR be "hot dip"galvanized to meet FM requirements In;mm O.D.In;mm In;mm Wall In;mm Lbs/Ft;kclm Lbs/Ft;kq/m 1" 1.315 7.049 0.133 1.680 2.05 1 for dry systems in accordance with the zinc coating 25 33.4 26.6 3.38 2.5 3.05 specifications of ASTM A-123. 11/4" 1.660 1.380 0.140 2.270 2.93 32 42.1 35.1 3.56 3.39 4.36 ® Superior Coating 1.903 1.610 0.145 7.720 3.61 , 40 48.3 40.9 3.68 4.0 5.37 Our advanced formula mill coating offers a clean, 2" 2.375 2.067 0.154 3.656 5.13 1 durable surface.It is also paint-ready for custom 50 60,3 52.5 3.91 5.4 7.63 color applications without special preparation. 21/2" 2.875 2.169 0.203 5.80 7.86 1 The internal surface of all black Allied Tube& 65 73 62.7 5.16 8.6 1.73 Conduit fire sprinkler pipe products up to 4.500" in diameter are coated with M-COAT,an advanced Sch-10 ASTM A135/A795 MIC coating that is FM approved for use in M-COAT Specifications hybrid sprinkle systems. NPS Nominal Nominal I.D. Nominal Wt. Wt.(1120 Filled) CRR In;mm O.D.In;mm In;mm Wall In;mm Lbs/Ft;kq/m Lbs/Ft;kq/m - 1¼" 1.660 1.442 0.109 1.810 2.525 7.0955 O American made 32 42.2 36.E 2.77 2.7 3.75 - 11/2" 1.900 1.682 0.109 2.09 3 04 5.6570 Able to meet"Buy American"requirement and 40 48.3 42.7 2.77 3.1 4.52 - is available through distributors in the USA, 2" 2.375 7.137 0.109 2.640 4.22 4.5827 Canada, Mexico and Latin America. 50 60:3 54.8 2.77 3.9 6.28 21/2" 1875 1.635 0.120 3.530 5.89 3.5196 65 73 66.9 3.05 5.26 8.77 - 0 Specifications & Approvals 3" 3.500 3.260 0.120 4.34 7.94 1.5550 75 88.9 82.8 3.05 6.4 11;82 Schedule-10/Schedule-40-M-COAT pipe are in 4 4 500 4,260 0.120 5 E1 78 1.6020 compliance with the following:ASTM A-135,Type 100 14.3 ios.zo 3.05 8.3 1253 E Grade A,and NFPA 13.All pipe products have a 5,. Ss63 5.295 0.134 a 7.33 4874 p p p 125 141.3 134,5 _ 3.40 11.58 25.80 rated working pressure of 300 psi maximum and 6" 6.625 6.357 0.134 9.3 23.03 1.0251 also meet the stringent requirements for the 150 168.3 161.5 3.40 13.8 34.27 following applications and tests: 8" 8.625 8.249 0.188 16.96 40.15 1.8365 •Welded Outlets 200 219 209 SO 4.78 25.2 59.75 • Hydrostatic Pressure ® D® r 9'dlied Customer Service (800) 882-5543 Fax: (800) 659-7730 www.alliedtube-sprinkler.com •16100 S Lathrop Ave. • 11350 Norcom Rd. •2525 N 27th Ave. TUBE & CONDUIT' Harvey,IL 60426 Philadelphia4 PA 19154 Phoenix,AZ 85009 ...ART OF A atkore CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Specification & Data 6.3 A::E• :i .-1 r:PT :ASP/ I - - -- ' i•I :1 A536 : . _ '.. ... • a:ii ',•Voi-iang Pressure.: a::: psi ..•..-•/ - ddicc :tom ..L. ULC i..7.:.:.. ri:...... Pipe Wrench Installation ..",..r..-..f..- -1,1•i;nnvit-ii.-i ili- --iig•-. .-: :•. (ion pipe joirt :"..i -r- pine threads a..A -..„:--:e:-. 7hree and one-haV :-.:-:--.fcra hand tight. Note P.....-!•:!;:o Ductile Iron i ri:.iia-.-.7::: F :1-.9s provide - , 31.7i CD'IC.5;:011 resi.:717:-.::.-an Cast iron rAtings. P.:....: .... ,.. :-.7.c.. Gr.c,!:•;5; ...,,.,4 1.75,.•r,-, . ..:r•nty•-i die ,...., the extra pi-eic,...s a.71.1-sc ing the rit,.icesit. .:-.•castirl 'This prcvideii, an ad.,,a-i--i..i.:,..:, ... •,..',:...g. ' . , -..• ..__ . . ... _ -2......31 •:3LI: iron as tr'o f lin:7:E 3..E: nal. .27,-,:•,i.,•;-..) Padrfitio :;:ii.ii.i•,:, iiii;:i- 1-7.:iigs u.-.6 I.gi: si- t-Ffn ::'‘'.''' '• '' mern easier lc-, hr.--i--,t-tte ar...-: .nstall. • i'i'....,.•: • :.. ..-.... •"••• : ....•, - ., . . ... 4:7::::"••=:-'- r 2' ATTEIT1C 1 Caution: r,s:aile:rs who have ;lc: use:: Juctile. iron ftiiicis: tiAore should be •:: •..•:.i •ned that the tittmcis have a higher ie.,_•••e •:-1fergth than stee p-pe. Tiierefore. ove.' ...Cr.: =7'nc„I tile fitting • . • .... n-.ay. ilc.n-.--ige the p,p-.7.- thc. .--irld cause leaks •• •• • " L. :••• . , ,. .• ... . t _._ • ... . . . _ should he at.c..,.:t o:,, 't ;_: : a turn difference ., :-2et.,:een cast irhin .:"..'eper.cis on the thread of oast , .. .. a iiiii-i.._-_,::t) and ouctihi-, ;cc-, f,ittfngs, Apply Tellz•n: tar.:e - - --'- - - ity,afily pipe.i,c.-iir-it co-hiocu7id on the pipe thread .:14i.:`•.-7 tighien three arc one•ha. ti••,ris beyond "-: • •......:t- . . „ t-•:-.:-.,:t 1:eht No rnore tnan feu! turns! . „',-;'-.1 ._ • — • . . -. . .. Caution for automatic make-on machine users: • -..-r.,-... ...r..P. ; . .Y.- • Exercise, specia: catnip!) 5-4 mg the inachiiie 1•:: „., .:'•:ii, : :;•:-"Y'i- "-.'1:-., ..-.: ,,,4 • • .0... . : --,-4 the :•.ii)per parameter p!...::.:r Id tightening fittings ..1 ,-.. ..,, :.:-.'..-• :he male pipe threads. •",.' ..:, ...tri:e.sg.,,,....L.. Distributed By . , 6 ---1 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 .I0 readed Fittings ..._ =.0:-•/ ..-A )°70 Air-Tested In A Water Soluable Oil Solution. Ductile Iron Hex Reducer Ductile Iron hex Bushing m:.jei Tici5 Wrench Wt. Box II Size bs Oty Model T-110 Size A Wt E ,.. e 1110 - —I Mil I /4 IIII 1 4.X 1 1 ai f1;91. A 5.2- 1 a0 1:,',c I 1 .53 1 '.../* 35 Ductile Iron Cross , -„„ E ( Wt. Box Maciei T-107 Size A 2 1Y, 1 the, Oty x 1 , .52 , 1 - f 1 1 ',/, 1 :/' z 9-7 46 17 1 = , -.50 25 ....-44i.7.. Ductile Iron Extension Piece ,,. 2 , • 2 , 29J 10 Nirir.: !. T--',11" Lb4;1st, 1, A Reducing , _...._ , . -rik •■ '_ x 1 .. x I x 1 1 7=4 1 Vtt '25 30 — y j1 -' x 1 x 1 1 "' I , .." a 2 27 : 2 • 2 ' 264 10 YiY i .7 22 -----,.------ -- X a 2 MI : Ductile Iron Straight Coupling Ductile Iron Plug Wrench WI Box Model T-108 Size A Svc Lts. Qw. 'M. B Model T-112' Size A ths c 1 -,/ 1 , , ic0 , ; ,,... 1 B _ 1 M ..--- . 1 I -_ 2 1 - 2 00 .._.....„....._.,—= A I ' ■ 2 7 2 ! 1 - 1/ 70_ Ductile Iron Cap 2 lin "e4° W ight Niodel T-109 S: Lebs. En Box av Will be available in early 1998 ., lila -441111111! -, REM i..4. 2 .e6 El I A 1111M 7 -5peCiticatiOns subject to change without notice. c October 1997 Paddico. Printed in the 1.J.S.A, CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 ill D u ctlie Iron 1 6 a Paddico Ductile Iron Threaded Fittings A Ductile Iron 90 Degree Elbow Ductile Iron Reducing Tee .__.,. Model T-101 Size A ' Lbs. Oty bx.--' 41411111Tro Model T-105 ----- • S iz.,s- A B C Wt-rats BOX ° •' 1 Y 4 1 a, 115 40 , . # 1 4 1 30 / „1.11 :1-1,, , # .2 o 2 a 11 ,,., # 11/ENRI 1,, II 1 ;2. 1 /1.5 1 1,1,1 Ductile Iron Reducing 90 Degree Elbow t Aodel T-102 Size A B Wt Box Lbs. QV 1 14/s4 1 V 1 "/ 1 03 7 • 4, -- __ , • 1 ' 1 1 4 1 # 1 ",,, 44 110 1 Ilt s AO"41 1 7/€ 53' 90 1 • - 1 ," 1 I 2.". x',".. 1' 1 Y, 64 75 , — _ 1 /;-, I 40 I 3 A — .." 4 i 11 56 1 3 _ ., l',4 X 1 1 14' 1 /6 77 xr , 1 / 1 ././. 1 ,07 _ -- 1, III 1 V x 2.• '' I 1,1 .95 ar. 1 1 ".,,,,E. I t., 1 ,4 72-1 t t 1 , 1 , ,, 1 7, 1 1.V . • , itye t; t ;" 1 ";,/o 2.9 4: 1 14 1 .'" 1,7... L • 2x "/„ 1 *1, 1 ,,.4'.o -,39' 10 / Iff 1 . 1 -1ta 1 r_fj ), , 1 2 x 1 - . ., 1 , 2 ,x 1 56 25 1 1 1 / 2 x 1V, i " 2 'e. 1 93 ' ':.- 2_ 2 ,I 2 'r , 2 124 1 ''s 1 ',,,.. 1 1 V: 1 /, 1 Ductile Iron 45 Degree Elbow Wt, Box l -/A 1 2.- 1 Ts, 1 Model T-103 Size - Lbs Oty i 2 2 2 2,/ 2 ' 1 .1._ 2 /. 2 '/a 2' °. 2 21 1 42 ao, . ' i".., - /r. 1 1.E2: - 1 V7e, 2 1 -31 1 ,/, • T.3 50 ./•, 1 1 . 1 71-, 2 2 - I 1 _.., i. a *atit IIIIIIEMIII 18 ,. 1 °, 1 7,,,,, 1 , 1 60. , 2 1 Ductile Iron Straight Tee l'i, z 2 VVt Box t.iodel T-104 Size A ' Lbs., Oty Ductile Iron Bullhead Tee - - micii-I so 7 7 i ., 1 , i i7c 1 MIMI 4 _rup ..o.. ...aPxxxit — .1 1 r„ 1 ',..„, t '.,r„, 1 ',/„... lid 3 • — 1 / # 1 30 35 1 V, 1 1 V: 1 .1 I .'XC / '7'; 14 3 , - 1/ # 11 , # ljgllIlEREEINlngaIII 1 ii 3 . , 1 - ' 1 53 24 1 l'il 111111 2 ,././A 2 2 80 2 n , _._ 2 2 _ 23 12 1 V: 11•# IMMO 2 Yu 2 I94 2 1 7, 11/ 2 : o 2 1/o- T 8 3 97 1 IPS CARBON STEEL PIPE-GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL 11/•V 1 OE073 Grooved End Fittings r NO.10 ELBOW NO.20 TEE MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. • Or: Segmentally welded steel as shown under nipples Nipples:(adapter,swaged&hose) • 3-4720-100mm: Carbon steel,Schedule 40,conforming to ASTM A-53,Type F • 5-67125-150mm:Carbon steel,Schedule 40,conforming to ASTM A-53,Type E or S,Gr. B • 8-127200-300mm:Carbon steel, Schedule 30 or 40,conforming to ASTM A-53, Type E or S, Gr. B Flanged Adapter Nipples:(Nipple-see above) • Class 125 Flange: Cast iron conforming to ANSI B-16.1 • Class 150 Flange: Carbon steel conforming to ANSI B-16.5,raised or flat face • Class 300 Flange:Carbon steel conforming to ANSI B-16.5, raised or flat face Fitting Coatings:Orange enamel • Optional: Hot dip galvanized and others.Some fittings supplied electroplated as standard-see product specifications. Flanged Adapter Nipple Coating: None(Unfinished) • Optional:Orange enamel, hot dip galvanized and others. www.victaulic.com 10 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. rCtaU�lt;. onr l 07 m z IPS CARBON STEEL PIPE- GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL U/ .0 I G: .i.i . Grooved End Fittings NO.10 ELBOW NO.20 TEE DIMENSIONS El bows NO. 10 90°Elbow NO. 11 45°Elbow NO. 12 22W Elbow NO. 13 111/4°Elbow O I w--C to E 7 NO. 100 90°Long Radius a E to E I NO. 110 45°Long Radius C to E-� m= I' C to E (Ductile Iron 1 l If cto E� �_A1 < CtoE C CtoE to i 7- NO.10 NO.11 NO.12 NO.13 NO.100 NO.110 No.10 No.11 No.12 No.13 No.100+ No.110t Sze 90"Elbow 45°Elbow 22W Elbow(sw) 11W Elbow(sw) 90°Long Radius Elbow IS) 45=Long Radius Elbow(S) Normal Actual Approx. Approx. Approx. 1 Approx. ... APprox.'.,. Size I Dutside Dia. C to E 'Wgt.Each C to E Wgt Each C to E Wgt.Each C to E Wgt.Each ! C to E I Wgt,Each C to E Wgt.Each finches Inches Inches Lbs. Inches Lbs. Inches Lbs. huhes Lbs. , Inches I Lbs. Inches Lbs. mm mm mm kg mm I kg rem kg mm kg mm kg mm kg 3e 1.050 2.25 0.5 150 , 03 [ 1635w 1.38 5w i _ _ _ _ 20 26.9 57 0.2 38 0.2 -W( 41 35 1-1 1 1.315 2.25 0.6 1.75 , 0.6 I 325@ 0.6 1.3 8 _03 _ 25 317 57 ( 0.3 44 1 1213 83 I:13 35 0.1 11/4 1.660 1 2.75 1.0 1.75 0.9 1.75 08 1.38 Sw I 05 _ 32 42.4 70 ) O S 44 0.4 44 04 35 l 0 2 - _ T 116 1.900 275 1.2 1.75 0.9 1.75 O 8 ' 1.38 sw 0 5 {{ _� - 40 48.3 70 ' 0.5 44 ti- 0.4 t 44 0.4 35 1 0.2 1 2 2.375 3.25 I 1.8 2.00 1 3 3.75 @ 1 4 1.38 1.0 4.38 i 25 i 2.75 1.8 50 l 60.3 83 t 0.8 51 0.6 95 0.6 35 0.5 111 1 1.1 1 70 0.8 4 21 i 2.875 375 3.2 2.25 2.2 400@ 23 150 11 5.00 I 4.1 1, 3.00 2.8 65 73.0 95 1 1.5 57 1,0 102 1.0 38 0.5 127 1 1.9 ? 76 1.3.............. 3 7 2 25 3 4 ' 76.7 mm 763.000.1 39.755 1.7 57 1.5 ' I 3 3.500 4.25 } 4.5 2.50 i 3.1 4.50 @ I 31 130 21 5 88 -+-1 6.0 3.38 4.9 80 889 108 j 2.0 64 1.4 114 1.4 38 1.0 149 l 2.7 86 _ _ 2.2 31/2 4.000 4.50 5.6 ! 2.75 I 4.3 2 50 sw , 4.0 ' 1 75 sw 1 2 7 I 90 101 6 114 2.5 € 70 2.0 64 E 1.8 44 1 1.2 ! - 4 4.500 5.00 t 7.1 € 3.00 5.6 288 1 5.6 1.75 j 3.6 750 12.3 4.00 7.3 100 1143 127 32 76 2.5 73 t 2.5 44 16 : 191 , 5.6 102 3.3• 108.0 mm 4.250 5.00 11.0 3.00 56 I _ 1080 127 5.0 76 25 :- € 4V 5.000 525 sw '' 10.0 ! 3.13 sw 00 350 66 1.88sw ; 42 _ ; - - - 120 1270 133 4.5 79 2.7 89 3.0 48 1.9 5 5.563 5.50 11.7 3.25 8.3 2.88 sw 7.8 2.00 sw . 5.0 182 14.8 125 1413 140 5 3 83 3 8 73 15 51 3 2.2 ( 8.3 I 6.7 133.0 mm 5.250 550 117 3.25 8.3 _ ' 133.0 140 53 83 32 i - 139:7 mm 5500 550 117 - 325 83 _ - 139.7 140 5.3 83 3.8 1 6 6625 6.50 172 350 1 108 ! 625@ 122 200 l 70 10.75 i 30.4 530 174 150 1623 165 78 89 i 4.9 159 55 ....... 51 _.i .... 32 273 ; 13.8 138 140 79 I 159.0mm 6250 6.50 18.6 3.50 10.8 ! I -159.0 165 84 1 89 49 I 1 r 6.500 650 15 5 350 9.8 313 114 ? 2.00 74 • 10.75 220 530 19.0 165.1 mm 165.1 _ 165 7.0 89 1 44 79 1 5.2 1 51 3.4 273 13.2 I 140 8.6 www.victaulic.com 11 Ctaulie VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. A7 A'1 A DM/ I IPS CARBON STEEL PIPE-GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL U/•U J. Grooved End Fittings r ,, X} " yak:_. NO.10 ELBOW NO.20 TEE • k.......---T I�C tO E-1 EtoE I CroEII�I #,,_ C �� C tO E to E _ I � C Ct- [OE MINIMINII =NM= NO.10 NO.11 NO.12 NO.13 NO.100 NO.110 No.10 No.11 No.12 No.13 No.100t No.110t Size 90°Elbow 45°Elbow 221/2 Elbow(sw) 111/4°Elbow(sw) 90`Long Radius Elbow(S) 45°Long Radius Elbow(S) No Size ' Acde Ap.Each Each Ea. .. Wgt.Each AP.Each Each Size Outside Dia. C to E I Wgl.Each C to E WgL.Exh C to E Wgt.Each C to E Wgt.Each C to E Wgt.Each C to E Wgt.Each Inches Inches Inches 1 Cos. Inches 1 Lbs. Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs. mm mm mm I kg mm i kg mm kg mrr I kg mm kg mm kg 8 8625 775 299 425 204 Z75@ € 20.0 2.00 10.1 c 1425 660 725 36.0 200 _219.1 197 13._6 108__ _ 93 197 I 91 51 4.6 362 300 184 16.3 10 10.750 1 9.00 � - 63.3 -475 375 4.38 sw 30.02.13 sw 115 ` 1500 1070 6.25 570 250 2730 229 283 121 17.0 111 135 54 53 381 48.5 159 25.9 12 12.750 1000 • 74.0 525 ._............I 18.00 1560 , 667 4.88 sw [ 40.0 225 sw 293 750 900 300 3239 254 33.6 ' 133 303 124 1 181 57 13 3 457 70 8 191 i 40.8 14# 14.000 1400 136.0 575 650 5.00 sw 1_ 46.0 350 sw 32.0 21.00 s 164 0 8.75 s 82.0 350 355.6 355.6 61.7 146 29.5 127 j 20.9 89 14.5 533 74.4 i 222 , 37.2 14843 1484 149.3 515 82.0 3770mm t 3770 3759 677 0 156.2 _ _372 - -• 16# 16.000 1690 171.0 6.63 880 : 5.00 sw 58.0 4 00 sw _ 420 24.00 s 210 0 - 10 00 s 1000 400 i 4064 406.4 77.6 168 • 39.9 • 127 3 26.3 102 19.1 610 95.3 254 454 •126.Omm t: 16.177 16.77 • 1985 695 101 3 i 426.0 426.0 90.1 1755 459 18# 18.000 18.00 228.0 746 108.0 i 5.50 sw ; 65 0 4.50 sw ! 532 2700 s 273.0 1125 s > 135.0 450 457.0 4572 103.4 189 50.0 140 29.5 114 24.1 686 123.8 286 : 61.2 4800mm t 18.898 1890 291.0 783 141.7 _ _ 480.0 480.0 1320 198.8 64.3 . 20# 20.000 2000 2980 828 138.0 6.00 sw € 78.6 5.00 sw € 65.0 ' 30.00 s 3430 ' 12.50 s i 1740 500 j 508.0 508.0 135.2 210 62.6 152 36.0 127 29.5 762 155.6 318 78.9 •530.0mm t; 20566 2087 355.0 864 179.0 _ - - ; 5300 5300 1610 2194 812 24# 24.000 ' 2400 • 438.0 994 221.0 700 sw ; 1400 600 sw 60.0 E 36005 5160 > 15.00s : 251.0 550 j 610.0 6096 198.7 252 1002 178 635 152 272 914 2341 381 : 113.9 630.0 mm t 24503 24.80 545.0 10.77 255.2 630.0 630.0 2472 261.0 115.7 14-74 AGS" 350-600 • A 65 For AGS fitting information,see publication 20.05 @ Gooseneck design,end-to-end dimension (sw)Segmentally welded steel #For use on cut grooved systems only.For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. t Chinese standard sizes www.victaulic.com 12 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.6'2 C6 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. iCt.`au�IC ovv I n,n1 C IPS CARBON STEEL PIPE-GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL U/ .0 I - JOB-#140d073 • • Grooved End Fittings NO.10 ELBOW NO.20 TEE • Tees, Crosses and True Wyes ,-ct0E1 aa>•a. C to LE C to Na 20 Tee 1.-c to E l ` � �E� N0. 35 Cross I N0.33 True Wye �� �� r 11 01 fi�� NO. 29M Tee with I c Threaded Branch to SE croTE .� a � �- (Ductile Iron') NO.20 NO 35 NO.33 NO.29M I No.20 No. 35 No 33 I I No.29M Size Tee Cross(so.) To Wye isw) TeL with Threaded Brooch Nominal A rox. No zeal I Outside 1 1 APProz. Approx. Approx. PP Size . Outside bia. 1 C to E IIII Weight Each C to E ' Weight Each C to LE C to SE Weight Eacn C to GE C to TE Weight Each Inches i Inches Inches 1 Lbs. Inches Lbs. Inches Inches Lbs. Inches Inches Lbs. mm rnm 1 mm kg mm kg - mm mm kg mm Inn, kg N II 1050 • 225 06 2.25 0.9 _ _ _ 2.25 2.25 06 20 26.9 _57 03 57 i 04 ! 57 57 03 _..... 1 '_315 ..._2.25 "-1 0 225 1 13 2.25 2.25 11 2.25 2.25 1.0 25 33.7 ,,. 57 0.5 ; 57 0.6 57 57......_. 0.5, , 57 57 --_-05 _..... ._._114_.. _......2... 1 r/, 1.660 2.75 - 13 2.75 21 j 275 2.50 15 2.75 i 2.75 ( 15 32 1 42.4 � 70 _0 7_ ! 70 ■ 1.0 E 70 64 0.7 70 70 1 0.7 _ ._,,,,_.__..._.__..-..._----'- ,_-__ ./--._..------ -_- 1EVz 1900 - 275 20 -V�1 275 25 275 ' 2.75 1 1.8 1 2.75 2.75 20 40 483 70 0.9 i 70 -._. 1.1 + 70 70 0.8 70 , 0 9 ..._..... ...........3. , -. ....._.. 2 2.375 3.25 "--30 ;. 3.25 3.8 3.25 • 2.75 2.5 3.25 4.25 3.00 50 60.3 ,,.._ 83 - 1.4 3 _83 1.7 83 • 70_ 1.1 1 83 ;m--108 1-- 1.4 2'/ 2.875 375 4.3 - 375 61. t 175 300 4.3 g 175 175 I 4.3 65 730 95 20 95 _=_. 28 ..._....3 95 76._....... _ _20.._. 95. . ...--95 I __.20 _. 3 75 3 75 2(sw 76.1 mm 3000 375 52 - - 95 95 5 2.4 ),___ 76.1 95 2.4 ._: - .. .. _ .._� ..._ 3 � 3.500 425 ! 6.8 �� 4.25 �, 10.5 ; 4.25 ' 3.25 6.1 4.25 ' 6.00 ! 6.8 80 1 88.9 108 3.0 108 4.8 108 83 ... .2:8..... ..108 ..........152 3.1.............. .._..._._,._ __.. . __... • 3y> t 4000 4.50(sw) 79 450 ; 115 450 330 1 96 4.50 450 7.9(sw) 90 101.6 114 ;: 3.6 i 114 I 5.2 114 89 4.4 114 11 - 73.6 ,. 1 4250 500 155 ) - i 5' 108•Omm , 1080 127 70 + _ __ 127 127 --.-. 70 -,,...,. . ..45.. _.._... a 4.500 5.00 11.9 1 5.00 1 15.8 ! 5.00 3.75 10.0 1 5.00 1 7.25 11.9 100 1 1143 127 54 127 1 72 r 127 95 45 1 127 1 184 5.4„ 4V 1 5.000 5.25(sw) 150 5.25 185 1 _ _ _ 525 525 15.0(5w) 120 i 1270 133 - 6.8 133 84 _ i , 133 133 -_.- 6.8 __......... 3250 5.50 178 _ ' - _ 540 540 8.1 133.0mm 133.0 140 8.1 t - i { 140 140 8.1_,-_- -... ... _..._.__.t. 5.500 5.50 1 178 ` , _ - 350 550 178 1397 mm 1397 140 _."., 8.1 -- 140 140 81 5 5563 5.50 178 5.50 20.0 550 4.00 15.0 ; 350 5.50 17.8(sw) 125 1 141.3 140 ! 8.1 140 9.1 140 102,,..,, ...6.8 . 140 _. ,ry 140 1 8.1 -- ...__._ r-- ._.. _._.s.._ 6250 650 271 1 _ ---_ -50 6 50 271 159.0 mm 1590 165 123 1 ., 165 165 123 6500 650 220 650 + 28.0 _ f'f _ 660 650 220 1651 mm ( 165.1 165 100 165 12.7 . 165 100 6 6.625 650 257 6.50 1 28.0 1 650 1 430 1 22.3 6.50 6.50 1 25.7(sw) 150 168.3 165 11.7 165 12.7 165 114 10.1 165 165 _ 11 7 _. ... ...-__ __..... .........._ ___...... I' ........._... t ...... _. 8 8.625 775 47.6 7.75 48.0 7.75 6.00 36.0 Z75 .7 75 47.6(sw) 200 j 2191 197 - 21.6 197 _ 21.8 197 152,.._. _ 16.3 .._197 .._ 197 21 6,_,,,, 10 10750 900 1 990 1 900 1 1213 900 650 699 900 900 730 250 2730 229 .. 449 -.._ 229 55.1 229 t 155 _ 31.7 . .229 ...,,...".229 331 _....'12. _._.....1 ,....... 12 ""f 12.750 1000 133.0 i 10.00 110.0 ) 1000 7.00 80.0 10.00 1000 1 99.0 300 f 323.9 1 254 60.3 , 254 49.9 1 254 l 178 36.3 254 254 44.9 www.victaulic.com 13 �Ct21UiaC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.02006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. - - °°- DCW 1 M fl1 0 IPS CARBON STEEL PIPE- GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL U I.U I Grooved End Fittings . ' NO.10 ELBOW NO.20 TEE Tees, Crosses and True Wyes wCto E� Na 20 Tee t. CtoEl �� CtoLE C10 N0.35 Cross St a& I ' GE -1 N0. 33 True Wye iI ' I' II N0. 29M Tee with 1I1jIi C Oil Threaded Branch E ° CtoTE (Ductile Iron *) �� ' �� _ SiE �_ NO.20 NO 35 NO.33 NO.29M t Nc `e0 Nc 35 Nc e: i No. ede Size ', Tee Cross(earl True Wye Isw'. Tee with Threaded trench Nominal Actual Approx. Approx. 1 Approx. Approx. Size Dut<ide Dia. C to E Weight Each C to E � Weight Each C to LE C to SE Weight Each ■ C to GE C to TE Weight Each Inches Inches Inches Lbs. Inches Lbs. Inches Inches Lbs. Inches Inches LGs. mm mm mm kg t mm kg I rem I mm Kg mm ' tern kg 149 14000 1100 1450 1100 198.0 11.00 Z50 1342 350 3556 279 65.8 279 89.8 . 279 191 60.8 ! - _.._.. .._.._. :.. __ .._ .._ _.o ._.__.m. - 3770mm 14000 1100 145.0 -'- 355.6 279 65.8 - - - - - - - 16 11 16.000 12 00 186.0 12.00 2500 12.00 800 1670 400 406.4 305 ` 84.4 305 113.4 305 203 . 75.7 - - - 426.0 mm t 16.000 1200 186.0 406.4 305 ' 84.4 - - - - - - 18# 18.000 1400 256.0 15.50 350.0 1550 8.50 2340 450 457.0 356 116.1 394 158.8 394 216 106.1 - !. - - 480.0 mmt 18D00 1400 = 256.0 457.0 356 1181 - - - - - - - - _1.725.. --.. 20# 20.000 - 1500 ' 339.0 1725 452.0 1725 9.00 281.0 �-���� �-- -........_. 500 508.0 381 153.8 - 438 205.0 ! 438 229 127.5 I - - - ,�. ._.. _..._....� ...w. ....� ;.._._ 530.0mmt 20000 1500 339.0 5080 381 1538 - - - - - - - 748 i 24000 1700 - 473.0 20.00 795.0 2000 1000 5230 550 6100 432 214.5 508 360.6 508 254 2372 .- 630.Ommt 264, 1700 4730 _-- 0.0 000 432 - 214.5 - - - - - - - - 350 600 v For ABS fitting information,see publication 20.05 "(sw)Segmentally welded steel #For use on cut grooved systems only.For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. t Chinese standard sizes IMPORTANT NOTE: Fittings size 26-487650-1050mm are available roll grooved for installation with Style 770 large diameter pipe couplings,Contact Victaulic for details. www.victaulic.com 14 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. V "r't'al.1I.C• onr l n7ni o IPS CARBON STEEL PIPE -GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL U I.U .1. • JOB#1406073 Grooved End Fittings NO.10 ELBOW NO.20 TEE • Cap it) NO. 60 (��J (Ductile Iron) NO.60 No,60 No.60 Sae Cap Size Cap .....- r..5. Nominal Actual T Approx. Nominal /KAUAI" T Appe s. Size Outside Diameter I Thickness Weight Each Size Outs de Diameter Thinness Weight Each Inches Inches Inches Lbs. Inches Inches Inches Lbs. mm mm mm kg mm 1 mm mm kg 'A 1050 0.88 0.2 6.500 100 73 20 269 22 01 165.1 mm 165.1 25 33 1 1315 0.88 6 6.625 � �- 100�� � 6.1 25 33.7 22 0.1 ..,....,,.150 1683 I 25 i 2.8 - - 1'4 1.660 0.88 0.3 8 8.625 1.19 1 13.1 32 42.4 22 0.1 200 219.1 30 5.9 11/2 1.900 0.88 0.5 10 10.750 1. 1.25 € 21.0 40 48.3 22 0.2 250 273.0 32 9.5 2 2.375 0.88 0.6 12 12.750 1 1.25 35.6 50 60.3 1 22 0 3 300 323.9 32 16.2 21/2 2.875 ( 0 88 1.0 14# 14.000 __-9.50 . 65 73.0 1 22 0.5 ..T_..,350 3556 241 -.-._ 76.1mm 3000 088 1.2 16# 16000 10.00 1 76.1 22 0.5 400 406.4 ...... .- ..__._.._ _ 254 i 3 3.500 0.88 1.2 186 18.000 11.00 , 80 88.9 1 22 - 0.5 450 457,0 279 31h 4.000 1 0.88 2.5 2 2 00 12.00 90 101.6 500 ■X0 3.0 301 106.0 mm 4250 , 1.00 23 24# 24.002 , , 108.0 'r 25 1.0 600 610.0 4 4 I. 1.00 2.5 14-24 AGS" For AGS fitting information,see publication 20.05 100 114.3 143 [ 25 1.1 .350.-600 v 41/2 5.000 100 2.5 IMPORTANT NOTES: 120 127.0 25 1.1 133.0 mm 5250 100 4.5 •Steel dish caps available through 24"/600 mm,contact Victaulic. 133.0 25 2.0 No.60 cap is not suitable for use in vacuum seance with Style 72 or 750 couplings. 5 500 1.00 4.5 No.61 bull plugs should be used,see pg.35. 1397mm 139.1 . 25 20 #For use on cut grooved systems only.For roll grooved systems,Victaulic 5 5.563 i 1.00 46 offers the Advanced Groove System(AGS).For pricing and availability of cut 125 141.3 25 21 groove fittings in this size,contact your nearest Victaulic sales office. 1 159.0 mm 6.250 ; 1.00 6.8 159.0 s 25 31 www.victaulic.com 15 CtaUlliC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. DM/ I nV na act IPS CARBON STEEL PIPE - GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL U I•U 1 is • '41.6 Grooved End Fittings .. 1_ NO.10 ELBOW NO.20 TEE Concentric/Eccentric Reducer NO. 50 Concentric E NO. 51 Eccentric Irto El (Ductile Iron #) EtoE-i NO.50 II 1(1 NO.511 No. 50 Nc.51 Nc 5C Nu 51 Size Concentric Reducer Eccentric Reducer Size Concentric Reducer Eccentric Reducer 1 Nominal I Approx. Approx. Nominal Approx. Approx. Size j E to E Weight Each E to E Weight Each Size E to E Weight Each E to E Weight Each Inches Inches Lbs. i Inches Lbs. Inches Inches Lbs. - Inches Lbs men 1 mm kg 1 mm. kg mm mm kg mm kg 11/4 x _1.9 ! 3'x 1/2 3 7.50(sw) • 2.0 9.50 70 32 x 20 + 0.9 _ 90 x 80 64 0.9 241 3.2 1 ...,,..._._. 1.9 _ � 4 1 3 00"'(sw) 3.0 00 65 75 + 0.9 100 x 25 76 1.4 330 2.9 1'h ' 1.4 17. , 4.6 40 x 20 ! + 0.6 32 + 2.1 1 2.50*(sw) 0.8 8.50 4.5 11/2 1000 i 6.9 10.00 8.1 25 1 64 04 216 2.0 40 254 3.1 254 3.7 1 /. - 2.50*(sw) = 1.0 _ r _ 2 3 00*(sw) 2.4 4.00(sw) 3.3 32 64 0.5 m 50 __ 76 1.1 102 1.5 ._..._....._.a___........... 7.._. ..�. .....�..,... •.._.m..___.._._._ _.._ . 2 xG 2.50'(sw) ! 0.9 9.00 2.0 2'h 3.00'(sw) 2.7 4.00(sw) = 3 4 50 x 20 64 0.3 229 0.9 65 76 12 102 15 1 2.50'(sw) !. 0.7 9.00 2.3 3 = 3.00'(sw) = 3.2 4.00(sw) • 3.5 25 64 0.3 229 1.0 80 76 1.4 102 1.6 11/4 . 2.50 (sw) 1.2 = 9.00 4.6 3'/2 3.00(sw) I 2.9 10.00 8.0 32 ! 64 0.5 229 2.1 90 76 1.3 254 3.6 11/2 2.50'(sw) . 1,0 9.00 4.6 5 2 11.00 5 9.0 11.00 5.2 40 . 64 0.5 229 2.1 125 x 50 279 4.1 279 2.4 •Ph ' 1.3 3.3 21/2 11.00 i 11.0 11.00 10.8 65 x 20 + 0.6 - + 1.5 65 279 5.0 279 4.9 1 9.50 = 3.6 9.50 3.5 3 4.00(sw) 55 11.00 11.1 25 64 1.5 241 1.6 80 i 102 2.5 279 5.0 11/4 r 2.50*(sw) 33 9.50 4 . 3.50(sw) 4.3 - 5.00(sw) i 12.0 32 I 64 1.5 ! 241 + 100 89 1.9 - 127 5.4 ____ a __._.. _............. __.._. ._ _....._. ........._; _...... ....._.._..... e........._... ...-......._.... 11/2 2.50'(sw) 3.6 9.50 3.7 6 1 . 4.00'(sw) i 5.0 11.50 i 14.5 40 64 1.6 241 1.7 150 x 25 , 102 2.3 292 6.6 2 2.50(Sw) 39 9.50 = 43 ='h 55 50 64 1.8 241 2.0 40 + 2.5 + + 3 3/"_ 1.5... •-...._ 4.5 2 4.00*(sw)..__. 6.6 11.50 = 14.5 80 x 20 ! + 0.7 + 2.0 50 102 3.0 . 292 6.6 1 2.50"(sw) 1.3 9.50 4.8 2'h 4.00"(sw) 6.4 11.50 14.2 25 64 0.6 241 2.2 65 102 2.9 - 292 i 6.4 1V 3.0 4.8 3 4.00"(sw) ; 6.4 5.50(5w) 15.0 32 + 1.4 + 2.2 80 102 2.9 140 6.8 Ph .. 2.50'(sw) 5.I 9.50 51 4 400(Sw) 6.5 550(sw) 1 17.0 40 64 2.3 241 2.3 100 102 2.9 140 77 2 2.50'(sw) 1.6 3.50(sw) 6.0 5 r 4.00(sw) i 6.4 5.50(sw) 17.0 50 64 0.7 89 2.7 125 r 102 2.9 140 7.7 242 i 250"(sw) 18 350(sw) 70 8 2'h 1600*(sw) = Z9 12.00 261 65 1 64 0.8 89 32 200 x 65 - 406 i 36 305 11.8 761 2.50(5w) 21 3 5.00(sw) = 9.3 12.00 220 64 1.0 80 ! 127 4.2 305 10.0 www.victaulic.com 16 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 1CtauI1�' 0 CV I n7na 94 IPS CARBON STEEL PIPE- GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL U / •U I -- _ -__---dOB-#4406073 • Grooved End Fittings NO.10 ELBOW NO.20 TEE Concentric/Eccentric Reducer NO. 50 Concentric E NO. 51 Eccentric I'to El a to E (Ductile Iron #) EE11 I NO.50 NO. No.50 I Na.51 No 50 Na 5 Size Ccnce-46c Redu:cr E¢en.oc Reducer Size ..')crane R■Oucef ELL,': Ru_W_i i I 1 1 Nominal Approx. Approx. Nominal I Approx. i 1 Approz. Size E to E Weight Each E to E Weight Each Size E to E Weight Each 1 E to E 1 Weight Each Inches inches Lbs Inches Lbs. Inches Inches Lbs. 1 Inches i Lbs. mm mm kg mm kg man mm kg 1 mm kg 8 4 5.00(sw) 104 12.00 23.0 #18 x 12 15.00 91.0 1500 91.0 200 x 100 127 4 8 305 10 4 450 300- 381 I 413 i 381 41.3 5 500(sw) 1 11.6 12.00 13.9 14 15 00 91 0 r 1500 91.0 175 . 127 52 305 10.4 350 381 413 I 381 I 41.3 6 500(sw) 4 11.9 1 6.00(sw) 24.0 16 15.00 91.0 15.00 91.0 150 127 ■ 54 I 152 109 400 381 41.3 i 381 413 10 4 6.00(sw) 19.7 13.00 32 0 #20 10 20.00 110.0 1 20.00 177.0 250 x 100 152 8.9 330 14 5 500 x 250 508 49.9 508 ' 80.3 5 343 Sib 12 20.00 t 1200 i 20.00 I 120.0 125 + 15 6 + 15 7 300 508 1 54.4 - 508 1 54-4 ■ 6 6.00(sw) I 20.0 13 00 36.9 14 20.00 1490 i 20.00 149.0 150 152 9.1 330 16.7 350 508 1 67.9 508 67.9 8 6.00(sw) 22.0 700(sw) 21.6 16 20.00 C 120.0 i 20.00 120.0 200 152 10.0 178 9.8 400 508 54.4 508 54.4 12 4 1 44.0 14 00 48 0 18 20 00 136.0 1 20.00 136.0 300 x 100 . + 1 20.0 356 21.8 450 J 508 j 61.7 508 I 61.7 6 700(sw) 246 1400 50.0 #24 10 20.00 i 1420 1420 2000 I 142 150 178 - 11.2 x 356 22.7 600 250 508 644 508 ' 64.4 0 700(sw) 52.0 1400 535 12 20.00 150.0 2000 150.0 200 178 23.6 { 356 24.3 300 508 1......,._ 680 508 68.0 10 7.00(sw) 39.0 14.00 57.0 14 20.00 162.0 20.00 162.0 250 178 ' 1Z7 356 259 350 508 735 508 1 735 4 14 6 13.00 650 13.00 60.0 16 20.00 162.0 I 20.00 162.0 350 x 150 330 29.5 330 27.2 400 508 73.5 508 73.5 8 13.00 i 65.0 13.00 60.0 18 20.00 162.0 20.00 162.0 200 330 i 29.5 1 330 27.2 450 508 73.5 1 508. 735 10 13.00 r_-_ 66.0 ) 13.00 650 20 ; 20.00 151.0 20.00 190.0 250 330 1 29.9 ____ 330 29.5 500 508 68.5 508 86.2 12 13.00 68.0 13.00 66.0 14 24 AGS- For AGS fitting information,see publication 20.05 300 330 tt 30.8 330 29.9 350-600 416 8 1400 730 1400 73.0 x + Contact Victaulic for details. 400 200 356 331 355 33.1 . Available with male threaded small end No 52. 10§ 1400 1 730 1400 73-0 250 356 331 355 33.1 # Ductile Iron except those marked(sw)which are segmentally welded steel. 12 1400 i 73.0 1400 73.0 300 356_ ` 33.1 355 33.1 IMPORTANT NOTE: 14 1400 73.0 4.00 73.0 Steel eccentric reducers available through 307750mm,contact Victaulic for 350 356 33.1 355 33.1 dimensions. #18 x 10 1 15.00 1 910 15.00 91.0 #For use on cut grooved systems only.For roll grooved systems,Victaulic 450 250 381 i 413 381 41.3 offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. §cast fitting available for J.I.S.size.Contact Victaulic for details. www.victaulic.com 17 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. iCtau! nom 9A Orli I JOB#1406073 � ". Grooved End Fittings NO.10 ELBOW NO.20 TEE WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. • NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. US&WORLD HEADQUARTERS CANADA CENTRAL AND SOUTH AMERICA P.O. Box 31 905-884-7444 1-610-559-3300 Easton, PA 18044-0031 USA 905-884-9774(fax) 1-610-559-3608(fax) 4901 Kesslersville Road viccanada @victaulic.com vicalgvictaulic.com Easton, PA 18040 USA EUROPE ASIA PACIFIC 1-800-PICK-VIC(1-800-742-5842) 32-9-381-15-00 86-21-54253300 1-610-559-3300 32-9-380-44-38(fax) 86-21-54253671 (fax) 1-610-250-8817(fax) viceuro@victaulic.be vicap@victaulic.com pickvic@victaulic.com UNITED KINGDOM MIDDLE EAST www.victaulic.com 44(0) 1438741100 971 4-883-88-70 I I III II IIIIII 'll Inllll 11 44(0) 1438313883(fax) 971-4-883-88-60(fax) WCAS-6M8PF7 viceuro@victaulic.be UPDATED 9/2006 07.01 1449 REV L 18 iCtauIiC` VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. —.----- - n Al • 1; • . . ; •"'.. si. •DOTJ T' ' -. - .. , JOB#1406073 FireLock® Rigid Coupling L vdS "` A 1JiZd L see iwles ar page 9 SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 005 WITH VIC-PLUSTM GASKET SYSTEM (NORTH AMERICA ONLY) FireLock®Style 005 rigid coupling has a unique, patented angle-pad design which allows the housings to offset while clamping the grooves. By permitting the housings to slide on the angled bolt pads,rigidity is obtained. Support and hanging requirements correspond to NFPA 13 Sprinkler Systems.Angle-pad design permits assembly by removing one nut/bolt and swinging the housing over the gasket.This PATENTED reduces components to handle during assembly. Style 005 FireLock coupling are designed and recommended for use ONLY on fire VICP/t/S protection systems. Casket sy,elm Vic-Plus' Gasket System: In North America,Victaulic®offers a gasket system which requires no field lubrication on wet pipe systems that are hydrostatically tested.The Vic-PlusT"System (patented)is dry,clean,and IJ.� 1r) non-toxic. It reduces assembly time substantially and eliminates the mess and chance of over- f14 •I lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook(1-100)for r. �k supplemental lubrication requirements and dry pipe fire protection system notes. Ira" Exaggerated for clarity III LISTING/APPROVALS The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Relater)Working Pressure-psi Related Working Pressure-psi I Related Working Pressure-.ps Pipe Size Pipe Size Pipe Size Srh. Inches all ' ULC FM .Sctl. Inches :UL ULC FM Sch i Inches UL ULC FM 5 t 1 Y.-3 j 175 175 175 EL 11/4 2 300 N/A N/A MT 'Y 2. 300 N/A N/A {1%"-4, 350 350 FT 1 CVs 2 300 N/A N/A STF r 1 4', N/A N/A 300 10'401 5 8 300 300 300 EL 4 6 300# N/A 300 Stedy 11/4 21. N/A N/A 300 Th • BLT ;1V. 2'i 300 300 N/A FE 11/4 41 N/A N/A 300 TF 3 B N/A N/A 300 OF 111/4-4 300 300 300 GAL 71/a 2 300 N/A N/A WLS 1'Vs 2 300 300 ! N/A DT j1 ' 2 300 3 00 '/N/A MI 1 7' 300 N/A N/A XL 1'Vs 3 300 I 300 300 /. � _.,,_..._. EF i.1'/-4! 175@ N/A 175 MF l.n 4 300 N/A _ 300' FM approved for service in 1'h—4"pipe. #UL Listed for service up to 4"pipe only. @ UL Listed for service up to 3'only. • II JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victauiic.com 19 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ilCt'aIIU�Ilt'i DM/ I 1n n9 1 IPS CARBON STEEL PIPE - FIRE PROTECTION PRORMV ISARSONS MATERIAL SUBMITTAL 1 U.U Z JOB#1406O7 ^ FireLock® Rigid Coupling ' STYLE 005 WITH VIC-PLUST''GASKET SYSTEM (NORTH AMERICA ONLY) DIMENSIONS I , Max.Work Max.End Allow.Pipe Bolt/Nut@ Approx. S¢c iPres,ur,c Load End Sep.I No-Size Dimensions-Inches/1nm Each V �2� cr Nominal Outside ,AL f'►rA u Mom Size Diameter PSI Lbs. Inches Inches • Lr �� ,t�hes,'mm 1 lnchestmm kPa N mm mm X Y 2 kg M,I ►�� �I1i� 660 350 755 0 0 2.75 1 450 88 2 �� 32 424 2413 3370 1.2 2-%x2 a 70 114 148 05 ............. r 1 1/2 1900 350 990 0.05 3.00 ■ 4 75 1 88 1.2 40 483 2413 4415 12 2 s/°x2/s 76 : 121 I 148 0.5 Rated for wet and dry sprinkler systems at 2 2 375 350 1550 0.07 2-s°x2/ 150 i 5 25 1 88 1.6 350 psi/2413 kPa for T'/°-4"/32-100mm SO 603 {, _2413 ..6900 _.17 89 1 133 148 07 sizes and 300 psi/2068 kPa for 4 Ye-8'/108 2 ......_.._ _ __................... P 2/z 2 875 350 7770 0 07 4.00 S 75 1 88 1.9 -200 mm sizes;Schedule 10 roll grooved or 65 73.0 2413 10110 7 2-Vs x 2/' 102 1 146 148 .09 Schedule 40 cut or roll grooved steel pipe. - 3 "' 3 000 350 2375 007 413 5 75 1 88 1.9 Style 005 is rigid and does not accommodate 76'mm 2-'�x 21/2 expansion,contraction or angular deflection. _. .. _ _761 2413 11010 _17 105 146 148 09 3 3 500 350 3365 0.07 ,/ 4.63 613 188 2.1 80 88.9 2413 14985 1 °x 2 a 118 � 156 148 1.0 4 4 500 350 5565 016 2_,/°x 2.4 5.75 7 25 213 3 1 100 ! 1143 2413 24770 41 146 ' 184 54 14 '08.0 mm 4.250 300 4255 0.16 I.2-1/2x 5.63 725 213 3.1 1080 2068 18940 41 143 1 184 54 1 14 5 5.563 1 300 7290 0.16 � 6.88 . 900 2.13 1 4.5 125 141.3 -...,,..,2068 32445 41 2-k x 3 175 1 229 54 E 2.0 t 5250 I 300 6495 0.16 6.63 ■ 9.00 • 2.13 4.5 1330mm 2 hx2V. 1330 2068 28900 41 .168 1 229 54 { 20 139.7 mm 5500 I 300 7125 0.16 2-1/2x 23/4 6.88 1 9.00 i 2.13 4.8 139.7 2068 31715 41 175 229 54 1 22 6 6625 ' 300 10340 0.16 2- 8.00 10.00 2.13 1 5.0 'k x 3 150 1683 2068 46020 41 203 254 53 23 159.Omm 6.250 300 9200 016 2 Vi x 2;4 7.63 10.00 : 2.13 5.5 1590 a .2066 40955 4 194 ` 254 . 54 ; 2.5 6500 300 9955 0.16 8.15 f 1000 2.13 3 5.5 765.1 mm 2-'hx3 1657 2068 44293 41 207 1 254 54 % 2.5 8 8625 300 17525 0.19 2_Vax41, 10.50 1 1314 { 263 11.3 200 219.1 1 2068 78000 4.8 267 1 334 67 5.1 • Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI) steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for perfor- mance on other pipe. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. t The allowable pipe separation dimension shown is for system layout purposes only.Style 005 couplings are con- sidered rigid connections and will not accommodate expansion or contraction of the piping system. Number of bolts required equals number of housing segments.Metric thread sire bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. § Style 005 couplings are VdS and LPC Approved to 12 Bar/175 psi. www.victaulic.com 20 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.02006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. sCtaUIIC� 1nn9 Div r IPS CARBON STEEL PIPE - FIRE PROTECTION PSRRI3iRSONS MATERIAL SUBMITTAL 1 U.UL JOB#140• FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUST"^ GASKET SYSTEM (NORTH AMERICA ONLY) MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel(North America); red enamel(Europe) • Optional: Hot dipped galvanized Gasket: • Grade"E"EPDM-Type A Vic-Plus"Gasket System Li (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Vic-Plus°'Gasket System,requiring no field lubrication for most installation conditions. • Grade"L"Silicone Recommended for dry heat,air without hydrocarbons to+350°F and certain chemical services. For dry services,Victaulic continues to recommend the use of Grade"E"Type A FlushSeal®Gasket. Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. A Standard gasket and FlushSeal gasket approved for dry pipe systems to-40°F/-40°C. Based on "typical" pipe surface conditions,supplemental lubricant is recommended for services installed below O'F/-18°C and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water.Supplemental lubrication may also be required on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams.Victaulic continues to recommend the use of FlushSeal gaskets for dry services. www.victaulic.com 21 ictaulic`' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.*2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. - oft I in an :u ;I • • 'T.-re l �I WO •thrt4U6073 i lli�1 r� �_ �iw � '... FireLock® Rigid Coupling • STYLE 005 WITH VIC-PLUS"" GASKET SYSTEM (NORTH AMERICA ONLY) GENERAL NOTES WARNING: Depressurize and drain the piping system before attempting to install, remove,or adjust any Victaulic piping products. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. IIIII1111111111N111111 WCAS-697KR4 For complete contact information,visit www.victaulic.com 10.02 1538 REV I UPDATED 9!2006 22 ct auIacc VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 1n n7 • Standard Flexible Coupling ® �S LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 77 Style 77 couplings are designed with cross-ribbed construction to provide a strong component for pressure piping systems.Sizes yn-12720-300mm are two-piece housings. For 14-24"/350-600mm sizes,Victaulic offers the Advanced Groove System(AGS)line of products. Request publication 20.03 for information on the flexible Style W77 AGS coupling. All sizes are provided with plated bolts and nuts. Galvanized and stainless steel housings are also available. Independent testing has shown the Style 77 coupling to be an effective stress relief � and vibration attenuation device providing performance superior to braided steel and elastomeric arch-type connectors when used in close proximity to the source of vibration. \ N.Za Refer to entt testing vibration Independent testing has shown that Victaulic Style 77 flexible couplings provide exceptional functionality during and after earthquake conditions. Refer to 26.12 for further information. I- Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel. • Optional: Hot dipped galvanized and others. Coupling Gasket: (specify choice*)f • Grade"E" EPDM (All other sizes) EPDM (Green color code).Temperature range-30°F to+230°F/-34°C to+110°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrite Nitrile(Orange color code).Temperature range-20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. ' Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. • Optional:Type 316 stainless steel,Grade B-8M,Class 2. t Supplemental lubricant is recommended for services installed at or continuously operating below 0°F/-18°C. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. jet a V Ilc' REV 1 06.04 1 CARBON STEEL PIPE-GROOVED COUPLINGS 1)0.U'F Standard Flexible Coupling STYLE 77 DIMENSIONS Max Weak AIIca.Pipe Bolt/Nutha i Approx. S u Pra s ro.' Max Ft c I cod" Led Sep. Deflect.K.(..3- -Size D;mensans-Inches!mon Wgt.Each Actual l , I Nca ntal Outside Size Diameter j Per Pips Inches I Inches , psl 1 Lbs. (robes Cplg. 1 In./14. Inches Lbs. RIM rem ( kPa i N rear Deg. mm/re mm R Y Z i kg 14 1.050 1,000 865 - 0-0.06 072 213 400 175 t.1 20 26.7 6900 3850 0-1.6 .s-24 60 2-3/B x 2 54 102 44 0.5• 1 I 1315 1,000 1,360 0-006 1 0.57 2 38 4.12 1 75 1.2 25 33.4 6900 6050 0-16 2°-43' 48 : 2 3/8 x 2 61 105 44 0.5 114 1 1660 1 000 2,160 0-0.06 - 2°_10, 0A5 2 65 5 00 1.88 2 0 37 1 422 6900 9610 0-1.6 38 2-'h x 2 67 127 48 0.9 1'h T� 1.900 1,000 2,835 0-0.06 040 313 5 38 1.88 2 1 40 ' 48.3 6900 12615 0-1.6 1"-56 33 2-kx , � 79 137 48 1.0 2 2.375 1,000 4,430 0-0.06 7.-31' 0 32 ! 2-'h x 21/2 3 63 ..__5 88 1.88 2 6 SO 603 6900 19715 1 0-1.6 26 92 149 48 12 2.664 1000 3955 0-0.16 033 343 573 1.9 30 ,7.Omm 570 6900 17597 0-1.6 1'-34 27 2-h x 21/2 87 146 48 1.4 I 2: 2.875 - 1,000 6,90 0-0.06 1'-15 2-4 0.26 i 5 234 425 650 1138 3.1 65 730 6900 28880 0-1 6 22 108 165 48 1.4 3.000 1,000 7,070 0-0.06 026 438 663 188 32 76.1 mm 761 6900 31460 0-1.6 1'-11 22 2-h x 23/4 t 1 1 168 48 1.5 3 3500 1,000 9,620 0-0.06 022 500 713 18S 3.7 80 88.9 6900 46810 0-1.6 1 -2' 18 .. 2-Va x 2 39 27 181 48 1.7•31 4.000 1,000 12,565 0-006 0'-54 019 2-5/8x341 5.63 8.25 188 56•90 101.6 6900 55915 0-1.6 16 143 210 48 2.5 .4. .m.�_-.1.00 .....2.13 67 4 4500 1,000 15,900 0 0 13 1 a 4 0 34 2-5/8 x 3 Y 6.13 8 88 100 114.3 6900 70755 0 3.2 28 156 226 54 3.0 4.250 1,000 14,180 0 0.13 0.35 600 8.63 2.13 1..10 I OS.Omm 108.0 6900 63100 0-3.2 1°-41 29 2-lnxfi2' 152 219 54 5.0 5 5.563 1,000 - 24,300 0-013 1°-18 0.27 2-'4x4'4 775- 1063 7.74 10.6 125 1413 !........6900 108135 0 3.7 ...,,...,,.23 197 270 34 48 5.250 1,000 21,635 0-0.13 028 763 1038 2.13 10.0 1330 mm 133.0 6900 96175 0-3.2 1°-21 24 _ 2-20x108 1 194 264 54 45 139. mm 5.500 1,000 23,745 0-0.13 r-18 0.28 - 863 2-20x108 10 65 2.13 10.0 139.7 6900 105665 0-32 24 219 270 54 45 6 6.625 1,000 34,470 0 0.13 1.-5. 0.23 2-33/4ax4V. 863 1188 2.13 120 150 1 168.3 6900 153390 0-3.2 18 2'9 907 54 5.4 6250 1,000 30,665 0-0.13 0.24 863 1150 2.13 13.2 159.Omm 1590 6900 136460 0-3.2 1°-9 20 2-20x108 7'9 292 54 6.0 6.500 1,000 33,185 0-0.13 023 8.88 11 63 2.13 13.2 65.1 mm 165.1 6900 147660 0-3.2 1 -6' 19 2-34 x 4'/. 226 795 54 6.0 Table continued on page 3. See notes on page 3. i Y • r-z1 . Y Z 1 Y . -NZ r.4.... .... �r,.,.� I Im,„...,.. 40 1 it (0)fir s.:.. ..,1 14-22"SIZES 24'SIZES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. iCtauIiC. 06.04 2 REV I CARBON STEEL PIPE-GROOVED COUPLINGS 1/0.U4+ ° Standard Flexible Coupling STYLE 77 • DIMENSIONS hl,,,..Work Alice. P,pc 'I R ,N�:< Ape°,. Size Presxre Max.End Loan' Ere-Sep.' Deflect F'.C.- Nc Sae D.mens;c r.-Inches/mm Met.Each Actual Nominal Outside Size Diameter Per Pipe Inches Inches psi Lbs. Inches Cpig• InJFt, Inches LIFe mm 1 mm kPa N mm Deg. minim mm X Y Z kg 8§ 8.625 800 46,740 • 0-013 0.18 11.00 14 75 2.50 20.8 200 2191 ... 5500 207995 0-3.2 0 50 14 E. 2 7/8 x 5 279 375 63 9 4 10 g l 10750 800 71280 0-013 : " 0.14 13.63 1713 2.63 31.1 250 273.0 5500 326100 0-3.2 0 -40 12 € 2 1 x 6 346 i 435 67 14.1 12g 12.750 j 800 102900 0-0.13 0°-34 012 ", 2-1x6Yx 1563 = 1925 • 2.63 278 300 3239 3- 5500 453900 0 3.2 9 ! 397 489 67 12b 14* i 14.000 l 300 46,180 l 0-013 i 011 I 16.63 I 1988 2.88 35.6 0°-31' � 4 1 x3Yz 350 355.6 2065 205500 0 32 9 t 422 505 73 16.1 377.0 14.842 300 51,875 0-0.13 011 1739 20.96 2.8 48.8 377.0 2065 230,845 0-3.2 0°-31' 9 4-1 x 3 Yz 442 531 71 22.1 ' 15A 15.000 300 53,000 t 0-0.13 0°-29 010 4 1x5Yz 1788 2163 3.00 ; 48.8 375 381.0 2065 235850 0-3.2 9 1 454 549 76 22.1 16 A 16.000 i 300 60320 0-013 i 010 1900 22.13 3.00 511 400 406.4 2065 268425 0-3.2 0°-2T 9 4-1 z 3 i� 482 562 76 23.2 426.0mmp 16772 300 66245 0-0.13 0°-27 010 4-1x3�%z 1969 2292 192 56.7 426 2065 : 294,795 0 3.2 9 500 581 74 ..,_..,...257 18A i 18.000 300 i 76340 • 0 013 i 908 • 2138 2450 313 644 0°-24 4 1 x3h 450 457.2 2065 339710 0 3.2 7 543 622 • 80 = 292 18.898 300 84,105 0-0.13 008 2238 2586 ` 304 772 4800mmp 48 2065 374,265 0-3.2 0°-24 7 4-1x3,: 569 ' 655 t 77 35 70A 20000 300 94,000 0-0.13 0.08 2363 ! 2725 313 91.2 0°-22 4 11/8x4 500 5080 `2065 i 418300 0 3.2 ! 7 600 !. 692 80 r 414 • 20.866 300 102,535 0-0.13 0.08 2479 278 307 I 91.7 530.0 mm U 530 2065 456,280 0-3.2 0° 22 7 4 1 1/8 x n 617 704 l 77 41.6 274 22.000 300 114000 0 0.13 007 7575 2950 I 313• 92.0 550 559.0 2065 507300 0-3.2 0` 19 6 4-1 178 x 4 654 749 • 80 ( 41.7 22.835 300 102,380 0-0.13 0 07 26 76 ! 30.01 312 92.8 5800mmN 580 2065 455,591 0-3.2 0°-19 6 4-11/8x4 680 762 79 42.2 74: 24000 250 111000 0-0.13 0.07 27 75 31.25 3.13 940 0°-18' 6 11/8x4 600 1 6096 1725 502850 0-3.2 6 704 794 • 80 = 42.6 630 mm p i 24 803 250 102,790 0-0.13 0.07 28.42 37 16 312 96.8 630 1725 457,416 0-3.2 0°-18 6 6-I 1/8 x 4 722 817 79 44 34424 - ABS` See Style W77,Publication 20.03- §Couplings 8,10,12 7200,250,300mm sizes available to JIS standards.Refer to Section 0617 for details. Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:5046 for 3/4-31/W/20-90 mm;25%for 4"/100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. *For cut groove systems only.For 14-247350-600 mm Roll Groove systems Victaulic offers the Advanced Groove System(AGS)line of products.Request publication 20.03 for information on the Style W77 flexible AGS coupling. p CIS size product is designed with two housings and requires two bolts. t Y 1 r-z-1 I Y -0.1 Z k- < Y -.I Z I.- I ME u-12'SIZES 411� � `7/ :cc 14-22'SIZES 24"SIZES www.victaulic.com �Ctauliid VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. RFV I 06..043 Standard flexible Coupling STYLE 77 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. • NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. 113 111 I N 1111111111111 WCAS-6UBJ5N For complete contact information,visit www.victaulic.com 06.04 1469 REV I UPDATED 6/2007 ictaLJlic' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.ID 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 06.04 JOB#1406073 - 71Zf 7d . • Reducing Coupling O ® (yds) SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 750 f The Style 750 Reducing Coupling permits direct reduction on the piping run. Designed to replace two couplings and a reducing fitting,the Style 750 features a special reducing gasket for pressure responsive sealing.A steel washer which prevents telescoping of the smaller pipe inside the larger pipe during vertical systems assembly is available upon request. • u all Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel • Optional: Hot dipped galvanized and others Gasket: (Specify choice*): • Grade"E"EPDM(All other sizes) EPDM (Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional:Assembly Washer: Galvanized,carbon steel Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com 27 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA r---.. I, PM/ u na 110 1 IPS CARBON STEEL PIPE-GROOVED COUPLINGSCAMP PARSONS MATERIAL SUBMITTAL Ub.Uo G: i.i ' Reducing CouplingLI ® ids 4 . SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 750 • DIMENSIONS Max.11k34, 1, Mica...Pipe Bolt/Nut@ Approx Size P,ess urt ' ' Max.Eno Load End Sep Di`lect. F No-S'IC Dimens"on_-Inches mm Wgt.Each Nominai I Per Pipe Size psi Lbs. 1 Cplg. In./Ft. Lb>_ 9ncbeslmm kPe N 1 Inches/mm Deg. minim inches X Y 2 kg 2 1 350 - 1000 0-0.07 ` 0.20 3.38 • 5.28 1.88 27 x - 0°-57' 2-Yex2 50 25 2410 4450 0-1.8 i 17 85 134 48 ( 12 173 350 1000 0-0.07 0.20 338 5.28 1.88 1 2.0 -57 3/4 x2 40 2410 4450 0 1.8 0° E ,,,.1.7 _2- 85 134 48 1.0 213 2 500 2215 0-0.07 0.16 4.00 5.93 1.88 i 3.1 65_... x 50 3450 9850 0 1_B 0 47' 14 2 /a x 2 102 i 151 48 i 14 76.1 mm x 2 350 1550 0-0.07 !. 0.16 4.36 I 6.63 1.88 4.6 50 2410 6900 0-1.8 0'-47' 14 2-4 x 284 111 168 48 2.1 3 2 350 1550 0-007 0.13 475 7.13 188 49 80 x 50 2410 6900 0-1.8 0'-39 11 2-'hx23/a 121 181 E 48 2.2 273 500 3250 0-007 0.-39, ? 013 475 7.13 i 1.88 4.3 65 3450 14460 0-1.8 11 2-h x 28i : 121 181 48 2.0 ■ 350 2275 0-0.07 0.13 !. 4.75 713 188 4.2 889mm x 76.1 mm 2410 10125 0-1.8 0°-39' ( t1 : 2-Yz x24b 121 181 48 19 4 x 2 350 1550 0-0.13 1°-19 0.28 2-4hx3Y4 6.25 890 225 8.1 100 50 2410 6900 0-3.2 25 159 • 226 57 3.7 2/a 350 2275 0 013 : 1. 19 0.28 2-s j 625 890 225 86 /8%3Y4 65 2410 10125 0 3.2 - 25 159 226 57 3.9 3 500 4810 0 0.13 i'-19, 0.28 2-s/8 x 3'/4 600 8.90 225 I 6.7 80 3450 21400 0-3.2 .25 152 226 57 3.0 350 2275 0-0.13 0.28 / 6.25 8.90 225 , 69 1,43mm x 76.1 ruin 1 -19 2-54x3/a 2410 10125 0 3.2 25 / 159 226 57 ' 3.1 5 4 350 5565 0 0.13 0 22 7.18 10.7o 2.13 11 2 x 1'-3 2-14x4'3 125 100 2410 24765 0 3.2 i 19 182 272 54 .-_.._5,1■ 6 x 4 350 5565 0-0.13 0'-52 i 0.18 2-3/4x474 8.63 11.90 2.25 16.7 150 100 2410 , 24765 0-3.2 15 : 181 302 57 i 7.6 5 350 8500 0-013 0°-52 018 2-74x4%4 8.31 1190 225 i 129 125 2410 i 37825 0-3.2 ' 15 211 302 57 1• 59 _.................. 165.1 mm x 4 350 5565 0-0.13 0.19 8.63 1190 225 152 100 2410 24765 0 3,2 0'-55 Z-1'<x4'/e 16 219 302 57 6.9 8 x 6 350 12000 0-0.13 0°-38' 013 2 3/ex5 10.81 1488 2.50 224 200 150 2410 53400 • 0-3.2 11 275 378 64 10.2 Refer to notes on back cover. Style 750 Reducing couplings should not be used with end caps(#60)in systems where a vacuum may be developed.Contact Victaulic for details. 1-s Y k-Z->.I Y.1111%....� Z 4i �co� fai im 111r It� 1 - wiL, °IJ www.victaulic.com 28 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ,CtauI.0 nA nix 9 P V IJ IPS CARBON STEEL PIPE-GROOVED COUPLINGS.cipiMP PARSONS MATERIAL SUBMITTAL U b.U o JOB#1406073 Reducing Coupling UL FM ® (Vds) SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 750 g FLOW DATA HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables.All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING Equiv.Pipe Egmv_Pipe Size Length Sze Length Nominal Nominal Sze See D . Size Sin.pia inches/mm i Feet/in Inches/mm Feettm 2 1 5.9 1 2 2.7 50 x 25 1.8 25 x 50 0.8 1K 2.0 1Ye 2 1.9 40 0.6 40 x 50 0.6 21/2 2 1.9 2 21 1.0 65 x 50 0.6 50 x 65 0.3 76.1 mm x 50 0.6 76.1 mm 0.3 3 2 5.5 3 ...... 3.5 80 x 50 1.7 80 1.1 2 Vz 3.8 4 3.0 65 1.2 100 0.9 88.9 m in x 761 mm 3.8 65 x 80 0.8 4 2 6.0 4 30 100 x 50 1.8 100 0.9 65 bg _... 76.1 mm x 889 mm 0.8 3 60.8 114.3 mm 09 80 114.3mm x 76.1 mm 6.8 80 X 100 0.8 5 4 3.0 4 5 3.3 125 x 100 0.9 100 x 125 1.0 6 4 6 0 6 4.6 150 x 100 1.8 150 1.4 5 125 4.5 165.1 mm 4 165.1 min x 100 68 125 x 150 0.7 8 6 7.3 6 8 6.0 200 x 150 2.2 150 x 200 - 1.8 www.victaulic.com 29 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAUUC COMPANY.O 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. iIctauillc' Dc1I U nc nv 9 _;_I, _ :... 1/1 .11= JOB#1406073 UL FM ULC wdS) Reducing Coupling SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 750 gkie • GENERAL NOTES * Working Pressure and End Load are total,from all internal and external loads, based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size. WARNING: FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 3/4—3 W/20—90 mm;25%for 47100mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request. Contact Victaulic for details. WARNING: Depressurize and drain the piping system before attempting to install, remove,or adjust any Victaulic piping products. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. US&WORLD HEADQUARTERS CANADA CENTRAL AND SOUTH AMERICA P.O. Box 31 905-884-7444 1-610-559-3300 Easton, PA 18044-0031 USA 905-884-9774(fax) 1-610-559-3608(fax) 4901 Kesslersville Road viccanada @victaulic.com vical@victaulic.com Easton, PA 18040 USA EUROPE ASIA PACIFIC 1-800-PICK-VIC(1-800-742-5842) 32-9-381-15-00 86-21-54253300 1-610-559-3300 32-9-380-44-38(fax) 86-21-54253671 (fax) 1-610-250-8817(fax) viceuro@victaulic.be vicap @victaulic.com pickvic@victaulic.com UNITED KINGDOM MIDDLE EAST www.victaDlic.cDm 44(0) 1438741100 971-4-883-88-70 III 111111111 1111111111 1111 11 11111111111 III 44(0) 1438313883(fax) 971-4-883-88-60(fax) WCAS-6QAQRU viceuro@victaulic.be UPDATED 6/2006 06.08 1536 REV H 30 •Ct'c]LJ l r C VICTAUUC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ------------- - nc nO . ,. ... .. ... - . ., S . IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS 10.04 I'. . L 451. Y4T1 VICTAULIC" IS AN ISO 9001 CERTIFIED COMPANY Style 744 FireLock® Flange Adapter VicPlus with Vic-Plus TM Gasket System Gasket System PRODUCT DESCRIPTION Style 744 FireLock Flange adapter is designed for directly incorporating flanged components with ANSI I CL. 125 or CL. 150 bolt hole patterns into a grooved pipe system. Sizes 2-8" (50-200 mm)are hinged for easy handling with integral end tabs which facilitate assembly. rim The design incorporates small teeth inside the key shoulder I.D.to prevent rotation. y _ eir. Because of the outside flange dimension, FireLock Flange adapters should not be used on FireLock fittings.When wafer or lug-type valves are used adjoining a Victaulic fitting,check disc dimensions to s 4116 assure proper clearance. FireLock Flange adapters should not be used as anchor points for tie-rods across nonrestrained joints. • Mating rubber faced flanges,valves,etc., require the use of a FireLock Flange washer. 2-8"Sizes FireLock Flange adapters with Vic-Plus gaskets do not require lubrication.The gasket must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. ii r ow !% so Style 744 FireLock Flange Adapters with the Vic-Plus TM Gasket System are designed and WRY, recommended for use ONLY on fire protection systems. �/"" Vic-Plus Gasket System: Victaulice now offers a gasket system which requires no field lubrication on wet pipe systems. The Vic- PlusT"System(patented) is dry,clean,and non-toxic. It reduces assembly time substantially and t� I �ib eliminates the mess and chance of over-lubrication. Please refer to the latest copy of the Victaulic Field IiInstallation Handbook(1-100)for supplemental lubrication requirements. 7/G ®® -: See Victaulic (Exaggerated for clarity) publication 10.01 for details. DIMENSIONS Style 744 seating Surface Dimensions Sizes 2-8"(50-200 mm) Pie S ANSI Class 125 and 150 Flange Pipe Max. Max. Inches/mm kRfieslmdinlMers AFL Actual Work End Wgt- Nominal Outside Press.' Load' No. Bob Each 2 Diameter Diameter PSI Lbs. Bolts t Size t "A" "B" tbs. �1 r In/mm Inimm kPa N Req'd. Inches Max. Min. W X Y Z kg Off\/, I 2 2.375 175 775 4 sle X 2'/4 2.38 3.41 6.75 6.00 4.75 0.75 2.7 ' S0 1200 3450 60 87 172 152 121 19 1,2 • g Y W 21/2 2787'35 175 1135 4 s/e X 3 2.88 3.91 7.88 7.00 5.50 0.88 4.2 VO� fO� 65 73.0 1200 5050 73 99 200 178 140 22 1,9 111 3 3.500 175 1685 4 2/ X 3 3.50 453 8.44 7.50 6.00 0.94 4.8 O BO 88.9 1200 7500 a 89 115 214 191 152 24 2.2 4 4.500 175 2780 s 4.50 5.53 9.94 9.00 7.50 0.94 7.1 100 114,3 1200 11045 8 /e X 3 114 141 252 229 191 24 3,2 Note:Gray area of mating face must 5 5.563 175 4250 5.56 6.71 11.00 10.00 8.50 1.00 8.3 be free from gouges,undulations or 125 141,3 1200 18920 8 '!4 X 31'2 141 171 279 254 216 25 3,8 deformities of any type for effective sealing. 6 150 66823 1200 6030 6840 8 'l4 X 31/2 6.63 fiB 198 12.00 30 11.00 9.50 1.00 4.2 8# 8.625 175 10219 1 8.63 9.94 14.63 13.50 11.75 1.13 13.9 200 219,1 1200 45475 8 /4 X 3/2 219 252 372 343 298 29 6,3 'Refer to notes below. tTotal bolts required to be supplied by installer.Bolt sizes for conventional flange-to-flange connection.Larger bolts are required when Vic-Flange adapter is utilized with water-type valves. 4 Not available with Vic-Plus gasket system.Lubrication is required. NOTES 'Working Pressure and End Load are total,from all internal and external loads,based on standard weight steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. Style 744 FireLock Flange adapters provide rigid joints when used on pipe with standard roll or cut groove dimensions and consequently allow no linear or angular movement at the joint. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. ®REGISTERED TRADEMARK OF VICTAUUC-0 COPYRIGHT 2004 VICTAULIC-PRINTED IN USA. 1477 REV 0 Victaulic Company of America•Phone:1-800-PICK-VIC(1-800-742-5842)•Fax:610-250-8817•e-mail:pickvic @viclauliccom Victaulic Company of Canada•Phone:905-884-7444•Fax:905-884-9774•e-mail:viccanada@victaulic.com Victaulic Europe•Phone:32-9-381-1500•Fax:32-9-380-4438•e-mail:viceuro @victaulic.be Victaulic America Latina•Phone:610-559-3300•Fax:610-559-3608•e-mail:viral @viclaulic.2ctn i et a u l i c•e Victaulic Asia Pacific•Phone:65-6235-3035•Fax:65-6235-0535•e-mail:vicap @victaulic.com CAMP PARSONS MATERIAL SUBMITTAL 10.04 JOB#1406073 • VIC-FLANGE ADAPTER NOTES 1 The Style 744 (2-(3750-200 mm)design incorporates small teeth inside the key shoulder I.D.to prevent rotation. 2 FireLock Flange adapter should not be used on FireLock fittings.When wafer or lug-type valves are used adjoining a Victaulic fitting,check disc dimensions to assure proper clearance. 3 FireLock Flange adapters should not be used as anchor points for tie-rods across nonrestrained joints. Mating rubber faced flanges,valves,etc.require the use of a FireLock Flange washer. 4 Area A-B noted in the above drawing must be free from gouges,undulations or deformities of any type for effective sealing. s FireLock Flange adapter gaskets must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. s Flange Washers:FireLock Flange adapters require a smooth hard surface at the mating flange face for effective sealing. Some applications for which the Vic-Flange adapter is otherwise well suited do not provide an adequate mating surface.In such cases,it is recommended that a metal Flange Washer be inserted between the FireLock Flange adapter and the mating flange to provide the necessary sealing surface. Typical applications where a Flange Washer should be used are: A When mating to a serrated flange:a standard flat flange gasket should be used adjacent to the serrated flange and then the Flange Washer is inserted between the FireLock Flange adapter and the flange gasket. B When mating to a wafer valve:where typical valves are rubber lined and partially rubber faced(smooth or not),the Flange Washer is placed between the valve and the FireLock Flange adapter. c When mating a rubber faced flange: the Flange Washer is placed between the FireLock Flange adapters and the rubber faced flange. o When mating AWWA cast flanges to IPS flanges:the Flange Washer is placed between two FireLock Flanges.The hinge points must be oriented approximately 90°to each other. If one flange is not a FireLock Flange adapter(e.g.flanged valve),then a standard flat flange gasket must be placed adjacent to that flange and the Flange Washer inserted between the flange gasket and the FireLock Flange adapter. E When mating to components(valves,strainers,etc.)where the component flange face has an insert: follow the same arrangement as in Application 1. F When mating to a Series 705-W Butterfly valve, Style 744 may only be used on one side of the connection. When ordering Flange Washers,always specify product style(Style 744)and size to assure proper Flange Washer is supplied. MATERIAL SPECIFICATIONS Flange Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Coating: Black enamel • Optional: Hot dipped galvanized Bolts/Nuts: Supplied by installer Gasket: • Grade"E" EPDM-Type A Vic-Plus Gasket System A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Ap- proved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated work- ing pressure using the Grade"E"Type A Vic-Plus Gasket System,requiring no field lubrication for most installation conditions. a Standard gasket approved for dry pipe systems to-40°F(-40°C).Based on"typical"pipe surface conditions,supplemental lubricant is recommended for services installed below 0°F(-18°C)and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water.Supplemental lubrication may also be rquired on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld scams. This product shall be manufactured by Victaulic Company.All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. 2 32 Style 744 FireLock® Flange Adapter IPS CARBON STEEL PIPE- FIRE Pr ti'EL•'I ON FITTINGS 10.21 • VICTAULIC' IS AN ISO 9001 CERTIFIED COMPANY No. 67 Vic®-End II End of Run Fitting PRODUCT DESCRIPTION The No. 67, Vic®-End II, End of Run Fitting is the fast, easy,economical way to end a branch line.The fitting installs easily with standard FireLock®couplings and allows direct head connection,sprigs or drops. ` Available in 11/4, 11/2, 2 and 21/2•(32-65 mm)sizes,the fittings can be supplied with 1/2, 3/4, or 1"(15, 20 = or 25 mm)female threaded (NPT)outlet(BSPT option available). The 90°reducing outlet fitting is UL/ULC Listed and FM Approved for a maximum rated working pressure of 500 psi (3450 kPa). F 4!) See Victaulic publication 10.01 for details. DIMENSIONS, PERFORMANCE t_f SIZE Approx. __ Nominal Inches C to E Weight Each Equivalent - �-\ mm Inches/mm Lbs.lkg Feet/meters of Pipe 1• -_ • 13/. X V2 NPT 2.38 1.4 2.8 C to E t 32 X 15 NP1 61 0,6 0,9 I Via- X 3/4 NPT 2.38 1.4 2.8 Iiiiiiiiiiii 1f X 20 NPT 61 0,6 0,9 X 1 NPT 2.38 1.4 2.8 X 25 NPT 61 0,6 0,9 C to E-•.) 1'h X V2 NPT 2.50 1.6 2.9 40 X 15NPT 64 0,7 0,9 X 3/4 NPT 2.50 1.6 2.9 X 20 NPT 64 0,7 0,9 X 1 NPT 2.50 1.6 2.9 X 25 NPT 64 0,7 0,9 2 X 1/2 NPT 2.75 1.7 4.0 50 X 15 NPT 70 0,8 1,2 X 3/4 NPT 2.75 1.7 4.0 X 20NPT 70 0,8 1,2 X 1 NPT 2.75 1.7 4.0 X 25 NPT 70 0,8 1,2 2n/2 X 1/2 NPT 3.00 2.0 5.7 65 X 15 NPT 76 0,9 1,7 X 3/4 NPT 3.00 2.0 5.7 X 20NPT 76 0,9 1,7 X 1 NPT 3.00 2.0 5.7 X 25NPT 76 0,9 1,7 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12, painted Orange Enamel.Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. • Optional: Galvanized -hot dipped. Outlet: NPT • Optional: BSPT This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. ®REGISTEREDTRADEMARK OF VICTAULC-0 COPYRIGHT 2005 VICTAULIC-PRINTED IN U.S.A.-SKU 0WCAS.6DCGPW 3209 REV C United States•Phone:1-800-PICK-VIC(1-800-742-5842)•Fax:610-250-8817•e-mail:pickvic @victaulic.com Canada•Phone:905-884-7444•Fax:905-884-9774•e-mail:viccanada @victaulic.com Europe•Phone:32-9-381-1500•Fax:32-9-380-4438•e-mail:viceuro@victaulic.be UK•Phone:44(0)1438741100•Fax:44(0)1438313883•e-mail:viceuro@victaulic.be ,� Central and South America•Phone:610-559-3300•Fax 610-559-3608•e-mail:vital @victault?.om a ct a u I C Australasia•Phone.86-21-58855151 •Fax:86-21-58851298•e-mail:vicap@victaulic.com CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 34 ula aa«n.U,JL41SCl @.J,: ':'. 'a'< !,Yu&°A.'+,`.6tid tlr'.'. . .,. EasyFlex Flexible @ Hose Sprinkler Assemblies UL listed (Braided or Unbraided)and FM approved (Braided only). This system includes: • Flexible stainless steel hose of various lengths • Nipples for attaching to rigid piping • Reducers for connecting sprinklers • Patented, light-weight mounting bracket systems The EasyFlex system installs without tools and allows complete lateral alignment of sprinklers during installation. Mounting bracket assemblies are available in 25'and 50" lengths. Each length can include a set of short or long T-Bar brackets.TBL brackets(long)are 1725mm higher than TBS(short)ones for recessed applications. The system accommodates 1/2"or 3/4"/12.7mm or 19.05mm sprinklers with flexible length hoses ranging from 24"—72760.9cm—182.8cm The stainless steel flexible hose is available in both braided and unbraided styles. The system requires no welding for assembly. MATERIAL SPECIFICATIONS Flexible Hose Composition:Stainless Steel 304(available braided and unbraided) Lengths Available:24",36",48',60", 72"/60.9cm,91.4cm, 121.92cm, 152.4cm, 182.8cm Pipe Openings Available: 1/2'or 4712.7mm or 19.05mm Seal Material: EPDM Optional Components: 25" Bracket Assembly 50' Bracket Assembly* Nylon isolation ring EPDM gasket Upright reducers for rigid pipe(4',5',6",7',87101mm, 127mm, 152mm, 178mm,203mm) *50' bracket not UL Listed or FM approved Minimum Bend Radius: 3"/76 mm(UL Listing) 8"/203 mm(FM Approval) Do not bend within 21/2763.5 mm from connection nut. Maximum Number of Bends per drop:3 JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. •CtaUIuC REV B 40.90 1 FIRE PROTECTION PRODUCTS—ACCESSORIES 4U.V U EasyFlex Flexible Hose Sprinkler Assemblies PERFORMANCE DATA Friction Loss for 1 "/12.7mm Flexible Hose* 100.00 ammummi 90.00 EM w 80.00 a 70.00 O MINIM 50.00 Lu LuJ F- 40.00 � Mani w 30.00 20.00 !r • 10.00 aimmim 0.00 0 20 40 60 BO 100 120 HOSE LENGTH(inches) UL + FM t 'Test Standard UL 1474 and FM Global Testing Class Number 1637 Friction Loss for 3/d'/14.47 mm Flexible Hose* 90.00 80.00• 60.00- -• 60.00 O 111111 50.00 Z 40.00 3000 E 0 20.00 5 Q 10.00 mom0.00 0 20 40 60 80 100 120 HOSE LENGTH (inches) UL t FM -U- 'Test Standard UL 1474 and FM Global Testing Class Number 1637 Note: Factory Mutual tests the flexible hose both straight and with the maximum number of allow- able bends.The pressure loss is then based on the average of the two tests at each of several pres- sures, using C=100.The pressure is varied from 15 psi to 175 psi in 10 psi intervals. Underwriter's Laboratory bases their test on five difference water velocities from 10—18 ft/sec using C=120. UL does not average the straight and multiple bend results to calculate an overall friction loss. • www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.02008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. iCtaul1C 40.90 2 REV 13 FIRE PROTECTION PRODUCTS-ACCESSORIES 4U. U EasyFlex Flexible Hose Sprinkler Assemblies PRODUCT WEIGHT BY MODEL Hoses 1 EasyFlex P/N 1 Weight 24"X 1"BRAIDED FLEX HOSE ___ EF3724 ,_. ,,...,,1.852 24"X?4"BRAIDED FLEX HOSE I EFB324 1.826 36"X''h"BRAIDED FLEX HOSE i EF3736 .,,.._ 2.119 36"X W BRAIDED FLEX HOSE EFB336 2.093 .... 48"X''h"BRAIDED FLEX HOSE EF8248 I _ __ 2.414 48"X44"BRAIDED FLEX HOSE _ EF6348 ._,.2.388 60"X'h BRAIDED FLEX HOSE 'F8260 2.714 60"X Y'BRAIDED FLEX HOSE EFB360 2.688 72"X Y"BRAIDED FLEX.HOSE i EFB272 3.032 72"X s/. BRAIDED FLEX HOSE _ EF6372 r• 3.005 24"X Y UNBRAIDED FLEX HOSE I EFU224 _ 1.482 24"X'k UNBRAIDED FLEX HOSE EFU324 1 1.455 mm 36 X UNBRAIDED FLEX HOSE EFU236 ;-- 1.667 36"X 3/4"UNBRAIDED FLEX HOSE EFU336 ' _._ __._... 1.641 , ........... 48"X)4 UNBRAIDED FLEX HOSE __. . . EFU248 E 1.861 _... .. 48"X 44"UNBRAIDED FLEX HOSE EFU348 1835 ri 60"X1/2 UNBRAIDED FLEX HOSE ___„-EFU260 _ 2.026 •60'X t4"UNBRAIDED FLEX HOSE EFU360 2.000 72°X V UNBRAIDED FLEX HOSE _.. EFU272 2.165 72"X W UNBRAIDED FLEX HOSE EFU372 2139 Brackets EasyFlex P/N Weight Sna Clam. SSB01 i 0.161 Wall Mount Bracket SSBWO1 W 0148 Metal Stud End Bracket MSB03 I 0.062 _... _ Wood Stud End Bracket i 0.049 Y� Snap On T-Bar Recessed Bracket • T6 _501 _ " _0 232 Snap On T-Bar Concealed Bracket TBL02 1,. .._.,._0287 25'Stock Bar 5025 ...,,,_0.518 50"Stock Bar 5050 1.036 Reducers EasyFlex P/N Weight Reducer'k"X 4/"(MXF) RD12 0.653 ..... _ ...__ Elbow/Reducer 39'Short_-- LRD125 1.114 Elbow/Reducer'h"Long LRD12L 1.482 ii_ Reducer a/<X4'/<"(MXF) RD34 0.626 Elbow/Reducer'/e Short • LRD3451.067 Elbow/Reducer3< Long LRD34L 1.506 Nipple 1"X7% TX I(MXM) NPOI 1 ,,.. 0.318 Reducer 1"X 434"TXT(MXF) RD1 0.650 Parts EasyFlex PIN Weight Nylon Isolation Rine PRO1 ... 0.013 Gasket GROI 0.022 _ _..... 'h"Reducer Plastic Lid TP12 0.002 3/4" • Reducer Reducer Plastic Lid TF34 • 0.002 www.victaulic.com \iCtaulic° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV B 40.90 3 ; • ; . , •;.. - _ .; •M 4•.MIMIII EasyFlex Flexible Hose Sprinkler Assemblies • WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. • NOTE EasyFlex is a registered trademark of Kofulso Co., Ltd. IllllIJ IHIll111111IIIIIIllIJlll IllI W C.4 S-/(8 QJ U For complete contact information,visit www.victaulic.com 40.90 4594 REV El UPDATED 3/2008 ICtauIiilC ■ VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. _2.,.. 40.90 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 39 VicFIexTM Sprinkler Fittings rctauI, Series AH1, AH2 and AH4 Braided Flexible Hose Assemblies io.85 • Brackets: Style AB1 for suspended and hard-lid ceilings, allows • r installation before ceiling tiles in place Style AB2 for hard-lid ceilings, allows for vertical sprinkler adjustment Style AB4 for hard-lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment Approvals/Listings: Style AB7 for suspended ceilings and hard-lid ceilings ® c OL us vas ILPCBI Style AB7 Adjustable for suspended and hard-lid ceilings usrm G412024 1041-01 Style AB8 for hard-lid ceilings (regionally available) See Victaulic Publication 10.01 for more details. Style AB9 for hard-lid ceilings with hat furring channel grid systems Product Description: Style AB10 for Armstrong®TechZone`" ceilings VicFlex sprinkler fittings provide sprinkler installation on suspended ceiling grids, wood or metal stud/joist or hat furring channel hard-lid ceilings utilizing a flexible, stainless steel hose and steel bracket assembly. Refer to the Installation Manual for all applicable ASTM ceiling material and installation standards. System Components • Hoses: Series AH1 Braided Hose Series AH2 Braided Hose Series AH4 Braided Hose Assembly lengths: 31, 36, 48, 60, 72790, 914, 1220, 1525, 183Omm. Note: length includes branch-line nipple and 5.757140mm straight reducer. • Sprinkler Reducers: 'h" and 3/"/15 and 20 mm sprinkler connections and 5.75"/140mm, 9"/230mm, 13"/330mm straight lengths and short, long 90° elbows. Note: The short 90°elbow is typically used with concealed sprinklers while the long 90°elbow is typically used in the installation of recessed pendent sprinklers. • Branch Connections: 1"/25mm NPT or BSPT branch line nipples for attaching to rigid pipe. 34"/20mm NPT or BSPT available for VdS. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date • victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. 1 ictaul.C" victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 • Tgchnical Specifications: Material Specifications: • Maximum Working Temperature: 225°F/107°C • Series AH1 Maximum Working Pressure: Flexible Hose: 300-series Stainless Steel • 200 psi/1375 kPa (FM Approval) Collar/Weld Fitting: 300-series Stainless Steel • 175 psi/1206 kPa (cULus Listed -Series AH2 only) • 1600 kPa/232 psi (VdS/LPCB Approved) Gasket Seal: Victaulic EPDM Isolation Ring: Nylon Connections: To branch line (inlet) via 1"/25.4 mm NPT or BSPT male Nut and Nipple: Carbon Steel, Zinc Plated thread OR Reducers (1/2 or 3/4'): Carbon Steel, Zinc-Plated To branch line (inlet) via 3/"/20 mm BSPT male thread • Series AH2 (VdS only) To sprinkler head (outlet) vial" or W/15 mm or 20 mm Flexible Hose: 300-series Stainless Steel NPT or BSPT female thread Collar/Weld Fitting: 300-series Stainless Steel Minimum Bend Radius: Gasket Seal: Victaulic EPDM • 77178 mm (FM Approval) • 2"/51 mm (cULus Listed - Series AH2 only) Isolation Ring: Nylon • 3"/76.2 mm (cULus Listed - Series AH1 only) Nut and Nipple: Carbon Steel, Zinc Plated • 3776.2 mm (VdS/LPCB Approved) Reducers (V2 or 3/4'): Carbon Steel, Zinc-Plated Maximum Allowable Sprinkler K-Factors: • Series AH4 • FM (1/2"/15mm reducer) K5.6/8,1 (S.I.) (3/4"/20mm reducer) K14.0/20,2 (S.I.) Flexible Hose: 300-series Stainless Steel • cULus (1/2"/15mm reducer) K8.0/11,5 (S.I.) Collar/Weld Fitting: 300-series Stainless Steel (3/4"/20mm reducer) K14.0/20,2 (S.I.) • VdS/LPCB (l '/15mm reducer) K5.6/8,1 (S.I.) Gasket Seal: EPDM per ASTM D2000 (3/4'/20mm reducer) K8.0/11,5 (S.I.) Isolation Ring: N/A Nut and Nipple: Carbon Steel, Zinc-Plated Reducers (' or 3/a"): Carbon Steel, Zinc-Plated • Brackets: Carbon Steel, Zinc-Plated 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ictaul.c' victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 c UL os FRICTION LOSS DATA: Limo -Series AH2 Braided Hose with Straight 5.75" Reducers -Style AB1 and AB1O Brackets Series AH2 Hose Maximum Length of Equivalent Length Number of Stainless Steel of 1733.7mm j 90°Bends at 2"/51mm Flexible Hose Outlet Size Sch.40 Pipe(C=120) Bend Radius inches inches/type feet/meters 31 '"/Straight 16/4.9 j 4 3/4"/Straight 17/5.2 4 36 1/2"/Straight 21/6.4 5 3/a"/Straight 23/7.0 5 Y:"/Straight 32/9.8 I— — 8 34"/Straight 37/113 I 8 Y"/Straight 46/14.0 • 10 60 W"/Straight 46/14.0 10 72 1/2"/Straight S5/16.8 12 3/e"/Straight 53/16.2 12 Series AH2 Braided Hose Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2"/51mm center line bend radius Length of Stainless Steel Flexible Outlet 1 2 3 4 5 6 7 8 9 10 11 12 Hose Size Bend I Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends inches inches 'k' 8.5/2.6 1 11.0/3.4 13.0/4.0116.0/4.9 NA N.A N.A N.A NA N.A NA NA 31 34" 10.0/3.0 i 12.5/3.8 14.0/4.3 17.0/5.2 N.A _N.A N.A N.A NA N.A NA NA 36 1/2" 13.5/4.1 16.0/4.9 18.0/5.5 i 19.0/5.8 21.0/6.4 N.A N.A N.A NA NA NA N.A 44. 14.0/4.3 17.0/5.2 19.5/5.9 20.0/6.1 23.0/7.0 N.A N.A N.A NA NA N.A N.A 1" 15.5/4.7 17.0/5.2 1 19.5/5.9 20.0/6.1 21.0/6.4 22.0/6.7 28.0/8.5 32.0/9.8 NA N.A NA N.A 3/4" 17.0/5.2 19.0/5.8 21.5/6.6 245/7.5 26.0/7.9 27.0/8.2 30.0/9.1 37.0/11.3 NA N.A NA N.A 1" 21.5/6.6 24.0/7.3 27.0/8.2 . 28.5/8.7 30.0/9.1 31.0/9.4 37.0/11.3 42.0/12.8 44.0/13.4 46.0/14.0 N.A NA /" 23.0/7.0 24.0/7.3 28.0/8.5 t_29.5/9.0 30.5/9.3 31.0/9.4 38.0/11.6 42.0/12.844.0/13.4 46.0/14.0 N.A NA 72 1/2" 30.0/9.1 32.0/9.8 136.5/11.1 137.5/11.4 40.5/12.5 41.0/12.8 42.0/12.8 46.0/14.0 49.0/14.9152.0/15.8 54.0/16.5 55.0/16.8 34 32.0/9.8 32.5/9.9 135.0/10.71355/1.0.8 40.0/12.3 40.5/123 41.0/12.5 46.0/14.0 50.0/15.2151.0/15.5 52.0/15.8 53.0/16.2 Note:Values for use with 5.75"straight reducers. How to use this Design Guide: 1 For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends.In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. 2 It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected.When this happens,the design guide may be used to find equivalent lengths based an the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 3 r cta u lr c` victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 UL c us FRICTION LOSS DATA: LISTED -Series AH1 Braided Hose with Straight 5.75" Reducers -Style AB1 and AB10 Brackets Series AH1 Hose Maximum Length of Equivalent Length Number of Stainless Steel of 1733.7mm 90' Bends at 3776.2mm Flexible Hose Outlet Size Sch.40 Pipe(C=120) Bend Radius inches inches/type feet/meters 31 1 "Straight 52/15.8 3 /4/Straight 55/16.8 3 36 __W/Straight 63/19.2 4 'k"/Straight 66/20.1 4 W./Straight 78/23.8 4 3/4"/Straight 80/24.4 4 16"/Straight 88/26.8 1 4 34"/Straight 90/27.4 4 72 W'/Straight 112/34.1 5 'h"/Straight 118/36.0 5 Series AH1 Braided Hose Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 3"/75mm center line bend radius 3 Length of Stainless Steel Flexible Outlet 1 ; 2 3 4 5 Hose Size Bend I Bends Bends Bends Bends inches inches 1/2" 32 42 52 NA N.A 31 3' 33 44 55 N.A N.A 1/2" 33 43 53 63 N.A 36 l" 36 46 56 66 N.A 11" 46 57 68 78 NA 4&" 51 60 71 80 N.A 16" 56 67 77 88 N.A 60 3/4" 58 69 80 90 N.A 72 1/a" 69 79 91 102 112 NI' 73 84 95 106 118 mm; Note:Values for use with 5.75"straight reducers. How to use this Design Guide: 1 For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends.In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. 2 It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected.When this happens,the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. �Ct:al.l�iC" victaulic.com 4 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 ® FRICTION LOSS DATA: -Series AH1, AH2 and AH4 Braided Hose -Various brackets specific to hose Series AH1 Hose Series AH2 Hose Series AH4 Hose For use with Style AB1,AB2, For use with Style AB1,AB2, AB4,AB7,AB7 Adj.,AB8,AB9 AB4,AB7,AB7 Adj.,AB8,AB9 For use with Style AB1,AB7,AB8, and AB10 VicFlex Brackets and AB10 Vic Flex Brackets and AB9 VicFlex Brackets Length of Maximum Maximum Maximum Stainless Equivalent Number of Equivalent Number Equivalent Number Steel Length of 90°Bends at Length of of 90°Bends at Length of of 90°Bends at Flexible Sprinkler Outlet 1"133.7mm 7"/178mm Bend 1733.7mm 7"/178mm 1"/33.7mm 7"/178mm Hose* K-Factor Size Sch.40 Pipe Radius Sch.40 Pipe Bend Radius Sch.40 Pipe Bend Radius inches Imperial/5.1. inches/type feet/meters feet/meters feet/meters 31 5.6/8.1 I'/Straight 53.8/16.4 233/7.1 20.6/6.3 W/90-Elbow 53.8/16.4 2 23/7.0 2 21.7/6.6 2 36 5.6/8.1 1/2"/Straight 63.7/19.4 2 27.8/8.5 2 29.7/9.0 ' '/90'Elbow 63.1/19.2 27.7/8.4 29.8/9.0 2 48 5.6/8.1 IT/Straight 87.9/26.8 38.2/11.6 27.5/8.3 W/90'Elbow 85.8/26.1 3 37.4/11.4 3 29.2/8.9 3 W/Straight 112.2/34.1 42.4/12.9 35.7/10.9 60 5.6/8.1 , 790"Elbow 108.4/33.0 _ 4 43/13.1 4 37.2/113 4 72 5.6/8.1 'h'/Straight 136.5/41.6 4 rt 46.6/14.2 45.9/14.0 W/90*Elbow 131.1/39.9 483/14.7 4 47.5/14.5 4 31 8.0/11.5 1k"/Straight 44.4/13.5 20.7/6.3 13.3/4.0 — '/n"/90'Elbow 47.6/143 2 20.5/6.2 2 14.6/4.4 2 36 8.0/11.5 1'a'/Straight 55.6/16.9 2 25.0/7.6 21.7/6.6 IV/90'Elbow 57.5/17.5 24.6/7.5 2 22.4/6.8—_ 2 48 8.0/115 ''/Straight 82.8/25.2 3 35.5/10.8 3 21.2/6.4 '/a"/90'Elbow 81.7/24.9 - 34.7/10.6 22.2/6.7 3 60 8.0/11.5 '7a'/Straight 110.1/33.5 4 39.6/12.1 _ 4 27.9/83 'k"/90'Elbow 105.9/32.2 40.1/12.2 28.9/8.8 4 72 8.0/115 4 4'/''/_Straight 137.3/41.8 _ 43.5/132 38.8/11.8 4 'k'/90°Elbow 130.2/39.7 452/13.7 39.4/12.0 31 11.2/16.1 '74"/Straight 45.5/13.8 2 17.8/5.4 2 16.4/5.0 2 'k'/90*Elbow 47.1/14.3 18/5.5 19.9/6.1 — 36 11.2/16.1 W/Straight 66.3/20.2 2 22.2/6.7 21.7/6.6 'k"/90'Elbow 57.5/17.5 22.1/6.7 2 24.2/7.4 2 48 11.2/16.1 '/a"/Straight 82.7/25.2 3 32.9/10.0 3 28.5/8.7 '/a'/90'Elbow 82.8/25.2 32.1/9.8 29.9/9.1 1 3 60 11.2/16.1 '/a'/Straight 109.1/33.2 36.8/11.2 34.7/103 '/a'/90'Elbow 108.1/32.9 4 37.1/11.3 4 30.3/9.2 4 72 11.2/16.1 'H"/Straight 135.5/41.3 40.5/12.3 4 38.6/11.6 #"/90°Elbow 133.4/40.6 4 41.9/12.7 38.6/11.7 — 4 31 14.0/20.2 'T'/Straight 44.3/13.5 2 14.9/4.5 16.3/5.0 'k"/90'Elbow 46.4/14.1 15.5/4.72 2 19.9/6.1 2 36 14.0/20.2 t4'/Straight 553/16.9 2 19.4/5.9 21.8/6.7 '/a"/90'Elbow 56.7/17.3 19.6/5.9 2 24.2/7.4 2 48 14.0/20.2 _. 'k'/Straight 83.0/25.3 3 30.3/9.2 3 28.3/8.6 'k"/90°Elbow 82.1/25.0 29.5/8.9 29.9/9.1 3 60 14.0/20.2 'k"/Straight 110.4/33.6 4 33.9/10.3 4 34.9/10.6 _ 4 ' 3/4"/90°Elbow 107.5/32.7 34.1/10.4 30.3/9.2 72 14.0/20.2 '7''/Straight 137.9/42.0 37.5/11.4 41.5/12.6 'k"190-Elbow 132.8/40.4 4 38.6/11.7 4 38.6/11.7 ' 4 FM Notes: Series AH1,AH2 and AH4 have been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13, 13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 and Vds standards for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance,leakage,mechanical and hydrostatic strength. Differences in equivalent lengths are due to varying test methods,per FM 1637 and VdS standards.Refer to these standards for additional information regarding friction loss test methods. EXAMPLE:A 48-inch hose installed with two 30°bends and two 90°bends at a 7-inch bend radius is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 5 ictaulic' victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 VdS -Series LOSS DATA: -Series AH1, AH2 and AH4 Braided Hose -Style AB1, AB2, AB4, AB7, AB7 Adj., AB8, AB9, and AB10 Brackets Series AH1 Hose Series AH2 Hose Series AH4 Hose Equivalent Length of Equivalent Length of Equivalent Length of steel pipe according to steel pipe according to steel pipe according to EN 10255 DN 20 EN 10255 DN 25 EN 10255 DN 25 Maximum Number (26,9 x 2,65)and (33,7 x 3,25)and i (33,7 x 3,25)and !of 90°Bends at Length of Stainless Outlet relating to a flow relating to a flow ! relating to a flow 3776.2mm Bend Steel Flexible Hose Size velocity of 5 m/s velocity of 5 m/s velocity of 5 m/s Radius ' mm/inches mm/inches type meters/feet meters/feet meters/feet 790/31 15mm/'/a"/Straight 4.0/12.9 5.5/18.0 I 5.5/18.0 3 20mm/3k"/Straight 15mm/'h'/Straight_ 915/36 20 mm/3/a"/Straight 4.6/15.0 6.4/21.0 i 6.4/21.0 3 1220/48 15mm/'/"/Straight 6.1/20.0 8.5/27.9 8.5/27.9 3 20 mm/N"/Straight 1525/60 15mm l'fz'/Straight 7.6/25.0 10.7/35.1 10.7/35.1 4 20 mm/3/,"/Straight 15mm/1/2"/Straight I 1830/72 9.2/30.0 12.8/42.0 i 12.8/42.0 4 20 mm/3A"/Straight 1 VdS Ceiling Manufacturers List AB1,AB2,AB7,AB10 AB4/9 ABS 1.AMF 2.Armstrong No specific approval 1.Hilti 3.Chicago Metallic 2.Knauf 4.Dipling 3.Lafarge 5.Durlum 4.Lindner 6.Geipel 5.Rigips 7.Gema-Armstrong 8.Hilti 9.Knauf 10.Lafarge 11.Linder 12.Odenwald 13.Richter 14.Rigips 15.Rockfon Pagos 16.Suckow&Fischer 17.USG Dorm LPCB FRICTION LOSS DATA: -Series AH2 Braided Hose -Style AB1 Bracket Series AH2 Hose Series AH2 Hose { I Equivalent Length 1 Equivalent Length of steel pipe 1 of steel pipe Length of according to Maximum 1 Length of , according to EN Maximum Stainless 1 EN 10255 DN 20 Number of E Stainless 10255 DN 25 Number of Steel l (26,9 x 2,65)and 190°Bends at i Steel (33,7 x 3,25)and 90°Bends at Flexible Outlet ' relating to a flow 13"/76.2mm 1 Flexible 1 Outlet relating to a flow 3776.2mm Hose Size 4 velocity of 5 m/s i Bend Radius! Hose 1 Size velocity of 5 m/s Bend Radius I mm/inches mm/inches/type meters/feet I mm/inches 1 mm/inches/type meters/feet 790/31 1/2lSmm/1z'/Straight 12.65/41.5 2 790/31( i15mm//'/90°Elbow 14.4/47.2 2 20mm/3b"/Straight _ { 20 mm/3;'/90°Elbow 15mm/1h'/Straight —1 15mm/1/2"/90°Elbow 915/36 14.8/48.6 3 l 915/36 - 14.3/46.9 3 / 2Omm/3 '/Straight I i 2Omm/3 '/90°Elbow 1220/48 15mm/W/Straight 15/49.2 3 1220/48 15mm/1h'/90°Elbow 15.3/50.2 3 20 mm/14'/Straight 20 mm/N''/90°Elbow 1525/60 15mm/'A"/Straight 15.3/50.2 3 1 1525/60 15mm/1/2/90°Elbow 16.0/52.5 3 20 mm/14'/Straight 20 mm/?4'/90°Elbow • 1830/72 _.15mm/1/3'/Straight 17.5/57.4 3 I 1830/72 15mm/V2'/90°Elbow 17.1/56.1 3 20 mm/3k./Straight 20 mm/34"/90°Elbow 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 6 ictaulic` victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 .._.._...._......_ Product Details - Series AH1 Braided Hose 4 , Series AH2 Braided Hose Series AH4 Braided Hose IP Item Description 0 p p O c3 � O 1 Flexible Hose 2 Isolation Ring(Series AH1 and AH2 only) MEI IC II lliii oillllllillmqur,mil 3 Gasket 4 Nut 1 A '1 J 5 Branch Line Nipple 6 6 Braid 7 Collar/Weld Fitting Hose Length Dimensions 8 Sleeve(AH2 Only) ' Hose Length A B inches inches I inches mm mm mm 31/790 _ 25.25 31/790 36/915 31.25 36/915 48/1220 I 42.25,,...-� 48/1220 60/1525 1 54.25 60/1525 72/1830 X66.25_ j 72/1830 Standard . 1ill ,IVllliilll�I, lll;.^ 5.75'/140 mm straight reducer Optional �(IiiililluJllliillii ii�ili`lllll )`Hu 9.07229 mm straight reducer II 13.07330 mm straight reducer 2.627 2.62'1 665 mm 66.5 mm `— ::lit II M% 1 6.307 — — 4.837 160.0 mm 122.7 mm e li J ■J WM 1t Mii EM Short 90°elbow reducer Long 90°elbow reducer Note:The Short 90°elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers. 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 7 NoilsiCtalulle victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 VicFlex Brackets Style AB1 p • Suspended Ceilings �... • Hard-Lid Ceilings (FM Only) i 1/Item Description � 1 247610mm or 48"/1219mm Square Bar* 2 Patented 1-Bee2°Center Bracket 3 End Bracket � `Both sizes FM/VdS/LPCB approved,cULus listed • a lel 1_ c t ►' /9 Style AB2 43 • Hard-Lid Ceilings �Item Description 1 24"/610mm or 4871219mm Square Bar* 2 Patent-Pending adjustable Center bracket 6 3 i End Bracket 'Both sizes FM/VdS approved. Note: s/m'/4mm hex key required for adjustment O 1„ L6` ei Style AB4 o ■,. • Hard-Lid Ceilings with Hat furring channel grid system Item Description N,,.1 24"/610mmor48"/1219mmSquare Bar* v g 2 Patent-Pending adjustable Center bracket 3 End Bracket for Hat Furring Channel - 'Both sizes FM/VdS approved. Note:5/32'/4mm hex key required for adjustment lt O 1,. i X1 al 0 l'i•Sii.,.11---' ` l f ' v 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 8 rctaulic" victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 VicFlex Brackets ., Style AB7 0 • Suspended Ceilings `� • Hard-Lid Ceilings ill 3 Item Description Ca 1 _ 24"/610mm or 48"/1219mm Square Bar` 2 Patented 1-Beets Center Bracket 3 End Bracket ,i;N�`LJ `Both sizes FM/VdS approved. _v' O Style AB7 Adjustable • Suspended Ceilings '` • Hard-Lid Ceilings 7 —1 0 i# Item Description 1 1 700mm or 1400mm Square Bar` 2 Patented 1-Bee'•Center Bracket 3 i End Bracket(adjustable) y v `Both sizes FM and VDS approved. P 41.E Style AB8 Is,a • Hard Lid Ceilings 4b4- ... 1 ' • Item Description 1 700mm or 1400mm Square Bar" ■ I 2 Patented 1-Bee'°Center Bracket 3 End Bracket(adjustable) *Both sizes FM/VdS approved. Style AB9 3 • Hard-Lid ceilings with Hat furring channel 0 4.' grid system 104;41 io Item Description -..'-'14:- , N4 1 24"/610mm or 48"/1219mm Square Bar* 2 Patented 1-Bee"Center Brackett, 3 End Bracket for Hat Furring Channel i Zi;, *Both sizes FM/VdS approved. ,.� Style AB10 a✓o • Suspended ceilings © C�'F.\ • Armstrong®TechZone'" ``` ' Item Description �%�y���`%■ 0 • 1 6"/152mm Square Bar" Yj� t 2 Patented 1-Bee"Center Bracket Ir . r 3 End Bracket 'FM/VdS approved,cULus listed. gf 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com g rctaulrc` victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 " Braided Hose Assembly Suspended Ceiling Grid with Recessed Sprinkler - Clearances above ceiling tile at various center-line bend radii ----I Hose Clearance Chart See chart Dimension inches/mm \ \- Minimum Bend 1 ■ Radius"R" 2/50 3/80 4/100 5/125 6/150 7/175 A See Chart 811111 Bracket assembly Minimum"A" 10.75/273 11.75/298.5 12.75/324 1 13.75/349 14.75/375 15.75/400 way S1y1e461 1-'r IU a i �i 4 li 4/� 13 mm I V/16 mm U�J Typal E1 = ceiling tile =w, 1.T/43 mm 1/ 1E p Typical red tg grid ':% ;d�� IWA!. 'jr . Fnished See note — ceiling face 24'/610 mm or 4871219mm on Center V2707 3G•/19 MM MAX.RECESS V2707 3k'/19mm Max. Recess Suspended Ceiling Grid with 90°Elbow (Long) ♦II!IIII Bracket assembly Style ABI ,1�1I Hose Clearance Chart A G.1 ti= mol inches/ seechar1 111 t�'- y� MIME,. Dimension mm �I = ', 447 113 mm A Min. 8/200 78716 mre LJ Typical = ceiling Ole ;le Note: Style AB1 and Series AH2 figures shown. 17•/43 mm is .2s, Y g 7yvi aleninggne IIt-111,' Variations of ceiling grids, sprinkler heads, brackets, -- —i�.�; Fanned and hoses are permitted but may result in clearance See note ceiling face 24'/610 mm differences from the figures above. or4871219 mm on Center V2707 3/4719mm Max. Recess 10.85 5839 Rev V Updated 11/2014 0 2014 Victaulic Company.All rights reserved. rc victaulic.com 10 taulrc` victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Series AQB Braided Hose Assembly - • Suspended Ceiling Grid with Hat Furring Channel Hose Clearance Chart i Dimension inches/mm Minimum Bend Radius"R' I 2/50 3/80 4/100 5/125 6/150 7/175 " / See Chart Minimum"A' 1 10.3/262 11.3/287 12.3/313 13.3/338 14.3/3635 15.3/389 N__ Kin See Chan I - I 397 I 99 mm - -__ / See Note _ \ — / 9 V2708 W/12.7mm Max. Recess Suspended Ceiling Grid with 90°Elbow(Short) ♦Ile• lls Hose Clearance Chart inches/ Dimension mm } �., "' 1116P� M. " /1Mi;)® r —_I - see Chin A Min. 8/200 99 mm - –!- /�-�•.N. See note 1 Note: Style AB9 and Series AH2 figures shown. + 1,.i;�; Prim i.,� Variations of ceiling grids, sprinkler heads, brackets, �.. and hoses are permitted but may result in clearance � i differences from the figures above. V3802 W/12.7mm Max. Recess 10.85 58.39 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 11 cta u I i c' victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 • Flexible Hose In-Plane Bend Characteristics ONE BEND TWO BENDS 2X Minimum - - bend radius I bend radius bend radius Minimum OR OR bend radius 14,\ 90° i \• Minimum Minimum bend radius bend radius Minimum Minimum bend radius bend radius Minimum I bend radius Note:For out-of-plane(three-dimensional)bends:care must be taken to avoid imparting torsional stress on the hose Model Number Correlation I AquaFlex•Designation .. ' VicFlex— A WARNING Designation Series AH4 Outlet Series AQB 1 Series AFB Hose Size 1 Hose i Hose • It is the responsibility of the system designer Assembly inches Assembly Assembly to verify suitability of 300-series stainless steel Y: AQB31HLD { AFB31HLD flexible hose for use with the intended fluid AH4-31 3/4 AQB31TLD y AFB31TLD media within the piping system and external AH4 h AQB36HLD AFB36HLD environments. Va AQB36TLD AFB36TLD AH4-48 / AQB48HLD AFB48HLD • The effect of chemical composition, pH level, a/a AQB48TLD AFB48TLD operating temperature, chloride level, oxygen �1 AI-14-60 AQ66oHLD AFB60HLD level, and flow rate on 300-series stainless steel 3k AQB60TLD AF86oTLD k AQB72HLD AFB72HLD flexible hose must be evaluated by the material AI-14-72 3 AQB72TLD ? AFB72TLD specifier to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause product failure, resulting in serious personal injury i and/or property damage. Installation Note Reference should always be made to I-VICFLEX-AB1-AB2-AB10,I-VICFLEX-AB4-A89, This product shall he manufactured by Victaulic or to Victaulic specifications.All products I-VICFLEX-Ae7,or I-VICFLEX-AB8 for the product you are installing.Handbooks are to be installed in accordance with current Victaulic installation/assembly instructions. included with each shipment of Victaulic products for complete installation and assembly Victaulic reserves the right to change product specifications,designs and standard data,and are available in PDF format on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic and VicFlex are registered trademarks of Victaulic Company. 10.85 5839 Rev V Updated 11/2014 0 2014 Victaulic Company.All rights reserved. victaulic.com 12 Ictaulic° CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 SECTION 2 . 2 FIRE SPRINKLERS 52 CAMP PARSONS MATERIAL SUBMITTAL JOG N1 A(^I74 Attica 800-381-9312 Technical Services +1-401-781-8220 www.tyco-fire.com Series DS-3 Dry-Type Sprinklers 11.2K* Horizontal Sidewall, Extended Coverage, Standard Response General Owners are responsible for maintaining their fire protection system and devices in proper operating condition. The Description installing contractor or sprinkler menu- `� , TYCO Series DS-3 Dry-Type Sprinklers, facturer should be contacted with any questions. 11.2K Horizontal Sidewall, Standard -. a' Response, Extended Coverage, Series DS-3 Dry-Type Sprinklers must Ordinary Hazard, are decorative glass only be installed in fittings that meet 1 bulb automatic sprinklers. They are the requirements of the Design Criteria intended for use in applications where section. Installation of Series DS-3 the sprinklers and/or a portion of the Dry-Type Sprinklers in a recessed , connecting piping may be exposed to installation will void all sprinkler warren Finishes freezin temperatures; for example, ties,as well as void the sprinkler's labo- g p p ratory approvals. Sprinkler: Natural Brass, Chrome horizontal piping extensions through a Plated,White Polyester wall to protect an unheated area of a building. Model/Sprinkler Escutcheon: White Coated or Chrome Plated, Brass Plated Series DS-3 Extended Coverage Identification Ordinary Hazard Horizontal Sidewall, Physical Characteristics Dry Type Sprinklers are designed for Number (SIN) Inlet Copper extended coverage use in ordinary Plug Copper hazard occupancies(ECOH)per NFPA TY5339 Yoke Stainless Steel 13. Series DS-3 Dr -T e S rinklers Casing Galvanized y yp p I T echnical Carbon Steel provide protection of coverage areas up Insert Bronze to 16 ft. x 20 ft. (320 ft2)as compared to standard coverage horizontal Data Bulb Seat Bronze sidewall sprinklers having a maximum Bulb Glass(3 mm) coverage area of 10 ft.x 10 ft. (100 ft2) Approvals Compression Screw Bronze for ordinary hazard occupancies. UL and C-UL Listed Refer to Table A and the Design Criteria Deflector Bronze NOTICE Section. Frame Bronze Guide Tube Stainless Steel Series DS-3 Dry-Type Sprinklers described herein must be installed Maximum Working Pressure Water Tube Stainless Steel and maintained in compliance with this 175 psi(12,1 bar) Spring Stainless Steel document, as well as with the appli- Inlet Thread Connections Gasketed Spring cable standards of the National Fire .1-Inch NPT Plate Seal Beryllium Nickel Protection Association, in addition to (Standard) w/TEFLON the standards of any other Authorities Pin Stainless Steel Having Jurisdiction. Failure to do so •ISO 7-R1 may impair the performance of these (For information on ISO Inlet Thread Button Spring Stainless Steel devices. Connections, contact your Tyco Helper Spring Stainless Steel Sales Representative.) Escutcheon Carbon Steel Discharge Coefficient IMPORTANT Refer to Table B. Always refer to Technical Data Sheet TFP700 for the "INSTALLER Temperature Ratings WARNING"that provides cautions 155°F(68°C)and 200°F(93°C) with respect to handling and instal- lation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. ^Refer to Table B for into on discharge coefficients. Page 1 of 8 SEPTEMER 2011 TFP55O CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page2of8 PLUG WITH YOKE PLUG CASING INSERT FRAME BULB DEFLECTOR GASKETED 1 SPRING SPRING SEAL PLATE % - ''' �1I r; -- : --c .� ,m�. % ; ------ _---------------------- ■ ► INLET WATER GUIDE BULB COMPRESSION INLET 1'NPT SPRING BAND TUBE TUBE SEAT SCREW FIGURE 1 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER TY5339 (ECOH) — ASSEMBLY- SPRINKLER FINISH Temperature Bulb K-Factor K-Factor Rating Color Code Natural Chrome White LENGTH GPM/psi112 Brass Plated Polyester Inches(mm) (LPM/barl'2) 155°F(68°C) Red Listed by Underwriters Laboratories,Inc. 2-1/2 to 14-3/4 11.2 (maximum order length of 48 inches) (63 mm to 375 mm) (161,3) 200°F(93°C) Green Listed by Underwriters Laboratories for use in Canada 15 to 18-3/4 10.9 (maximum order length of 48 inches) (381 mm to 476 mm) (157,0) TABLE A 19 to 23 10.8 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS (483 mm to 584 mm) (155,5) EXTENDED COVERAGE, ORDINARY HAZARD(TY5339) 23-1/4 to 26-3/4 10.7 — LABORATORY LISTINGS AND APPROVALS— (591 mm to 679 mm) (154,1) 27-1/4 to 31-1/4 10.6 (692 mm to 794 mm) (152,6) Operation 31-1/2 to 35-1/4 10.5 When TYCO Series DS-3 Dry-Type (800 mm to 895 mm) (151,2) Sprinklers are in service, water is 35-1/2 to 39-1/2 10.4 prevented from entering the assembly (902 mm to 1003 mm) (149,8) by the Plug with Gasketed Spring 39-3/4 to 43-1/2 10.3 Seal Plate(Figure 1) in the Inlet of the (1010 mm to 1105 mm) (148,3) Sprinkler. 43-3/4 to 48 10.2 The glass bulb contains a fluid that (111 mm to 1219 mm) (146,9) j expands when exposed to heat.When the rated temperature is reached,the Notes fluid expands sufficiently to shatter K-Factor Length is determined as follows: the glass bulb, and the Bulb Seat is • Flush:Order Length from Figure 2 plus released 1/2 inch(12,7 mm) The compressed Spring is then able • Deep:Order Length from Figure 4 plus to expand and push the Water Tube as 3-1/4 inch(82,6 mm) well as the Guide Tube outward. This • Without Escutcheon:Order Length from action simultaneously pulls inward on Figure 5 minus 2-1/4 inches(57,2 mm) the Yoke, withdrawing the Plug with Gasketed Spring Seal Plate from the Inlet allowing the sprinkler to activate TABLE B and flow water. — DISCHARGE COEFFICIENTS - 54 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 3 of 8 Coverage Top Of Minimum Areal W x L Minimum Flow2 Min Pressure2 Deflector-to-Ceiling Temperature n Ft.( ) Application Ft.x Ft. GPM(LPM) PSI(bar) Distance3, Rating°F(°C) Spacing4 x m) Inches(mm) m) 16 x 16 38(144) 11.5 Series DS-3(TY5339) (4,9 x 4,4) (0,79) Horizontal Sidewall Dry-Type Sprinkler(ECOH) (q g x x 18 5 5) 43(163) (1 01) OH Group 1 (0.15 gpm/sq.ft) , Standard Response 16 x 20 18.4 (4,9 x 6,1) 48(182) (1,27) (150 6 to 12 to 300) 155,200 8 16 x 16 51 (193) 20.7 (68,93) (2,4) Series DS-3(TY5339) (4,9 x 4,4) (1,43) Horizontal Sidewall 26.8 Dry-Type Sprinkler(ECOH) (4,9 x 5,5) 56(220) (1,85) OH Group 2(0.20 gpm/sq.ft) Standard Response 16 x 20 32.7 (4,9 x 6,1) 64(242) (2,25) Notes 1. Backwall(where sprinkler is located)by sidewall(length of throw). 2. Requirement is based on minimum flow in GPM from each sprinkler.The indicated residual pressures are based on the nominal K-Factor of 11.2. 3. The centerline of the sprinkler waterway is located below the deflector as shown in Figures 2,3,and 4. I, 4. Minimum spacing is for lateral distance between sprinklers located along a single wall.Otherwise adjacent sprinklers(that is,sidewall sprinklers on an adjacent wall,on an opposite wall,or pendent sprinklers)must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized. TABLE C SERIES OS-3 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS — UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA - Temperatures for Heated Areal Ambient Temperature Exposed to Discharge End 40°F(4°C) I 50°F(10°C) I 60°F(16°C) of Sprinkler Minimum Exposed Barrel Length, Inches(mm)2 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE D EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS — MINIMUM RECOMMENDED LENGTHS - 55 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 4 of 8 Design ORDER LENGTHS: FACE OF 3"to 45-1/4'(76,2 to 1149,4 mm) MOUNTING Criteria IN 1/4'(6,4 mm)INCREMENTS SURFACE 2"±1/8" TYCO Series DS-3, Standard FACE OF (50,8±3,2 mm) Response, Extended Coverage SPRINKLER FITTING 2.3/4"DIA. 9/16°(14,3 mm) Ordinary Hazard, Horizontal Sidewall, 1"NPT, (69,9 mm) v Dry Type Sprinklers (ECOH) are for NOMINAL MAKE-IN It use in ordinary hazard occupancies 9/16^(1 a,3 mm) , 1 with non-combustible unobstructed ��I� 3-11/16'DIA. construction and with a ceiling slope '�N�u�Illll� `C� (93,7 mm) not exceeding 2 inches per foot(9.2°), } using the design criteria provided I� in Table C, as well as any additional SPRINKLER FITTING 1I requirements specified in NFPA 13 for (REFER TO DESIGN \ CENTERLINE Extended Coverage Sidewall Spray CRITERIA SECTION) OF WATERWAY Sprinklers. A 36-inch (914 mm) clearance must FIGURE 2 be maintained between the top of the SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER sprinkler deflector and any miscella- WITH FLUSH ESCUTCHEON(TY5339) neous storage. Series DS-3 Dry Type Sprinklers may be installed on sloped ceilings in loading docks with a maximum roof ORDER LENGTHS: FACE OF slope of 4 inches per foot (18.4°) as 1"to 44"(25,4 to 1117,6 mm) MOUNTING shown in Figure 8 and using the design IN 1/4'(6,4 mm)INCREMENTS SURFACE criteria provided in Table C. 4-1/8"t 3/8" FACE OF (104,8±9,5 mm) Sprinkler Fittings SPRINKLER FITTING (14,3 mm) Install 1-Inch NPT Series DS-3 2-3/4"DIA. 9/16' 1"NPT, (69,9 mm) Dry-Type Sprinklers in the 1-Inch NPT NOMINAL MAKE-IN \ I outlet or run of the following fittings: 9/16"(14,3 mm) r I 1 •malleable or ductile iron threaded ,11 1 tee fittings that meet the dimen- �IINII6 3-1/2"DIA. IIII��IIII `�� (88,9 mm) sional requirements of ANSI 916.3 i (Class 150) SPRINKLER FITTING �� 1 •cast iron threaded tee fittings that (REFER TO DESIGN \ CENTERLINE meet the dimensional requirements CRITERIA SECTION) OF WATERWAY of ANSI B16.4(Class 125). Do not install Series DS-3 Dry Type Sprinklers into elbow fittings.The Inlet of the sprinkler can contact the interior FIGURE 3 of the elbow. SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER WITH DEEP ESCUTCHEON(TY5339) The unused outlet of the threaded tee is plugged as shown in Figure 6. Series DS-3 Dry-Type Sprinklers can also be installed in the 1-Inch NPT ORDER LENGTHS: outlet of a GRINNELL Figure 730 5-1/4"to 48"(133,4 to 1219,2 mm) Mechanical Tee. However, the use of IN 1/4"(6,4 mm)INCREMENTS MINIMUM the Figure 730 Tee for this arrangement 2-1/4"(57,2 mm) is limited to wet pipe systems. FACE OF SPRINKLER FITTING DEFLECTOR TO 1"NPT, MOUNTING The configuration shown in Figure 7 is NOMINAL MAKE-IN SURFACE only applicable for wet pipe systems 9MIN NOMINAL MAKE-IN KE- where the sprinkler fitting and water- filled pipe above the sprinkler fitting are mm) �pNll/� not subject to freezing and where the 'IIIIIII VIII' C�� length of the pry-Type Sprinkler has the minimum exposure length depicted in --K 9/16" Figure 10.Refer to the Exposure Length SPRINKLER FITTING (14,3 mm) section. (REFER TO DESIGN CENTERLINE CRITERIA SECTION) OF WATERWAY FIGURE 4 SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER WITHOUT ESCUTCHEON(TY5339) 56 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 • Page 5 of 8 NOTICE TO DRY r Do not install Series DS-3 Dry-Type SYSTEM ~� Sprinkler into any other type fitting MAXIMUM without first consulting the Technical THROW \ Services Department. Failure to use the 01 m ti,... appropriate fitting may result in one of the following: ' "': • Failure of the sprinkler to operate prop- DSB-2 y / erly due to formation of ice over the INTENDED 6"(152,4 mm) - Inlet Plug or binding of the Inlet Plug. FOR FREEZER TO 12"(304,6 mm) STRUCTURES 4/12 •Insufficient engagement of the Inlet CEILING TO TOP £, pipe-threads with consequent leakage. OF SPRINKLER MSLOMUM AREA y DEFLECTOR Drainage SUBJECT DISTANCE In accordance with the minimum TO requirements of the National Fire FREEZING FIGURE 8 Protection Association for dry pipe SPRINKLER PLACEMENT ►"� sprinkler systems, branch,cross, and UNDER SLOPED CEILINGS P feed-main piping connected to Dry FIGURE 5 IN LOADING DOCKS Sprinklers and subject to freezing subject 9 SPRINKLER FITTING temperatures must be pitched for — UNHEATED AREA — proper drainage. 2-3/4"DIA. (69,9 mm) Exposure Length DSB-2 ,r CLEARANCE INSULATED When using Dry Sprinklers in wet pipe RUN INTENDED HOLE FREEZER sprinkler systems t0 protect areas OUTLET FOR FREEZER ADHESIVE STRUCTURE subject to freezing temperatures, use PLUGGED STRUCTURES alio' Table D t0 determine a sprinkler's DSB-2 ,� appropriate exposed barrel length .Ill'- BOOT 1I_=�� to prevent water from freezing in the �� connecting pipes due to conduction. SPRINKLER The exposed barrel length measure- FITTING , ment must be taken from the face of tO (SEE DESIGN the sprinkler fitting to the surface of the CRITERIA 011111111111 structure or insulation that is exposed SECTION) . � to the heated area.Refer to Figure 7 for TO DRY an example. SYSTEM STRAP ENDS N DS-3 For protected area temperatures AREA (ENDS ON SHOWN between those given above, the SUBJECT OPPOSING WITH FLUSH minimum recommended length from TO SBOO ) ESCUTCHEON the face of the fitting to the outside of FREEZING ,� BOOT) the protected area may be determined FIGURE 9 by interpolating between the indicated FIGURE 6 MODEL DSB-2 DRY SPRINKLER values. SPRINKLER FITTING BOOT WITH SERIES DS-3 — UNHEATED AREA — DRY-TYPE PENDENT SPRINKLER Clearance Space In accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13, when EXPOSURE 't For wet pipe system installations of connecting an area subject to freezing LENGTH 1-Inch NPT Series DS-3 Dry-Type and an area containing a wet pipe - —(SEE DESIGN sprinkler system,the clearance space CRITERIA SECTION) Sprinklers connected to CPVC piping, around the sprinkler barrel of Dry-Type use only the following TYCO CPVC Sprinklers must be sealed. Due to FACE OF fittings: temperature differences between two SPRINKLER .1" x 1" NPT Female Adapter (P/N areas, the potential for the formation FITTING 80145) of condensation in the sprinkler and I •1" x 1" x 1" NPT Sprinkler Head subsequent ice build-up is increased. If Adapter Tee(P/N 80249). this condensation is not controlled,ice build-up can occur that might damage DSB-2 Zill For dry pipe system installations, use the dry-type sprinkler and/or prevent INTENDED only the side outlet of maximum 2-1/2- proper operation in a fire situation. FOR FREEZER inch reducing tee when locating Series STRUCTURES DS-3 Dry-Type Sprinklers directly Use of the Model DSB-2 Dry Sprinkler below the branch line. Otherwise, use Boot,described in technical data sheet HEATED the configuration shown in Figure 6 to TFP591 and shown in Figure 9, can AREA assure complete water drainage from provide the recommended seal. above Series DS-3 Dry-Type Sprinklers FIGURE 7 and the branch line. Failure to do so SPRINKLER FITTING may result in pipe freezing and water — HEATED AREA — damage. 57 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 6 of 8 Do not install any bulb-type sprinkler if Care and the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler Maintenance held horizontally, a small air bubble 4%:- should be present.The diameter of the TYCO Series DS-3 Dry Type Sprinklers 014.0...;-4416 air bubble is approximately 1/16 inch must be maintained and serviced (1,6 mm)for the 135°F(57°C) rating to in accordance with the following h�� 1/8 inch(3,2 mm)for the 360°F(182°C) instructions. rating. Obtain a leak-tight 1-Inch NPT sprinkler NOTICE rl DO NOT joint by applying a minimum-to Before closing a fire protection system maximum torque of 20 to 30 ft. lbs. main control valve for maintenance (26,8 to 40,2 Nm). Higher levels of work on the fire protection system torque may distort the sprinkler Inlet that it controls, obtain permission to with consequent leakage or impairment shut down the affected fire protection of the sprinkler. systems from the proper authorities FIGURE 10 Do not attempt to compensate and notify all personnel who may be — DO NOT GRASP DEFLECTOR — for insufficient adjustment in an affected by this action. Escutcheon Plate by under or over- Absence of the outer piece of an tightening the Sprinkler. Re-adjust the escutcheon, which is used to cover a WRENCH FLAT position of the sprinkler fitting to suit. may delay hole, ma the time to ;I4 ENGAGEMENT Y ;'*' AREA 1. Install horizontal sidewall sprinklers sprinkler operation in a fire situation. 4%. I with the center line of waterway A Vent Hole is provided in the Bulb Seat parallel to the ceiling and perpen- Fi 1)to indicate if the Dry Sprinkler WRENCH • dicular to the back wall surface.The (Figure ) ry P FLATS word "TOP" on the deflector must is remaining dry. Evidence of leakage � face upwards toward the ceiling. from the Vent Hole indicates potential 4r leakage past the Inlet seal and the need 04,1 2. With a non-hardening pipe-thread to remove the sprinkler to determine sealant such as TEFLON applied to the cause of leakage;for example, an the Inlet threads, hand-tighten the improper installation or an ice plug. sprinkler into the sprinkler fitting. Close the fire protection system control APPLY Do not grasp the sprinkler by the valve and drain the system before WRENCH AS deflector(Figure 10). removing the sprinkler. SHOWN 3. Wrench-tighten the sprinkler using Exercise care to avoid damage before, either: during, and after installation. Never FIGURE 11 • a pipe wrench on the Inlet Band or paint, plate, coat, or otherwise alter W-TYPE 8 SPRINKLER WRENCH the Casing(Figure 1). automatic sprinklers after they leave the factory. • the W-Type 8 Sprinkler Wrench on Installation the Wrench Flat(Figure 11). adversely Non-factory elaapor prevent paint delay prevent Apply the Wrench Recess of the operation in the event of a fire. Series DS-3 Dry Type Sprinklers must W-Type 8 Sprinkler Wrench to the Re laces sprinklers that: be installed in accordance with the Wrench Flat. P P following instructions. • were damaged by dropping,striking, Note:If sprinkler removal becomes necessary, remove the sprinkler wrench twisting,wrench slippage,or NOTICE using the same wrenching method the like. Series DS-3 Dry-Type Sprinklers must noted above. Sprinkler removal • were modified or over-heated. only be installed in fittings that meet is easier when a non-hardening • have cracked bulbs or have lost liquid the requirements of the Design Criteria sealant was used and torque guide- from the bulbs.Refer to the Installation section. Refer to the Design Criteria lines were followed. After removal, Section in this data sheet. section for other important require- inspect the sprinkler for damage. ments regarding piping design and 4. After applying a wall finish, slide on • are leaking or exhibiting visible signs sea ling of the clearance space around of corrosion. the Sprinkler Casing. With reference to the outer piece of the Escutcheon Figure 10, do not grasp the sprinkler until it comes in contact with the by the deflector. Failure to follow this mounting surface. instruction may impair performance of For Deep Escutcheons, slide the the device. outer skirt over the inner cup to make firm contact with the mounting surface. 58 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 7 of 8 Responsibility lies with owners for the Limited Ordering inspection,testing,and maintenance of their fire protection system and devices Warranty Procedure in compliance with this document, as well as with the applicable standards of Products manufactured by Tyco Contact your local distributor for avail- the National Fire Protection Association Fire Protection Products (TFPP) are ability.When placing an order,indicate (for example, NFPA 25), in addition to warranted solely to the original Buyer the full product name, including the standards of any other Authorities for ten (10) years against defects description and Part Number(P/N). Having Jurisdiction. The installing in material and workmanship when contractor or sprinkler manufacturer paid for and properly installed and Dry Sprinklers should be contacted relative to any maintained under normal use and When ordering 11.2 K-Factor Series questions. service. This warranty will expire DS-3 Horizontal Sidewall Dry Type Automatic sprinkler systems are recom- ten (10) years from date of shipment Sprinklers, specify the following mended to be inspected, tested, and by TFPP. No warranty is given for information: maintained by a qualified Inspection products or components manufac- •Model/SIN TY5339 Service in accordance with local tured by companies not affiliated by • Length requirements and/or national codes. ownership with TFPP or for products 9 and components which have been Dry-Type Sprinklers are furnished subject to misuse, improper instal- based upon Order Length as lation, corrosion, or which have not measured from the face of the been installed, maintained, modified wall to the face of the sprinkler or repaired in accordance with appli- fitting (Figure 2, 3, and 4). After the cable Standards of the National Fire measurement is taken, round it to Protection Association, and/or the the nearest 1/4 inch increment. standards of any other Authorities •Inlet Thread Connections Having Jurisdiction. Materials found 1-Inch NPT or 7-R1 by TFPP to be defective shall be either repaired or replaced, at TFPP's sole •Temperature Rating option. TFPP neither assumes, nor •Sprinkler Finish authorizes any person to assume for it, any other obligation in connection •Escutcheon Type with the sale of products or parts of •Part Number from Table E. products. TFPP shall not be respon- sible for sprinkler system design errors Sprinkler Wrench or inaccurate or incomplete infor- Specify W-Type 8 Sprinkler Wrench, mation supplied by Buyer or Buyer's P/N 56-010-4-118. representatives. In no event shall TFPP be liable, in Sprinkler Boot contract, tort, strict liability or under Boot, Model 00-0- Dry Sprinkler Y Boot, P/N 63-000-0-002. This Part any other legal theory, for incidental, Number includes one Boot,two Strap indirect, special or consequential Ties,and 1/3 oz. of Adhesive(quantity damages, including but not limited to of adhesive is sufficient for installing labor charges, regardless of whether one Boot). TFPP was informed about the possi- bility of such damages, and in no event shall TFPP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,express or implied. including warranties of merchantability and fitness for a Partic- ular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. 59 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 8 of 8 P/N` 61 - XXX - X - XXX � I SPRINKLER ESCUTCHEON MODEL/SIN FINISH FINISH(1) Flush Escutcheon 1 NATURAL BRASS BRASS PLATED 161 (1"NPT),155°F(68°C) TY5339 Flush Escutcheon 4 WHITE POLYESTER WHITE COATED 163 (1"NPT),200°F(93°C) TY5339 Deep Escutcheon 9 CHROME PLATED CHROME PLATED 171 TY5339 (1"NPT),155°F(68°C) Deep Escutcheon 0 CHROME PLATED WHITE COATED 173 TY5339 (1"NPT),200'F(93°C) Without Escutcheon 151 (1"NPT),155°F(68°C) TY5339 Without Escutcheon ORDER 153 (1"NPT),200°F(93°C) TY5339 LENGTH(2) 055 5.50" Notes 082 8.25" Use Prefix"I"for ISO 7-R1 Connection;for example,1-61-161-1-055. 1. Does not apply to assemblies without escutcheon. 180 18.00" 2. Dry-Type Sprinklers are furnished based upon "Order Length"as measured per Figures 2,3,and 4.After the measurement is taken,round it to the nearest 1/4 inch increment. 187 18.75" 372 37.25" 480 48.00" TABLE E SERIES DS-3 HORIZONTAL SIDEWALL, DRY-TYPE SPRINKLERS(ECOH) — PART NUMBER SELECTION— • Copyright©2011 Tyco Fire Protection Products.All rights reserved. tgcc TEFLON is trademark of The DuPont Corporation. 60 CAMP PARSONS MATERIAL SUBMITTAL 'ca t".''c°c72 fitgea 800-381-9312 Technical Services +1-401-781-8220 www.tyco-fire.com Series DS-3 Dry-Type Sprinklers 11.2K* Horizontal Sidewall, Extended Coverage, Standard Response General Owners are responsible for maintaining their fire protection system and devices Description in proper operating condition. The installing contractor or sprinkler manu- TYCO Series DS 3 Dry-Type S Sprinklers, facturer should be contacted with any , ,a p questions. 11.2K Horizontal Sidewall, Standard i % Response, Extended Coverage, Series DS-3 Dry-Type Sprinklers must Ordinary Hazard, are decorative glass only be installed in fittings that meet bulb automatic sprinklers. They are the requirements of the Design Criteria intended for use in applications where section. installation of Series DS-3 the sprinklers and/or a portion of the Dry-Type Sprinklers in a recessed connecting piping may be exposed to installation will void all sprinkler warren-g temperatures;freezin tem eratu ; for example, ties,as well as void the sprinkler's labo- p ratoryapprovals. Sprinkler: Natural Brass, Chrome horizontal piping extensions through a Plated,White Polyester wall to protect an unheated area of a Model/Sprinkler Illodel/Sprinkler Escutcheon: White Coated or Chrome Plated, Brass Plated Series DS-3 Extended Coverage Identification Ordinary Hazard Horizontal Sidewall, Physical Characteristics Dry-Type Sprinklers are designed for Number (SIN) Inlet Copper extended coverage use in ordinary Plug Copper hazard occupancies(ECOH)per NFPA TY5339 Yoke Stainless Steel 13. Series DS-3 Dry-Type Sprinklers Casing Galvanized ov Technical Carbon Steel provide protection of coverage areas up to 16 ft.x 20 ft. (320 ft2) as compared Insert Bronze to standard coverage horizontal Data Bulb Seat Bronze sidewall sprinklers having a maximum Bulb Glass(3 mm) coverage area of 10 ft.x 10 ft. (100 ft2) Approvals Compression Screw Bronze for ordinary hazard occupancies. UL and C-UL Listed Refer to Table A and the Design Criteria Deflector Bronze NOTICE Section. Frame Bronze Guide Tube Stainless Steel Series DS-3 Dry-Type Sprinklers Maximum Working Pressure described herein must be installed Water Tube Stainless Steel and maintained in compliance with this 175 psi (12,1 bar) Spring Stainless Steel document, as well as with the appli- Inlet Thread Connections Gasketed Spring cable standards of the National Fire •1-Inch NPT Plate Seal Beryllium Nickel Protection Association, in addition to (Standard) w/TEFLON the standards of any other Authorities Pin Stainless Steel Having Jurisdiction. Failure to do so •ISO 7-R7 may impair the performance of these (For information on ISO Inlet Thread Button Spring Stainless Steel devices. Connections, contact your Tyco Helper Spring Stainless Steel Sales Representative.) Escutcheon Carbon Steel Discharge Coefficient IMPORTANT Refer to Table B. Always refer to Technical Data Sheet TFP700 for the "INSTALLER Temperature Ratings WARNING"that provides cautions 155°F(68°C)and 200°F(93°C) with respect to handling and instal- lation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. *Refer to Table B for info on discharge coefficients. Page 1 of 8 SEPTEMMR 2011 TFP55O CAMP PARSONS MATERIAL SUBMITTAL 713550 JOB#1406073 Page 2 of 8 PLUG WITH YOKE PLUG CASING INSERT FRAME BULB DEFLECTOR GASKETED I SPRING SPRING SEAL / ) PLATE 41`'I tiallilliti 1 \ I INLET WATER GUIDE BULB COMPRESSION INLET 1" NPT SPRING BAND TUBE TUBE SEAT SCREW FIGURE 1 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER TY5339(ECOH) —ASSEMBLY— SPRINKLER FINISH Temperature Bulb K-Factor K-Factor Rating Color Code Natural Chrome White LENGTH GPM/psi1r2 Brass Plated Polyester Inches(mm) (LPM/barlr2) • 155°F(68°C) Red Listed by Underwriters Laboratories, Inc. 2-1/2 to 14-3/4 11.2 (maximum order length of 48 inches) (63 mm to 375 mm) (161,3) 200°F(93°C) Green Listed by Underwriters Laboratories for use in Canada 15 to 18-3/4 10.9 (maximum order length of 48 inches) (381 mm to 476 mm) (157,0) TABLE A 19 to 23 10.8 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS (483 mm to 584 mm) (155,5) EXTENDED COVERAGE, ORDINARY HAZARD(TY5339) 23-1/4 to 26-3/4 10.7 — LABORATORY LISTINGS AND APPROVALS — (591 mm to 679 mm) (154,1) 27-1/4 to 31-1/4 10.6 (692 mm to 794 mm) (152,6) Operation 31-1/2 to 35-1/4 10.5 When TYCO Series DS-3 Dry-Type (800 mm to 895 mm) (151,2) Sprinklers are in service, water is 35-1/2 to 39-1/2 10.4 prevented from entering the assembly (902 mm to 1003 mm) (149,8) by the Plug with Gasketed Spring 39-3/4 to 43-1/2 10.3 Seal Plate (Figure 1) in the Inlet of the (1010 mm to 1105 mm) (148,3) Sprinkler. 43-3/4 to 48 10.2 The glass bulb contains a fluid that (111 mm to 1219 mm) (146,9) expands when exposed to heat.When the rated temperature is reached, the Notes fluid expands sufficiently to shatter K-Factor Length is determined as follows: the glass bulb, and the Bulb Seat is released. • Flush:Order Length from Figure 2 plus 1/2 inch(12,7 mm) The compressed Spring is then able • Deep:Order Length from Figure 4 plus to expand and push the Water Tube as 3-1/4 inch(82,6 mm) well as the Guide Tube outward. This • Without Escutcheon:Order Length from action simultaneously pulls inward on Figure 5 minus 2-1/4 inches(57,2 mm) the Yoke, withdrawing the Plug with Gasketed Spring Seal Plate from the Inlet allowing the sprinkler to activate TABLE B and flow water. — DISCHARGE COEFFICIENTS — 63 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP55Q Page 3 of 8 Coverage Top Of Minimum Application Areal W x L Minimum Flow2 Min Pressure2 Deflector-to-Ceiling Temperature Spacing4 Ft.x Ft. GPM(LPM) PSI(bar) Distance • Rating°F(°C) Ft.(m) (m x m) Inches(mm) 16x16 38(144) 11.5 Series DS-3(TY5339) (4,9 x 4,4) (0,79) Horizontal Sidewall 18 Dry-Type Sprinkler(ECOH) (q g x 5 5) 43(163) (1 01) OH Group 1 (0.15 gpm/sq.ft) _ - Standard Response 16 x 20 18.4 48(182) (4,9 x 6,1) (1,27) 6 to 12 155,200 8 16 x 16 20.7 (150 to 300) (68,93) (2,4) Series DS-3(TY5339) (4,9 x 4,4) 51 (193) (1,43) Horizontal Sidewall 16 x 18 26.8 Dry-Type Sprinkler(ECOH) (4,9 x 5,5) 58(220) (1,85) OH Group 2(0.20 gpm/sq.ft) Standard Response 16 x 20 32.7 (4,9 x 6,1) 64(242) (2,25) - Notes 1. Backwall(where sprinkler is located)by sidewall(length of throw). 2. Requirement is based on minimum flow in GPM from each sprinkler.The indicated residual pressures are based on the nominal K-Factor of 11.2. 3. The centerline of the sprinkler waterway is located below the deflector as shown in Figures 2,3,and 4. 4. Minimum spacing is for lateral distance between sprinklers located along a single wall.Otherwise adjacent sprinklers(that is,sidewall sprinklers on an adjacent wall,on an opposite wall,or pendent sprinklers)must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized. TABLE C SERIES DS-3 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS — UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA - Temperatures for Heated Areal Ambient Temperature Exposed to Discharge End 40°F(4°C) 50°F(10°C) 60°F(16°C) of Sprinkler Minimum Exposed Barrel Length, Inches(mm)2 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE D EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS — MINIMUM RECOMMENDED LENGTHS - 64 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 4 of 8 Design ORDER LENGTHS: FACE OF Criteria 3"to 45-1/4"(76,2 to 1149,4 mm) MOUNTING IN 1/4"(6,4 mm)INCREMENTS SURFACE 2"±1/8" TYCO Series DS-3, Standard FACE OF (50,8±3,2 mm) Response, Extended Coverage SPRINKLER FITTING 2_3/4"DIA. 9/16"(14,3 mm) Ordinary Hazard, Horizontal Sidewall, 1'NPT (69,9 mm) Dry-Type Sprinklers (ECOH) are for NOMINAL MAKE-IN \ use in ordinary hazard occupancies 9/16"(14,3 mm) with non-combustible unobstructed VII ■' 3-11/16" DIA. f (93,7 mm) construction and with a ceiling slope 1�uII�I� 1 `C• not exceeding 2 inches per foot(9.2 ), using the design criteria provided --�� t I� in Table C, as well as any additional SPRINKLER FITTING 1 requirements specified in NFPA 13 for (REFER TO DESIGN 1 CENTERLINE Extended Coverage Sidewall Spray CRITERIA SECTION) OF WATERWAY Sprinklers. A 36-inch (914 mm) clearance must FIGURE 2 be maintained between the top of the SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER sprinkler deflector and any miscella- WITH FLUSH ESCUTCHEON(TY5339) neous storage. Series DS-3 Dry Type Sprinklers may be installed on sloped ceilings in loading docks with a maximum roof ORDER LENGTHS: FACE OF slope of 4 inches per foot (18.4°) as 1"to 44"(25,4 to 1117,6 mm) MOUNTING shown in Figure 8 and using the design IN 1/4'(6,4 mm)INCREMENTS SURFACE criteria provided in Table C. 4-1/8"±3/8" FACE OF (104,8±9,5 mm) Sprinkler Fittings SPRINKLER FITTING "DIA. 9/16'(14,3 mm) Install 1-Inch NPT Series DS-3 2-3/4" 1'NPT, Dry-Type Sprinklers in the 1-Inch NPT (89,9 mm) , outlet or run of the following fittings: NOMINAL MAKE-IN 9/16"(14,3 mm) •malleable or ductile iron threaded '�NIVII���gll� I' 3 8,9 DIA. tee fittings that meet the dimen- �I��II `�� (86,9 mm) sional requirements of ANSI B16.3 ' (Class 150) \ `� 1 •cast iron threaded tee fittings that SPRINKLER FITTING meet the dimensional requirements (REFER TO DESIGN CENTERLINE of ANSI B16.4(Class 125). CRITERIA SECTION) OF WATERWAY Do not install Series DS-3 Dry Type Sprinklers into elbow fittings.The Inlet of the sprinkler can contact the interior FIGURE 3 of the elbow. SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER WITH DEEP ESCUTCHEON(TY5339) The unused outlet of the threaded tee is plugged as shown in Figure 6. Series DS-3 Dry Type Sprinklers can also be installed in the 1-Inch NPT ORDER LENGTHS: outlet of a GRINNELL Figure 730 ---5-1/4"to 48"(133,4 to 1219,2 mm) Mechanical Tee. However, the use of IN 1/4"(6,4 mm)INCREMENTS MINIMUM the Figure 730 Tee for this arrangement FACE OF SPRINKLER FITTING 2-1/4"(57,2 mm) is limited to wet pipe systems. DEFLECTOR TO 1"NPT, MOUNTING The configuration shown in Figure 7 is NOMINAL MAKE-IN SURFACE only applicable for wet pipe systems 9/16"(14,3 mm) where the sprinkler fitting and water- filled pipe above the sprinkler fitting are '�III„�IIII '' not subject to freezing and where the Ilil [ length of the Dry Type Sprinkler has the I minimum exposure length depicted in -----_, 9/16" Figure 10.Refer to the Exposure Length SPRINKLER FITTING (14,3 mm) section. (REFER TO DESIGN CENTERLINE CRITERIA SECTION) OF WATERWAY FIGURE 4 SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER WITHOUT ESCUTCHEON(TY5339) 65 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP55() Page 5 of 8 NOTICE TO DRY Do not install Series DS-3 Dry-Type SYSTEM �\ Sprinkler into any other ry yng MAXIMUM P Y type fitting without first consulting the Technical THROW Services Department.Failure to use the DI s=' : `__ appropriate fitting may result in one of "" the following: •Failure of the sprinkler to operate prop- D58-2 } erly due to formation of ice over the INTENDED >, Inlet Plug or binding of the Inlet Plug. FOR FREEZER 6"(152,4 mm) 9 9 9• TO 12"(304,8 mm) •Insufficient engagement of the Inlet STRUCTURES ri CEIUNG TO TOP 4/12 Pipe threads with consequent leakage. OF SPRINKLER SLOPE AREA DEFLECTOR MAXIMUM ;: Drainage SUBJECT DISTANCE In accordance with the minimum TO requirements of the National Fire FREEZING 8 Protection Association for dry pipe 'W SPRINKLER PLACEMENT sprinkler systems, branch,cross, and UNDER SLOPED CEILINGS feed-main piping connected to Dry FIGURE 5 IN LOADING DOCKS SPRINKLER FITTING temperatures and us be to freezing — UNHEATED AREA — temperdrares must be pitched for 2-3/4"DIA proper drainage. (69,9 mm) Exposure Length DSB-2 r CLEARANCE INSULATED When using Dry Sprinklers in wet pipe RUN INTENDED HOLE FREEZER OUTLET FOR FREF7FR ADHESIVE STRUCTURE sprinkler systems to protect areas PLUGGED STRUCTURES Al( subject to freezing temperatures, use _ DSB-2 Table D to determine a sprinkler's BOOT = �� i appropriate exposed barrel length ,� to prevent water from freezing in the Ste— connecting pipes due to conduction. SPRINKLER ( ',III. The exposed barrel length measure- 1 FITTING • _ I. ment must be taken from the face of (SEE DESIGN z the sprinkler fitting to the surface of the RIA O SECTION) i ; structure or insulation that is exposed to the heated area.Refer to Figure 7 for TO DRY III an example. SYSTEM STRAP TIES 135-3 For protected area temperatures (ENDS ON AREA SHOWN between those given above, the OPPOSING SUBJECT WITH FLUSH minimum recommended length from TO SIBOOT)F ESCUTCHEON the face of the fitting to the outside of FREEZING the protected area may be determined FIGURE 9 by interpolating between the indicated FIGURE 6 MODEL DSB-2 DRY SPRINKLER values. SPRINKLER FITTING BOOT WITH SERIES DS-3 — UNHEATED AREA — DRY-TYPE PENDENT SPRINKLER Clearance Space 1 In accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13, when EXPOSURE For wet pipe system installations of connecting an area subject to freezing LENGTH 1-Inch NPT Series DS-3 Dry-Type and an area containing a wet pipe ~(SEE DESIGN Sprinklers connected to CPVC in sprinkler system, the clearance space CRITERIA SECTION) p piping, around the sprinkler barrel of Dry-Type use only the following TYCO CPVC Sprinklers must be sealed. Due to FACE OF fittings: p SPRINKLER FIR temperature differences between two •1 x 1" NPT Female Adapter (P/N areas, the potential for the formation FITTING 80145) of condensation in the sprinkler and 111 S •1" x 1" x 1" NPT Sprinkler Head subsequent ice build-up is increased. If Adapter Tee(P/N 80249). this condensation is not controlled, ice build-up can occur that might damage DSB-2 VII For dry pipe system installations, use the dry-type sprinkler and/or prevent INTENDED only the side outlet of maximum 2-1/2- proper operation in a fire situation. FOR FREEZER inch reducing tee when locating Series STRUCTURES DS-3 Dry-Type Sprinklers directly Use of the Model DSB-2 Dry Sprinkler below the branch line.Otherwise,use Boot,described in technical data sheet HEATED the configuration shown in Figure 6 to TFP591 and shown in Figure 9, can AREA assure complete water drainage from provide the recommended seal. above Series DS-3 Dry-Type Sprinklers FIGURE 7 and the branch line. Failure to do so SPRINKLER FITTING may result in pipe freezing and water — HEATED AREA — damage. 66 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 6 of 8 Do not install any bulb-type sprinkler if Care and 1 the bulb is cracked or there is a loss of liquid from the bulb.With the sprinkler Maintenance held horizontally, a small air bubble rr! should be present.The diameter of the TYCO Series DS-3 Dry Type Sprinklers tl`.•.y� air bubble is approximately 1/16 inch must be maintained and serviced ♦� (1,6 mm)for the 135°F(57°C) rating to in accordance with the following ra- 1/8 inch (3,2 mm)for the 360°F(182°C) instructions. rating. Obtain a leak-tight 1-Inch NPT sprinkler NOTICE joint by applying a minimum-to Before closing a fire protection system DO NOT maximum torque of 20 to 30 ft. lbs. main control valve for maintenance (26,8 to 40,2 Nm). Higher levels of work on the fire protection system torque may distort the sprinkler Inlet that it controls, obtain permission to with consequent leakage or impairment shut down the affected fire protection of the sprinkler. systems from the proper authorities FIGURE 10 Do not attempt to compensate and notify all personnel who may be - DO NOT GRASP DEFLECTOR - for insufficient adjustment in an affected by this action. - Escutcheon Plate by under or over- Absence of the outer piece of an tightening the Sprinkler. Re-adjust the escutcheon, which is used to cover a WRENCH FLAT position of the sprinkler fitting to suit. clearance hole, may delay the time to 1<'� ENGAGEMENT y y [1` AREA 1. Install horizontal sidewall sprinklers sprinkler operation in a fire situation. with the center line of waterway A Vent Hole is provided in the Bulb Seat parallel to the ceiling and perpen- (Figure 1)to indicate if the Dry Sprinkler FLATS WRENCH i� dicular to the back wall surface.The is remaining dry. Evidence of leakage d "TOP" th word on the deflector must from the Vent Hole indicates potential ,b� face upwards toward the ceiling. leakage past the Inlet seal and the need IK:4 r,G; 2. With a non-hardening pipe-thread to remove the sprinkler to determine APPLY libiloissiih WRENCH AS sealant such as TEFLON applied to the cause of leakage;for examplebefore, an the Inlet threads, hand-tighten the improper installation or an ice plug. sprinkler into the sprinkler fitting. Close the fire protection system control Do not grasp the sprinkler by the valve and drain the system deflector(Figure 10). removing the sprinkler. SHOWN 3. Wrench-tighten the sprinkler using Exercise care to avoid damage before, either: during, and after installation. Never FIGURE 11 • a pipe wrench on the Inlet Band or paint, plate, coat, or otherwise alter W-TYPE 8 SPRINKLER WRENCH the Casing(Figure 1). automatic sprinklers after they leave the factory. • the W-Type 8 Sprinkler Wrench on Non-factory applied paint can the Wrench Flat(Figure 11). Installation adversely delay or prevent sprinkler Apply the Wrench Recess of the operation in the event of a fire. Series DS-3 Dry Type Sprinklers must W-Type 8 Sprinkler Wrench to the be installed in accordance with the Wrench Flat. Replace sprinklers that: following instructions. Note:If sprinkler removal becomes • were damaged by dropping,striking, necessary, remove the sprinkler wrench twisting,wrench slippage,or NOTICE ry the like. using the same wrenching method Series DS-3 Dry-Type Sprinklers must noted above. Sprinkler removal •were modified or over-heated. only be installed in fittings that meet is easier when a non-hardening . have cracked bulbs or have lost liquid the requirements of the Design Criteria sealant was used and torque guide- from the bulbs.Refer to the Installation section. Refer to the Design Criteria lines were followed. After removal, Section in this data sheet. section for other important require- inspect the sprinkler for damage. ments regarding piping design and 4. After applying a wall finish, slide on • are leaking or exhibiting visible signs sealing of the clearance space around of corrosion. the outer piece of the Escutcheon the Sprinkler Casing. With reference to Figure 10, do not grasp the sprinkler until it comes in contact with the by the deflector. Failure to follow this mounting surface. instruction may impair performance of For Deep Escutcheons, slide the the device. outer skirt over the inner cup to make firm contact with the mounting surface. 67 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 7 of 8 Responsibility lies with owners for the Limited Ordering inspection,testing,and maintenance of their fire protection system and devices Warranty Procedure in compliance with this document, as well as with the applicable standards of Products manufactured by Tyco Contact your local distributor for avail- the National Fire Protection Association Fire Protection Products (TFPP) are ability.When placing an order, indicate (for example, NFPA 25), in addition to warranted solely to the original Buyer the full product name, including the standards of any other Authorities for ten (10) years against defects description and Part Number(P/N). Having Jurisdiction. The installing in material and workmanship when contractor or sprinkler manufacturer paid for and properly installed and Dry Sprinklers should be contacted relative to any maintained under normal use and When ordering 11.2 K-Factor Series questions. service. This warranty will expire DS-3 Horizontal Sidewall Dry-Type Automatic sprinkler systems are recom- ten (10) years from date of shipment Sprinklers, specify the following mended to be inspected, tested, and by TFPP. No warranty is given for information: maintained by a qualified Inspection products or components manufac- •Model/SIN TY5339 Service in accordance with local tured by companies not affiliated by requirements and/or national codes. ownership with TFPP or for products •Order Length and components which have been Dry-Type Sprinklers are furnished subject to misuse, improper instal- based upon Order Length as lation, corrosion, or which have not measured from the face of the been installed, maintained, modified wall to the face of the sprinkler or repaired in accordance with appli- fitting (Figure 2, 3, and 4).After the cable Standards of the National Fire measurement is taken, round it to Protection Association, and/or the the nearest 1/4 inch increment. standards of any other Authorities •Inlet Thread Connections Having Jurisdiction. Materials found 1-Inch NPT or 7-R1 by TFPP to be defective shall be either repaired or replaced, at TFPP's sole •Temperature Rating option. TFPP neither assumes, nor •Sprinkler Finish authorizes any person to assume for it, any other obligation in connection •Escutcheon Type with the sale of products or parts of •Part Number from Table E. products. TFPP shall not be respon- sible for sprinkler system design errors Sprinkler Wrench or inaccurate or incomplete infor- Specify W-Type 8 Sprinkler Wrench, mation supplied by Buyer or Buyer's P/N 56-010-4-118. representatives. In no event shall TFPP be liable, in Sprinkler Boot Specify Model DSB-2 Dry Sprinkler contract, tort, strict liability or under Boot, P/N 63-000-0-002. This Part any other legal theory, for incidental, Number includes one Boot,two Strap indirect, special or consequential Ties,and 1/3 oz.of Adhesive(quantity damages, including but not limited to of adhesive is sufficient for installing labor charges, regardless of whether one Boot). TFPP was informed about the possi- bility of such damages,and in no event shall TFPP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,express or implied, including warranties of merchantability and fitness for a partic- ular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components,whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part,of any portion of this warranty will not affect the remainder. 68 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 8 of 8 P/N* 61 - XXX - X - XXX SPRINKLER ESCUTCHEON MODEL/SIN FINISH FINISH(1) 161 Flush Escutcheon TY5339 1 NATURAL BRASS BRASS PLATED (1"NPT),155°F(68°C) Flush Escutcheon 4 WHITE POLYESTER WHITE COATED 163 (1"NPT),200°F(93°C) TY5339 Deep Escutcheon 9 CHROME PLATED CHROME PLATED 171 TY5339 (1"NPT),155°F(68°C) Deep Escutcheon 0 CHROME PLATED WHITE COATED 173 TY5339 (1"NPT),200°F(93°C) 151 Without Escutcheon TY5339 (1"NPT),155°F(68°C) 153 Without Escutcheon TY5339 ORDER (1"NPT),200°F(93°C) LENGTH(2) 055 5.50" Notes 082 8.25" Use Prefix"I"for ISO 7-R1 Connection;for example,1-61-161-1-055. 1. Does not apply to assemblies without escutcheon. 180 18.00" 2. Dry-Type Sprinklers are furnished based upon "Order Length"as measured per Figures 2,3,and 4.After the measurement is taken,round it to the nearest 1/4 inch increment. 187 18.75" 372 37.25" 480 48.00" TABLE E SERIES DS-3 HORIZONTAL SIDEWALL,DRY-TYPE SPRINKLERS(ECOH) — PART NUMBER SELECTION - Copyright©2011 Tyco Fire Protection Products.All rights reserved. Vi ico TEFLON is trademark of The DuPont Corporation. 69 CAMP PARSONS MATERIAL SUBMITTAL „THE INCH" JOB#1406073 ICK RESPONSE ""° ' AUTOMATIC SPRINKLERS i110.. ' ,, MODEL GL5606 FIRE SPRINKLER CORPORATION ONE INCH ADJUSTABLE DESCRIPTION AND OPERATION CONCEALED PENDENT The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile, aesthetically pleasing design. It provides sprinkler operation approximately six times faster than ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specified when allowed by the applicable standards. It offers the additional feature of greatly increased safety to life and should be used advisedly and under the direction of approving authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover plate assembly. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate or an optional 23/4"diameter ceiling plate color finished to match the specifier's exact requirements. The GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the"smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its 3mm frangible glass ampule which is located above the ceiling and concealed from view by the ceiling plate. The provided protective cap needs to be removed in order to install the sprinkler with the proper wrench.The protective cap must be replaced on the sprinkler until the time the cover plate is to be installed. The "push on - screw off" designed cover plate is easily installed and with a nominal 1" inch of adjustment makes it easier to get a proper fit at the ceiling. Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the 3mm glass bulb to burst allowing the deflector to drop down and distribute water in an approved pattern to extinguish or control the fire. TECHNICAL DATA •See reverse side for Approvals and Specifications. : ' *Temperature Ratings - 135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate 155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate 155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate 3 5/16" diameter plate 175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate 200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate *Water Working Pressure Rating - 175 psi (12 Bars) •Factory tested hydrostatically to 500 psi (34 Bars) •Maximum low temperature glass bulb rating is -67°F (-55°C) •Frame - bronze • Deflector- brass • Screw- brass •Bulb seat - brass • Spring - nickel alloy • Seal - teflon 2 3/4" diameter plate •Bulb - glass with alcohol based solution, 3mm size QUICK RESPONSE •Drop Pin - stainless steel WHITE ADJUSTABLE •Cover Plate - brass CONCEALED PENDENT •Upper Escutcheon Assembly- plated steel NOTE: Globe's wrench P/N 332765 must be used to install this sprinkler. • SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE BULB N.F.P.A. MAXIMUM CEILING SPRINKLER TEMPERATURES COLOR TEMPERATURE ORDINARY •:' ORANGE/RED INTERMEDIATE t s" YELLOW/GREEN 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 (989) 846-4583 * FAX 989-846-9231 MAY 2012 A-3871 BULLETIN GL5606 REV#6 QUICK �+p� �+ CAMP PARSONS MATERIAL SUBMITTAL ESP ONS E JOB#1406073 AUTOMATIC SPRINKLERS MODEL GL5606 ONE INCH ADJUSTABLE CONCEALED PENDENT SPECIFICATIONS NOMINAL"K" FACTOR THREAD SIZE LENGTH FINISHES Bright Chrome White Painted 5.6 (80 metric) 1/2" NPT 2 1/2"(6.4 cm) Bright Brass' Satin Chrome' Other Painted Finishes' NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. FOR PAINTED PLATES OTHER THAN WHITE,CONTACT GLOBE FOR ORDERING SPECIFICATIONS. APPROVALS **135°F (57°C) 155°F (68°C) **155°F (68°C) 175°F (79°C) 200°F (93°C) NYC-DOB STYLE SIN K with plate with plate with plate with plate with plate cULus *FM MEA MODEL FACTOR 135°F (57°C) 135°F (57°C) 155°F (68°C) 155°F (68°C) 155°F (68°C) 101-92-E Adjustable Concealed GL5606 5.6 X X X X X X X X Pendent °FM APPROVED AS STANDARD RESPONSE '"NO FM APPROVALS CROSS SECT IONS 2 lie OIAMIN.-J —2IH'DLL MIN.— HOLE IN CEILING HOLE IN CEILING 1 7/6' 1 7/6' OIL DIA 1•11/2' 2" REDUCER _ I r 1/ ■ pED11�R 1 1jiii ! IIiii !23NMAIL -,, 211;MIN. DEFLECTOR E{� , I, 12/6'MIN. DROP PIN : DROP PI! `� �' SUPPORT 5n�1111M1 , SUPPORT SHELL I�I�.111111.111111 2 314' 1/6' 35/I6' 1/6" CEILING COVER MATE CEILING COVER PLATEN OPTIONAL COVER WHITE 135°F WHITE 155°F CHROME 135°F CHROME 155°F PLATE SIZE PART# PART# PART# PART# 2 3/4" 332726 332731 332724 332729 3 5/16" 332706 332711 332704 332709 ORDERING INFORMATION GLOBE® PRODUCT WARRANTY SPECIFY Globe agrees to repair or replace any of its own manufactured •Quantity • Model Number • Style products found to be defective in material or workmanship for •Orifice • Thread Sizes • Temperature a period of one year from date of shipment. .Finishes desired For specific details of our warranty, please refer to Price List •Quantity-Adjustable Concealed Wrenches - P/N 332765 Terms and Conditions of Sale (Our Price List). GL 64 BE 4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658 989-846-4583 FAX 989-846-9231 FIRE SPRINKLER CORPORATION 1-800-248-0278 www.globesprinkler.com MAY 2012 PRIN-f D U.S.A. BULLETIN GL5606 REV#6 CAMP PARSONS MATERIAL SUBMITTAL ;;; JOB#1406073 G " ► ` . QUICK RESPONSE ��� AUTOMATIC SPRINKLERS FIRE SPRINKLER C P TIO GL SERIES DESCRIPTION AND OPERATION DRY TYPE The Globe Quick Response GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples. The Globe Quick Response GL Series Dry Type Pendent Sprinkler utilizes a 3mm frangible glass ampule as the il thermosensitive element. This provides sprinkler operation ap- proximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the ,� spring assembly to pivot alongside the inner tube. At this time, ,- waterflows through the sprinkler and is distributed bythe deflector -.'- ' in an approved discharge pattern. It can be installed wherever °- .-,4' standard spray sprinklers are specified but offers the additional }. t feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of �= approving authorities having jurisdiction. The heart of Globe's Model GL Series sprinkler proven actu SURFACE SLEEVE ating assembly is a hermetically sealed frangible glass ampule MOUNT & SKIRT that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern." ;I " TECHNICAL DATA • See reverse side for Approvals and Specifications. 1 ;.1 • Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F ,r, (79°C), 200°F (93°C), 286°F (141°C) � . '' * Water Working Pressure Rating - 175 psi (12 Bars) , • Factory tested hydrostatically to 500 psi (34 Bars) t t 1 • Maximum low temperature glass bulb rating is -67°F (-55°C) • Frame - bronze• Deflector - brass • Screw - brass • Bulb seat - brass • Spring - teflon coated nickel alloy EXTENDED RECESSED • Retainer - brass • Pin - stainless steel *Torsion spring - stainless steel • Bulb - glass with alcohol based solution, 3mm • Orifice insert - brass • 3/4" NPT or 1" NPT • Outer tube - galvanized steel pipe • Inner tube stainless steel • SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM TEMPERATURES CEILING TEMPERATURE ORDINARY t` '^ , ,_ �v ORANGE/RED 'ea " , x.° INTERMEDIATE 17 EE r;� . . ., ° YELLOW/GREEN ' ._'" HIGH ' Ills .e.z , 'I 1 BLUE ` 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX 989-846-9231 JULY 2010 A 545 BULLETIN GL5635, REV.#13 1 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • QUICK RESPONSE AUTOMATIC SPRINKLERS GL SERIES DRY TYPE SPECIFICATIONS NOMINAL"K" FACTOR THREAD SIZE LENGTH FINISHES cULus Variable Factory Bronze 5.6 (80 metric) 3/4"or 1"NPT to 48" Satin Chrome' Bright Chrome White Polyester2 8.1 (116 metric) 1"NPT FM Variable Black Polyester" to 36" Lead Coated" NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. 'cULus LISTED CORROSION RESISTANT: POLYESTER MUST BE SPECIFIED ON ORDER. APPROVALS 'LEAD COATED IS UL APPROVED ONLY STYLE SIN MODEL KFACTOR THREAD SIZE 135°F 155°F 175°F 200°F 286°F *FM cULus NYC-DOB MEA 57°C 68°C 79°C 93°C 141°C 101-92-E GL5635 5.6 1"NPT X X X X X X X X PENDENT GL5636 5.6 3/4"NPT X X X X X - X X GL8135 8.1 1"NPT X X X X X - X X RECESSED GL5635 5 6 1"NPT X X X X X _ X X X PENDENT GL5636 5.6 3/4"NPT X X X X X - X X GL8135 8.1 1"NPT X X ■ X X X - X X NOTE: LISTED FOR ALL HAZARDS *PENDENT STYLE-FM APPROVED 155°F,200°F,AND 286°F IMPORTANT INSTALLATION DATA *RECESSED PENDENT STYLE-FM APPROVED 55°F AND 200°F Globe GL Series Dry Pendent sprinklers should be installed in accordance with the requirements set forth in NFPA 13. CROSS SECTIONS These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible,the proper w e1•;' ,nti' '''',U `'41r sprinkler head wrench may be used with extreme care for ".7,:,' i r' `L∎1, lengths up to approximately 18". Excessive force may distort • ' the frame thus destroying the unit. " When installed in a wet system extending into a freezing 1;71..21;:l' ,///1'''� • ..vim area see chart on Dry Caution Sheet for minimum exposed /,�/, _ barrel length to prevent ice plugs. Please refer to our Dry "°" _ Caution sheet for further important installation data. Z " ����/�� 1977''''' ORDERING INFORMATION � ,f . J la�ii SPECIFY EXTENDEDPENDENT PENDENT •Quantity • Model Number • Style • Orifice •Temperature • Finishes desired ,w•,.:- 1 " °;i,,.. 2g---,; `1 •Quantity-Wrenches- P/N 333010 ;� t „° I "Quantity - Recessed Wrenches - P/N 337014 'Quantity- Protective Caps - P/N 327109-cap(Friction Fit u.� � ' „,•„• Recessed) 'MY MX""' 'Escutcheons desired - 7 4 6 •"A" Dimension - Distance from face of fitting to the finished ■a .7 [7:"-`°`-' L- ` ceiling line regardless of escutcheon used. ! h � °°• - GLOBE® PRODUCT WARRANTY il0 Globe agrees to repair or replace any of its own manufactured .lv'. products found to be defective in material or workmanship for a RECESSED PENDENT SLEEVE&SKIRT PENDENT period of one year from date of shipment. For specific details of our warranty, please refer to Price List Terms and Conditions of Sale (Our Price List). GIAor 4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658 • 989-846-4583 FAX989-846-9231 FIRE MOM ONIPORATIOW Z 1-800-248-0278 www.globesprinkler.com JULY2010 PRINTZbU.S.A. BULLETIN GL5635,REV.#13 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 QUICK RESPONSE Gli i 1:14:thoir BE AUTOMATIC SPRINKLERS AM i" GL SERIES �` DRY TYPE FIRE SPRINKLER CORPORATION HORIZONTAL SIDEWALL RECESSED HORIZONTAL SIDEWALL DESCRIPTION AND OPERATION The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler is designed for use in special applications such as freezing environments and ,. conditions where sediment or foreign materials might accumulate in ordinary , , .. horizontal pipe nipples. t� The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler -,. , utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times fasterthan ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, QUICK RESPONSE causing the inner tube assembly to move, allowing the spring assembly to pivot DRY NON-ADJUSTABLE alongside the inner tube. At this time, water flows through the sprinkler and is HORIZONTAL SIDEWALL distributed by the deflector, in an approved discharge pattern. It can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used 1c a advisedly and under the direction of approving authorities having jurisdiction. The heart of Globe's GL Series sprinkler proven actuating assembly is a , i . t hermetically sealed frangible glass ampule that contains a precisely measured }!t '' d amount of fluid. When heat is absorbed, the liquid within the bulb expands rah ,, increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern. QUICK RESPONSE DRY SLEEVE & SKIRT TECHNICAL DATA HORIZONTAL SIDEWALL • See reverse side for Approvals and Specifications. • Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C). _ __ • Water Working Pressure Rating - 175 psi (12 Bars). �_ `_ ter= • Factory tested hydrostatically to 500 psi (34 Bars). • Maximum low temperature glass bulb rating is -67°F (-55°C). • Frame - bronze * Deflector- brass • Screw - brass • Bulb seat - brass • Spring - teflon coated nickel alloy QUICK RESPONSE • Retainer - brass • Pin - stainless steel • Torsion spring - stainless steel DRY RECESSED • Bulb - glass with alcohol based solution, 3mm • Orifice insert - brass HORIZONTAL SIDEWALL • 3/4" NPT or 1" NPT • Outer tube - galvanized steel pipe • Inner tube - stainless steel • SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM TEMPERATURES CEILING TEMPERATURE ORDINARY 241WagilgatgoCzmw ORANGE/RED 6 '- .�.$_ _ INTERMEDIATE 31 YELLOW/GREEN r ' a � . p HIGH q,. BLUE e, tt-r 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX 989-846-9231 JULY 2010 A-58 BULLETIN GL5641, REV. #14 CAMP PARSONS MATERIAL SUBMITTAL QUICK RESPONSE JOB#1406073 AUTOMATIC SPRINKLERS GL SERIES DRY TYPE SPECIFICATIONS NOMINAL "K' FACTOR THREAD SIZE LENGTH FINISHES cULus Factory Bronze 5.6 (80 metric) 3/4" or 1" NPT Variable to Satin Chromes 48" Bright Chrome FM White Polyester 8.1 (116 metric) 1" NPT Variable to Black Polyester 36" Lead Coated2 NOTE: Metric Conversions are approximate. 'Finishes available on special order. cULus listed corrosion resistant: Polyester must be specified on order. 'Lead Coated is UL approved only. APPROVALS STYLE SIN CODE K FACTOR THREAD SIZE 135°F 155°F 175°F 200°F 286°F *FM cULus 57°C 68°C 79°C 93°C 141°C HORIZONTAL GL5641 5.6° 1" NPT X X X X X X X SIDEWALL GL5642 5.63 3/4" NPT X X X X X - X GL8141 8.15 1" NPT X X X X X - X RECESSED GL5641 5.6° 1" NPT X X X X X X X HORIZONTAL GL5642 5.6° 3/4" NPT X X X X X - X SIDEWALL GL8141 8.1° 1" NPT X X X X X - X NOTE:'Listed for light hazard only with deflector from 4"-12"below the ceiling. 'Listed for light and ordinary hazard with deflector from 4"-12"below the ceiling. IMPORTANT INSTALLATION DATA 'Recessed Horizontal Sidewall-FM Approved 155°F and 200°F only. 'Horizontal Sidewall-FM Approved 155°F,200°F,and 286°F only. Globe GL Series Dry Horizontal Sidewall sprinklers should be installed in accordance with the requirements set forth in CROSS SECTIONS NFPA 13. These sprinklers are to be installed using a pipe . wrench applied to the outer tube. When this is not possible,the -- °'"'fS proper sprinkler head wrench may be used with extreme care •.. ^l I for lengths upto approximately 18". Excessiveforce may distort ° the frame thus destroying the unit. ii. When installed in a wet system extending into a freezing tiL, (4/ +----tt- area see chart on Dry Caution Sheet for minimum exposed I' l?ii„ I' I .,,•,,.°. barrel length to prevent ice plugs. Please refer to our Dry Caution sheet for further important installation data. /--m Wes'' IL ORDERING INFORMATION °' SPECIFY EXTENDED RECESSED .Quantity • Model Number • Style HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL •Orifice • Temperature •Finishes desired •Quantity-Wrenches-P/N 333010 ";r ,�"°` —' " '-, •Quantity-Recessed Wrenches-P/N 337014 "� ,._ •Quantity-Protective Caps-P/N 327109-CAP(Friction Fit •.A. m"° 9i Recessed) •Escutcheons desired *-----,L-', 9/, w" c----:=-• L ."A"Dimension-Distance from face of fitting to the finished ii Cr" II I ceiling regardless of escutcheon used. i %�:. " J 4, �e& _„� � `.'"w° GLOBE®PRODUCT WARRANTY '—'r' ”'"- Globe agrees to repair or replace any of its own manufactured NON-ADJUSTABLE SLEEVE&SKIRT products found to be defective in material or workmanship for a HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale(Our Price List). 4077 AIRPARK DRIVE, STANDISH,MICHIGAN 48658 FIRE SPRINKLER CORPORATION 989-846-4583 FAX 989-846-9231 1-800-248-0278 www.globesprinkler.com JULY2010 PRINT6$ U.S.A. BULLETIN GL5641, REV.#14 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 SECTION 2. 3 VALVES AND ACCESSORIES 79 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Fire Department Connection , Straight Pattern '7.4" ' qfti • Description Installation Specs p p cs The Straight Pattern Fire Installation of the Fire De- Size: Department Connection is partment Connection is 4" IPS Outlet Underwriters' Laboratories achieved with readily avail- (2) 2 1/2" NST listed and Factory Mutual able jobsite tools. Prior to Swivel Inlets Approved. Manufactured installation make sure the Tyoe: from solid brass components proper identification sign has Straight Pattern rt'f to increase service life.The been installed on the nipple. single clapper design fea- Coat male threads of 4" IPS Material: tures brass clapper and nipple liberally with a suit- Brass brass seats within a cast able pipe thread sealant brass body. The 2 1/2" such as Pipefit®. Tighten Swivels: swivels are pin lug design FDC one full turn past hand 2 1/2" NST PL for ease of use and tight. Make sure FDC is BCT campatablilty with local fire aligned according to require- ONT service districts.Swivel ments. QST gaskets are included. Break- PHX able caps in either metal or DO NOT OVER TIGHTEN. TEM plastic should be installed to OVERTIGHTENING MAY CLV protect swivels and prevent CAUSE SEVERE debris from being accidently STRETCHING AND POS- Approvals: introduced into the water way. SIBLE CRACKING OF THE OF THE FDC BODY. UL Listed FM Approved r�s For questions: 1 800 344-1822 1 800 344-3775 fax http://www.fppi.com F P P I info @fppi.com f*MIRA 4=4111 NS. ©1995-2000 Fire Protection Products, Inc. 80 StaCAMP PARSONS MATERIAL ndpipe Equipment ® I 0 X61 fill Fire Department Connections & Accessories F P P i` Storz Type Fire Department Connection Provides a"quick connection"of large diameter hose by Fire Service Professionals to fire sprinkler or standpipe systems. Conforms with NFPA1963 requirements. Forged aluminum. Storz Fire Dept.Connections w/Caps Box Qty. 09-205-00 4" Storz x 4" FNPT w/Cap (UL) 2 09-207-00 5" Storz x 4" FNPT w/Cap (UL) 2 09-215-00 4" Storz x 4" FNPT, 30°w/Cap (UL) 1 -` 09-217-00 5" Storz x 4" FNPT, 30°w/Cap (UL) 1 ,Y, Storz Kits Fire Dept. Connections w/Caps Box Qty. & Sprinkler Wall Plates — 09-230-00 4" Storz x 4" FNPT w/Cap &Wall Plate (UL) 1 09-234-00 5" Storz x 4" FNPT w/Cap&Wall Plate (UL) 1 09-236-00 4" Storz x 4" FNPT, 30° w/Cap &Wall Plate (UL) 1 09-238-00 5" Storz x 4" FNPT, 30° w/Cap &Wall Plate (UL) 1 0 E Storz Individual Storz Components Box Qty. 09-200-00 4" Storz x 4" FNPT (UL) 4 .,01‘ c 09-202-00 5"Storz x 4" FNPT(UL) 4 4� v• 09-210-00 4" Storz x 4" FNPT w/30° Elbow (UL) 1 2 09-212-00 5" Storz x 4" FNPT w/30° Elbow (UL) 1 • 09-220-00 4" Storz Cap & Chain 4 C■ 09-222-00 5"Storz Cap & CHain 4 a d r'' fi s d C a T FDC Wall Plates Part No. Description Box Qty. 09-507-00 FDC W/P 4" IPS "Auto Spr" Plastic 25 + 0" } 09-508-00 FDC W/P 4"IPS "Auto Spr" AL 12 OJ 09-509-00 FDC Sign 4" x 8" "Fire Dept Conn" AL 100 09-510-00 FDC W/P 4" IPS "Auto Spr" RB 5 09-510-10 FDC W/P 4" IPS "Auto Spr" PC 5 09-514-00 FDC W/P 4" IPS "Standpipe" AL 12 _ •- • r'; r 09-516-00 FDC W/P 4" IPS "Standpipe-Auto" AL 12 ., 09-520-00 FDC W/P 21/" IPS "Auto Spr" RB 10 r �- 09-522-00 FDC W/P 2W IPS "Auto Spr" AL 20 AL=Aluminum RB=Rough Brass PC=Polished Chrome 82 33 G11• „: .\ IIL :14 . 1 WILKINS Model 350A a ZURN= company Double Check Valve Assembly SPECIFICATION SUBMITTAL SHEET I( 14 APPLICATION Designed for installation on potable water lines to protect against 1 ` both backsiphonage and backpressure of polluted water into the I(, , ;, ,)l` ; _ t -, potable water supply.The Model 350A shall provide protection where a potential health hazard does not exist. Ideal for use where lead-free*valves are required. (with OSY gates) (with BGVIC valves) I "-1 STANDARDS COMPLIANCE(Horizontal&Vertical) FEATURES • ASSE®Listed 1015 Sizes: 02 1/2"* 03"` 04" 06" 08" 010" • AWWA Compliant C510(with gates only) Maximum working water pressure 175 PSI • IAPMO®Listed Maximum working water temperature 140°F • CSA®Certified Hydrostatic test pressure 350 PSI • UL®Classified End connections • C-UL®Classified (Grooved for steel pipe) AWWA C606 • FM®Approved (Flanged) ANSI B16.1 • NYC MEA 220-04-M Vol 2(2 1/2"-8") Class 125 • Approved by the Foundation for Cross Connection Control `2 1/2"&3"sizes use 4"body&reducer couplings and Hydraulic Research at the University of Southern OPTIONS(Suffixes can be combined) California ❑ - with flanged end NRS gate valves(standard) • NSF®Listed-Standard 61,Annex G' ❑ FSC - with epoxy coated wye type strainer(flanged only) *(0.25%MAX.WEIGHTED AVERAGE LEAD CONTENT) ❑ G - with grooved end NRS gate valves MATERIALS LI GF - with grooved inlet gate connection and flanged Main valve body Ductile Iron ASTM A 536 Grade 4 outlet gate connection Access covers Ductile Iron ASTM A 536 Grade 4 ❑ FG - with flanged inlet gate connection and grooved Coatings FDA Approved electrostatic epoxy outlet gate connection finish ❑ L - less shut-off valves(grooved body connections) Internals Stainless steel, 300 Series ❑ OSY - with flanged end OS&Y gate valves NORYLTM, NSF Listed ❑OSYG- with grooved end OS&Y gate valves Fasteners&springs Stainless Steel, 300 Series ❑ PI - with Post Indicator Gate Valves(3"-12") Seal ring EPDM (FDA approved) ❑BGVIC- with grooved end butterfly valves 0-ring Buna Nitrile(FDA approved) ACCESSORIES _ i ❑ Repair kit(rubber only) MODEL 350A ❑ Thermal expansion tank(Model XT) with OSY& LI OS&Y Gate valve tamper switch (OSY-40) FSC option 7. = _'- II '' E ❑ Test Cock Lock(Model TCL24) '*'- '_ -,�- Aka _ lam) DIMENSIONS&WEIGHTS (do not include pkg.) 1 II I illtrallitkri .1 ...0• WEIGHT ! I4' L' B---1 C MODEL WITH OS&Y WITH WITH SIZE WITHOUT WITH NRS GATES WITH NRS OS&Y BUTTERFLY _ A D GATES GATES GATES GATES VALVES G (GXF) (GXF) (GXG) (GXG) (GXG) in mm lbs kg lbs. kg lbs. kg lbs. kg lbs kg lbs. kg A IN • } 2112 65 90 41 184 83.5 192 87 176 80 184 63.5 108.8 49.4 MODEL �� 11..g -1 dm le 350A with ( ` 14��` E 3 80 89 40.5 204 92.5 210 95.3 194 88 200 90.8 109.4 50 11■■ ,�1 4 100 76 34.5 220 100 230 104 194 88 204 93 108 49 BGVIC option mil �,I��I'I�� II "7 " F 6 150 126 57.2 346 157 362 164 316 143 332 151 178 81 _ __,_1_ 8 200 286 130 738 335 762 335 738 335 738 335 394 179 8 10 -250 339 153.8 966 438.2 1024 464.5 844 382.8 902 409.1 511 232 A C D DIMENSION(approximate) MODEL e E E E WITH SIZE A A WITH LESS C D OS&Y OS&Y E BUTTERFLY F G BUTTERFLY GATE OPEN CLOSED NRS GATE VALVES Attention: VALVES Model 350A In. mm in. mm in. mm in. mm in mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm (grooved body) 21/2 65 35 1/8 892 321/8 816 20 1/8 511 4 1/2 114 7114 184 16 3/8 416 13 7/8 352 11 3/8 289 8 203 6 152 45 1/4 1150 &Model 350 3 80 36 1/8 918 33 838 20 118 511 4 1/2 114 71/4 184 187/8 479 15 5/8 397 12 3/8 314 8 203, 6 152 46 7/8 1191 (flange body) 4 100 381/4 972 331/4 845 197/8 505 41/2 114 8 203 223/4 578 181/4 464 143/4 375 91/8 232 6 152 533/8 1356 havedifferent 6 _150 47 1/4 1200 40 1/4 1022 25 7/8 657 51/2 140 10 254 30 1/8 765 23 3/4 603 19 483 101/8 257 7 178 65 3/8 1661 lay lengths. 8 200 62 1575 55 1397 38 1/2 978 10 254 11 279 37 3/4 959 29 1/4 743 221/2 572 1115/18 303 81/2 216 86 3/8 2194 10 250 64 5/8 1642 58 12 1485 38 1/2 978 10 254 12 305 45 3/4 1162 35 3/8 899 26 1/2 673 135/16 338 81/2 216 94 3/8 2398 (Patent NO. 5,913,331) BF-35 A ENT#: REVISION: Page 1 of 2 c4 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 ' FLOW CHARACTERISTICS MODEL 350A 2 1/2",3"&4"(STANDARD& METRIC) FLOW RATES(Vs) 0.0 12.6 25.2 37.9 50.5 (715 4mm 1�a_ 00mm)- w • 10 - 65mm) 69 Li O K w ` D 5 ' o� 35 y w Ul d w ce a 0 0 0 200 400 600 800 FLOW RATES(GPM) MODEL 350A 6",8"&10"(STANDARD&METRIC) FLOW RATES(I/s) 0.0 63.1 126.2 189.3 252.4 15 104a a -- 10"(250mm) rn 150mm) '�� �� 69 u1• w• 10 I�- ( I- (200mm) -�- 5 ���* w ce • 35 w w w a a 0 0 0 1000 2000 3000 4000 FLOW RATES(GPM) 0 Rated Flow(established by approval agencies) TYPICAL INSTALLATION Capacity thru Schedule 40 Pipe(GPM) Local codes shall govern installation requirements.Unless other- Pipe size 5 ft/sec 7.5 ft/sec 10 ftJsec 15 ft/sec wise specified, the assembly shall be mounted at a minimum of 2 1/2" 75 112 149 224 12" (305mm) and a maximum of 30" (762mm) above adequate drains with sufficient side clearance for testing and maintenance. 3" 115 173 230 346 The installation shall be made so that no part of the unit can be 4" 198 298 397 595 submerged. 6" 450 675 900 1351 l- 8" 780 1169 1559 2339 IIII -if ii I 10" 1229 1843 2458 3687 ilii:�,N— 12" 1763 2644 3525 5288 M o o„ Ill _ °�- W it PROTECTIVE l-■ " - $' _-- ° ''''t.:.–. 11011F"1—_ I ��;,,■,,,.���■,, �' I Ah ������ IiA I I'! 11�i • II 1 d, s I. 12"MIN 12"MIN. I El 30MA30"MAX.FII t ,-= DIRECTION OF FLOW�CTION OF FLOW I • INDOOR INSTALLATION INDOOR INSTALLATION OUTDOOR INSTALLATION MODEL 350ABGVIC (VERT.)MODEL 350A MODEL 350AFS SPECIFICATIONS The Double Check Backflow Prevention Assembly shall be ASSE® Listed 1015, and supplied with full port gate valves.The main body and access cover shall be epoxy coated ductile iron(ASTM A 536 Grade 4),the seat ring and check valve shall be NORYLTM the stem shall be stainless steel (ASTM A 276)and the seat disc elastomers shall be EPDM.The checks shall be accessible for maintenance without removing the device from the line.The Double Check Backflow Prevention Assembly shall be a WILKINS Model 350A. WILKINS a Zurn company,1747 Commerce Way,Paso Robles,CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW(1-877-222-5356) • Website:http://www.zurn.com Page 2 of 2 85 CAMP PARSONS MATERIAL SUBMITTAL 'GQ 1'11^6G72 ANCO 800-381-9312 Technical Services +1-401-781-8220 www.tyco-fire.com Series DS-3 Dry-Type Sprinklers 112K* Horizontal Sidewall, Extended Coverage, Standard Response General Owners are responsible for maintaining their fire protection system and devices Description in proper operating condition. The installing contractor or sprinkler manu- / TYCO Series DS-3 Dry-Type Sprinklers, facturer should be contacted with any 1' % questions. 11.2K Horizontal Sidewall, Standard �E s, Response, Extended Coverage, Series DS-3 Dry-Type Sprinklers must Ordinary Hazard, are decorative glass only be installed in fittings that meet bulb automatic sprinklers. They are the requirements of the Design Criteria intended for use in applications where section. Installation of Series DS-3 the sprinklers and/or a portion of the Dry-Type Sprinklers in a recessed connecting piping may be exposed to installation will void all sprinkler warran- Finishes freezing temperatures; for example, ratory well v void the sprinkler's labo- Sprinkler: Natural Brass, Chrome horizontal piping extensions through a rato approvals. Plated,White Polyester wall to protect an unheated area of a building. Model/Sprinkler Escutcheon: White Coated or Chrome Plated, Brass Plated Series DS-3 Extended Coverage Identification Ordinary Hazard Horizontal Sidewall, Physical Characteristics Dry-Type Sprinklers are designed for Number (SIN) Inlet Copper extended coverage use in ordinary Plug Copper hazard occupancies(ECOH)per NFPA TY5339 Yoke Stainless Steel 13. Series DS-3 Dry-Type Sprinklers Casing Carbon Steel provide protection of coverage areas up to 16 ft. x 20 ft. (320 ft2) as compared Insert Bronze to standard coverage horizontal Data Bulb Seat Bronze sidewall sprinklers having a maximum Bulb Glass(3 mm) coverage area of 10 ft. x 10 ft. (100 ft2) Approvals Compression Screw Bronze for ordinary hazard occupancies. UL and C-UL Listed Refer to Table A and the Design Criteria Deflector Bronze NOTICE Section. Frame Bronze Guide Tube Stainless Steel Series DS-3 Dry-Type Sprinklers described herein must be installed Maximum Working Pressure Water Tube Stainless Steel and maintained in compliance with this 175 psi(12,1 bar) Spring Stainless Steel document, as well as with the appli- Inlet Thread Connections Gasketed Spring cable standards of the National Fire .1-Inch NPT Plate Seal Beryllium Nickel Protection Association, in addition to (Standard) w/TEFLON the standards of any other Authorities Pin Stainless Steel Having Jurisdiction. Failure to do so •ISO 7-Ri may impair the performance of these (For information on ISO Inlet Thread Button Spring Stainless Steel devices. Connections, contact your Tyco Helper Spring Stainless Steel Sales Representative.) Escutcheon Carbon Steel Discharge Coefficient IMPORTANT Refer to Table B. Always refer to Technical Data Sheet TFP700 for the "INSTALLER Temperature Ratings WARNING"that provides cautions 155°F(68°C)and 200°F(93°C) with respect to handling and instal- lation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. •Refer to Table B for info on - discharge coefficients. Page 1 of 8 SEPTEMWER 2011 TFP55O CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 , • Page 2 of 8 PLUG WITH YOKE PLUG CASING INSERT FRAME BULB DEFLECTOR GASKETED SPRING SPRING SEAL ' PLATE .Nromovd'‘:>t IIIII IIII' r I IU[• - �iY $. -\ ‘11111101. : I 1 INLET WATER GUIDE BULB COMPRESSION INLET 1"NPT SPRING BAND TUBE TUBE SEAT SCREW FIGURE 1 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER TY5339(ECOH) —ASSEMBLY— SPRINKLER FINISH Temperature Bulb K-Factor K-Factor Rating Color Code Natural Chrome White LENGTH GPM/psi112 Brass Plated Polyester Inches(mm) (LPM/bartr2) 155°F(68°C) Red Listed by Underwriters Laboratories,Inc. (maximum order length of 48 inches) 2-1/2 to 14-3/4 11. (63 mm to 375 75 m mm) (161,, (161,3) 200°F(93°C) Green Listed by Underwriters Laboratories for use in Canada 15 to 18-3/4 10.9 (maximum order length of 48 inches) (381 mm to 476 mm) (157,0) TABLE A 19 to 23 10.8 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS (463 mm to 584 mm) (155,5) EXTENDED COVERAGE, ORDINARY HAZARD(TY5339) 23-1/4 to 26-3/4 10.7 — LABORATORY LISTINGS AND APPROVALS — (591 mm to 679 mm) (154,1) 27-1/4 to 31-1/4 10.6 (692 mm to 794 mm) (152,6) Operation 31-1/2 to 35-1/4 10.5 When TYCO Series DS-3 Dry-Type (800 mm to 895 mm) (151,2) Sprinklers are in service, water is 35-1/2 to 39-1/2 10.4 prevented from entering the assembly (902 mm to 1003 mm) (149,8) by the Plug with Gasketed Spring 39-3/4 to 43-1/2 10.3 Seal Plate(Figure 1) in the Inlet of the (1010 mm to 1105 mm) (148,3) Sprinkler. 43-3/4 to 48 10.2 The glass bulb contains a fluid that (111 mm to 1219 mm) (146,9) expands when exposed to heat. When the rated temperature is reached, the Notes fluid expands sufficiently to shatter K-Factor Length is determined as follows: the glass bulb, and the Bulb Seat is released. • Flush:Order Length from Figure 2 plus 1/2 inch(12,7 mm) The compressed Spring is then able • Deep:Order Length from Figure 4 plus to expand and push the Water Tube as 3-1/4 inch(82,6 mm) well as the Guide Tube outward. This • Without Escutcheon:Order Length from action simultaneously pulls inward on Figure 5 minus 2-1/4 inches(57,2 mm) the Yoke, withdrawing the Plug with Gasketed Spring Seal Plate from the Inlet allowing the sprinkler to activate TABLE B and flow water. — DISCHARGE COEFFICIENTS — 88 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP55O Page 3 of 8 • Coverage Top Of Minimum Areal W x L Minimum Flow2 Min Pressure2 Deflector-to-Ceiling Temperature Spacing4 Application Ft.x Ft. GPM(LPM) PSI(bar) Distances, Rating°F(°C) Ft.(m) (m z m) Inches(mm) 16 x 16 38(144) 11.5 Series DS-3(TY5339) (4,9 x 4,4) (0,79) Horizontal Sidewall 16 x Dry-Type Sprinkler(ECOH) (4,9 x 55) 43(163) (1,01) OH Group 1 (0.15 gpm/sq.ft) Standard Response 16 x 20 48(182) 18.4 (4,9 x 6,1) (1,27) 6 to 12 155,200 8 (150 to 300) (68,93) (2,4) 16 x 16 51 (193) 20.7 Series DS-3(TY5339) (4,9 x 4,4) (1,43) Horizontal Sidewall 16 x Dry-Type Sprinkler(ECOH) (4,9 x 5,5) 58 (220) (1,85) OH Group 2(0.20 gpm/sq.ft) Standard Response 16 x 20 64(242) 32.7 (4,9 x 6,1) (2,25) Notes 1. Backwall(where sprinkler is located)by sidewall(length of throw). 2. Requirement is based on minimum flow in GPM from each sprinkler.The indicated residual pressures are based on the nominal K-Factor of 11.2. 3. The centerline of the sprinkler waterway is located below the deflector as shown in Figures 2,3,and 4. 4. Minimum spacing is for lateral distance between sprinklers located along a single wall.Otherwise adjacent sprinklers(that is,sidewall sprinklers on an adjacent wall,on an opposite wall,or pendent sprinklers)must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized. TABLE C SERIES DS-3 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS — UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA — Temperatures for Heated Areal Ambient Temperature Exposed to Discharge End 40°F(4°C) I 50°F(10°C) I 60°F(16°C) of Sprinkler Minimum Exposed Barrel Length, Inches(mm)2 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE D EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS — MINIMUM RECOMMENDED LENGTHS — 89 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 4 • Page 4 of 8 Design ORDER 1 "( 6E to 1149,4 FACE MOOF UNTING 3"to 45-1/4"(76,2 to 1149,4 mm) MOUNTING IN 1/4"(6,4 mm)INCREMENTS SURFACE 2"±1/8 TYCO Series DS-3, Standard FACE OF (50,8±3,2 mm) Response, Extended Coverage SPRINKLER FITTING 2.3/4 DIA. 9/16"(14,3 mm) Ordinary Hazard, Horizontal Sidewall, 1"NPT, (69,9 mm) Dry-Type Sprinklers (ECOH) are for NOMINAL MAKE-IN MI use in ordinary hazard occupancies 9/16"(14,3 mm) =' 1 with non-combustible unobstructed III- ��� f (83,7 mm) construction x exceeding and inches a ceiling fin foot slope �f� 3-11/16"DIA. not exceeding 2 inches per foot(9.2°), '— using the design criteria provided in Table C, as well as any additional SPRINKLER FITTING 1 requirements specified in NFPA 13 for (REFER TO DESIGN \\ CENTERLINE Extended Coverage Sidewall Spray CRITERIA SECTION) OF WATERWAY Sprinklers. A 36-inch (914 mm) clearance must FIGURE 2 be maintained between the top of the SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER sprinkler deflector and any miscella- WITH FLUSH ESCUTCHEON(TY5339) neous storage. Series DS-3 Dry Type Sprinklers may be installed on sloped ceilings in loading docks with a maximum roof ORDER LENGTHS: FACE OF slope of 4 inches per foot (18.4°) as 1"to 44"(25,4 to 1117,6 mm) MOUNTING shown in Figure 8 and using the design IN 1/4"(6,4 mm)INCREMENTS SURFACE criteria provided in Table C. 4-1/8'±3/8" FACE OF (104,8±9,5 mm) Sprinkler Fittings SPRINKLER FITTING Install 1-Inch NPT Series DS-3 1"NPT 2-3/4"DIA. 9/16"(14,3 mm) Dry Type Sprinklers in the 1-Inch NPT (69,9 mm) \ outlet or run of the following fittings: NOMINAL MAKE-IN 9/16"(14,3 mm) •malleable or ductile iron threaded IIIII ,I' , tee fittings that meet the dimen- sional requirements of ANSI B16.3 i } (88,9 mm) (Class 150) SPRINKLER FITTING \' \ t •cast iron threaded tee fittings that (REFER TO DESIGN meet the dimensional requirements ( CENTERLINE of ANSI 816.4 Class 125). CRITERIA SECTION) OF WATERWAY B16.4(Class Do not install Series DS-3 Dry-Type Sprinklers into elbow fittings.The Inlet of the sprinkler can contact the interior FIGURE 3 of the elbow. SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER WITH DEEP ESCUTCHEON(TY5339) The unused outlet of the threaded tee is plugged as shown in Figure 6. Series DS-3 Dry-Type Sprinklers can also be installed in the 1-Inch NPT ORDER LENGTHS: outlet of a GRINNELL Figure 730 — - 5-1/4•to 48"(133,4 to 1219,2 mm) Mechanical Tee. However, the use of IN 1/4"(6,4 mm)INCREMENTS MINIMUM the Figure 730 Tee for this arrangement FACE OF SPRINKLER FITTING 2-1/4"(57,2 mm) is limited to wet pipe systems. / DEM TO 1" NPT, OUNTIING The configuration shown in Figure 7 is NOMINAL MAKE-IN SURFACE only applicable for wet pipe systems 9/16"(14,3 mm) where the sprinkler fitting and water- filled pipe above the sprinkler fitting are lair' , not subject to freezing and where the C- f length of the Dry-Type Sprinkler has the minimum exposure length depicted in —'\ 9/16" Figure 10. Refer to the Exposure Length SPRINKLER FITTING (14,3 mm) section. (REFER TO DESIGN CENTERLINE CRITERIA SECTION) OF WATERWAY FIGURE 4 SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER WITHOUT ESCUTCHEON(TY5339) 90 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 5 of 8 NOTICE li TO DRY Do not install Series DS-3 Dry-Type SYSTEM Sprinkler into any other type fitting MAXIMUM without first consulting the Technical THROW \ Services Department. Failure to use the O `'` >.:. . appropriate fitting may result in one of '' the following: "w:. •Failure of the sprinkler to operate prop- OsB-2 ter,, erly due to formation of ice over the INTENDED 6"(152,4 mm) Inlet Plug or binding of the Inlet Plug. FOR FREEZER :.STRUCTURES TO 12"(304,6 mm) - •Insufficient engagement of the Inlet CEILING TO TOP 4/12 pipe threads with consequent leakage. OF SPRINKLER SLOPE AREA DEFLECTOR MAXIMUM Drainage SUBJECT e DISTANCE - In accordance with the minimum TO requirements of the National Fire FREEZING FIGURE 8 Protection Association for dry pipe SPRINKLER PLACEMENT sprinkler systems, branch,cross, and UNDER SLOPED CEILINGS feed-main piping connected to Dry FIGURE 5 IN LOADING DOCKS Sprinklers and subject to freezing SPRINKLER FITTING temperatures must be pitched for — UNHEATED AREA — proper drainage. 2-3/4" DIA. (69,9 mm) Exposure Length DSB-2 mili CLEARANCE INSULATED When using Dry Sprinklers in wet pipe RUN INTENDED HOLE FREEZER sprinkler systems to protect areas OUTLET FOR FREEZER ADHESIVE STRUCTURE subject to freezing temperatures, use PLUGGED STRUCTURES Table D to determine a sprinkler's DSB-2 �� appropriate exposed barrel length VIM S CDT �� � to prevent water from freezing in the ��— connecting pipes due to conduction. SPRINKLER �, The exposed barrel length measure- FIrnNG IIF ment must be taken from the face of (SEE DESIGN I ' �� the sprinkler fitting to the surface of the cf CRITERIA I structure or insulation that is exposed SECTION) ` ! � to the heated area. Refer to Figure 7 for TO DRY r 1111. an example. SYSTEM STRAP TIES DS-3 For protected area temperatures (ENDS ON AREA SHOWN between those given above, the SUBJECT OPPOSING WITH FLUSH minimum recommended length from TO SIDES OF ESCUTCHEON the face of the fitting to the outside of FREEZING Boor) the protected area may be determined FIGURE 9 by interpolating between the indicated FIGURE 6 MODEL DSB-2 DRY SPRINKLER values. SPRINKLER FITTING BOOT WITH SERIES DS-3 — UNHEATED AREA — DRY-TYPE PENDENT SPRINKLER Clearance Space - In accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13, when EXPOSURE r connecting an area subject to freezing For wet pipe system installations of LENGTH and an area containing a wet pipe `(SEE DESIGN 1-Inch NPT Series DS-3 Dry Type sprinkler system,the clearance space CRITERIA SECTION) Sprinklers connected to CPVC piping, around the sprinkler barrel of Dry Type Aar! use only the following TYCO CPVC Sprinklers must be sealed. Due to FACE OF fittings. temperature differences between two SPRINKLER •1" x 1" NPT Female Adapter (P/N areas, the potential for the formation ,— �/FITTING 80145) of condensation in the sprinkler and (I •1" x 1" x 1" NPT Sprinkler Head subsequent ice build-up is increased. If UL Adapter Tee(P/N 80249). this condensation is not controlled, ice build-up can occur that might damage DSB-2 For dry pipe system installations, use the dry-type sprinkler and/or prevent INTENDED only the side outlet of maximum 2-1/2- proper operation in a fire situation. FOR FREEZER inch reducing tee when locating Series 6 STRUCTURES DS 3 Dry Type Sprinklers directly Use of the Model DSB-2 Dry Sprinkler below the branch line.Otherwise, use Boot,described in technical data sheet HEATED the configuration shown in Figure 6 to TFP591 and shown in Figure 9, can AREA assure complete water drainage from provide the recommended seal. above Series DS-3 Dry Type Sprinklers FIGURE 7 and the branch line. Failure to do so SPRINKLER FITTING may result in pipe freezing and water — HEATED AREA — damage. 91 I CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 6 of 8 Do not install any bulb-type sprinkler if Care and the bulb is cracked or there is a loss of liquid from the bulb.With the sprinkler Maintenance ;. held horizontally, a small air bubble should be present.The diameter of the TYCO Series DS-3 Dry-Type Sprinklers ' y1 air bubble is approximately 1/16 inch must be maintained and serviced (1,6 mm)for the 135°F(57°C) rating to in accordance with the following �/ ► 1/8 inch(3,2 mm)for the 360°F(182°C) instructions. ;�1, rating. 1� Obtain a leak-tight 1-Inch NPT sprinkler NOTICE DO NOT joint by applying a minimum-to- Before closing a fire protection system maximum torque of 20 to 30 ft. lbs. main control valve for maintenance (26,8 to 40,2 Nm). Higher levels of work on the fire protection system torque may distort the sprinkler Inlet that it controls, obtain permission to with consequent leakage or impairment shut down the affected fire protection of the sprinkler. systems from the proper authorities FIGURE 10 Do not attempt to compensate and notify all personnel who may be - DO NOT GRASP DEFLECTOR - for insufficient adjustment in an affected by this action. - Escutcheon Plate by under or over- Absence of the outer piece of an tightening the Sprinkler. Re-adjust the escutcheon, which is used to cover a WRENCH FLAT position of the sprinkler fitting to suit. ENGAGEMENT clearance hole, may delay the time to t-P. AREA 1. Install horizontal sidewall sprinklers sprinkler operation in a fire situation.4-1111. B Assso with the center line of waterway A Vent Hole is provided in the Bulb Seat parallel to the ceiling and perpen- Fi ure 1 to indicate if the Dr Sprinkler WRENCH I dicular to the back wall surface.The ( g ) y p FLATS "TOP" on the deflector must is remaining dry. Evidence of leakage face upwards toward the ceiling. from the Vent Hole indicates potential `� leakage past the Inlet seal and the need hG 2. With a non-hardening pipe-thread to remove the sprinkler to determine sealant such as TEFLON applied to the cause of leakage;for example, an the Inlet threads, hand-tighten the improper installation or an ice plug. sprinkler into the sprinkler fitting. Close the fire protection system control APPLY Do not grasp the sprinkler by the valve and drain the system before WRENCH AS deflector(Figure 10). removing the sprinkler. SHOWN 3. Wrench-tighten the sprinkler using Exercise care to avoid damage before, either during, and after installation. Never FIGURE 11 a pipe wrench on the Inlet Band or paint, plate, coat, or otherwise alter •W-TYPE 8 SPRINKLER WRENCH the Casing(Figure 1). automatic sprinklers after they leave the factory. • the W-Type 8 Sprinkler Wrench on Non-factory applied paint can Installation the Wrench Flat(Figure 11). adversely delay or prevent sprinkler Series DS-3 Dry-Type S Sprinklers must Apply the Wrench Recess of the operation in the event of a fire. P W-Type 8 Sprinkler Wrench to the Re laces sprinklers that: be installed in accordance with the Wrench Flat. p P following instructions. • were damaged by dropping,striking, Note:If sprinkler removal becomes NOTICE necessary, remove the sprinkler the like.twisting,wrench slippage,or using the same wrenching method Series DS-3 Dry-Type Sprinklers must noted above. Sprinkler removal • were modified or over-heated. only be installed in fittings that meet is easier when a non-hardening • have cracked bulbs or have lost liquid the requirements of the Design Criteria sealant was used and torque guide- from the bulbs.Refer to the Installation section. Refer to the Design Criteria lines were followed. After removal, Section in this data sheet. section for other important require- inspect the sprinkler for damage. ments regarding piping design and 4. After applying a wall finish, slide on • are leaking or exhibiting visible signs sealing of the clearance space around of corrosion. the Sprinkler Casing. With reference to the outer piece of the Escutcheon Figure 10, do not grasp the sprinkler until it comes in contact with the by the deflector. Failure to follow this mounting surface. instruction may impair performance of For Deep Escutcheons, slide the the device. outer skirt over the inner cup to make firm contact with the mounting surface. 92 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP5SO • Page 7 of 8 Responsibility lies with owners for the Limited Ordering inspection,testing,and maintenance of their fire protection system and devices warranty Procedure in compliance with this document, as well as with the applicable standards of Products manufactured by Tyco Contact your local distributor for avail- the National Fire Protection Association Fire Protection Products (TFPP) are ability.When placing an order,indicate (for example, NFPA 25), in addition to warranted solely to the original Buyer the full product name, including the standards of any other Authorities for ten (10) years against defects description and Part Number(P/N). Having Jurisdiction. The installing in material and workmanship when contractor or sprinkler manufacturer paid for and properly installed and Dry Sprinklers should be contacted relative to any maintained under normal use and When ordering 11.2 K-Factor Series questions. service. This warranty will expire DS-3 Horizontal Sidewall Dry-Type Automatic sprinkler systems are recom- ten (10) years from date of shipment Sprinklers, specify the following mended to be inspected, tested, and by TFPP. No warranty is given for information: maintained by a qualified Inspection products or components manufac- •ModeVSIN TY5339 Service in accordance with local tured by companies not affiliated by requirements and/or national codes. ownership with TFPP or for products •Order Length and components which have been Dry-Type Sprinklers are furnished subject to misuse, improper instal- based upon Order Length as lation, corrosion, or which have not measured from the face of the been installed, maintained, modified wall to the face of the sprinkler or repaired in accordance with appli- fitting (Figure 2, 3, and 4). After the cable Standards of the National Fire measurement is taken, round it to Protection Association, and/or the the nearest 1/4 inch increment. standards of any other Authorities •Inlet Thread Connections Having Jurisdiction. Materials found 1-Inch NPT or 7-R1 by TFPP to be defective shall be either repaired or replaced, at TFPP's sole •Temperature Rating option. TFPP neither assumes, nor •Sprinkler Finish authorizes any person to assume for it, any other obligation in connection •Escutcheon Type with the sale of products or parts of •Part Number from Table E. products. TFPP shall not be respon- sible for sprinkler system design errors Sprinkler Wrench or inaccurate or incomplete infor- Specify W-Type 8 Sprinkler Wrench, mation supplied by Buyer or Buyer's P/N 56-010-4-118. representatives. In no event shall TFPP be liable, in Sprinkler Boot Specify Model DSB-2 Dry Sprinkler contract, tort, strict liability or under Boot, P/N 63-000-0-002. This Part any other legal theory, for incidental, Number includes one Boot,two Strap indirect, special or consequential Ties,and 1/3 oz.of Adhesive(quantity damages, including but not limited to of adhesive is sufficient for installing labor charges, regardless of whether one Boot). TFPP was informed about the possi- bility of such damages,and in no event shall TFPP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties.express or implied, including warranties of merchantability and fitness for a partic- ular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components,whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. 93 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 8 of 8 P/N* 61 - XXX - X - XXX SPRINKLER ESCUTCHEON FINISH FINISH(1) MODEL/SIN 161 Flush Escutcheon TY5339 1 NATURAL BRASS BRASS PLATED (1"NPT),155°F(68°C) Flush Escutcheon 4 WHITE POLYESTER WHITE COATED 163 TY5339 (1°NPT),200°F(93°C) 9 CHROME PLATED CHROME PLATED Deep Escutcheon 171 TY5339 (1"NPT),155°F(68°C) 0 CHROME PLATED WHITE COATED Deep Escutcheon 173 TY5339 (1"NET),200°F(93°C) Without Escutcheon 151 TY5339 (1"NPT),155°F(68°C) Without Escutcheon ORDER 153 (1"NET),200°F(93°C) TY5339 LENGTH(2) 055 5.50" Notes 082 8.25" Use Prefix"I"for ISO 7-R1 Connection;for example,I-61-161-1-055. 1. Does not apply to assemblies without escutcheon. 190 18.00" 2. Dry-Type Sprinklers are furnished based upon "Order Length"as measured per Figures 2,3,and 4.After the measurement is taken,round it to the nearest 1/4 inch increment. 187 18.75" 372 37.25" 480 48.00" TABLE E SERIES DS-3 HORIZONTAL SIDEWALL, DRY-TYPE SPRINKLERS(ECOH) — PART NUMBER SELECTION — Copyright©2011 Tyco Fire Protection Products.All rights reserved. tqc® TEFLON is trademark of The DuPont Corporation. 94 '7 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 . tgC0 Fire & Building Products Technical Services: Tel:(800)381-9312/Fax:(800)791-5500 Model 513 (13) Riser Manifold 1-1/2 thru 6 Inch (DN40 thru DN15O) For NFPA 13 Sprinkler Systems General Technical Description Data _ 111111 The Figure 513 (13) Riser Manifolds Approvals described in this technical data sheet The Figure 513 (13) Riser Manifolds provide the necessary waterflow with a cover tamper switch for the wa- alarm, pressure gauge, alarm test ori- terflow alarm switch are UL Listed, fice, drain, and sight glass equipment ULC Listed, and FM Approved. in a single assembly for use in NFPA The Figure 513 (13) Riser Manifolds P r 13 sprinkler systems as follows: without a cover tamper switch for the ft NFPA 13* waterflow alarm switch are UL Listed ", • 1-1/2 Inch (DN40) and FM Approved. ; Male Thread x Female Thread Maximum Working Pressure rg • 1-1/2 thru 6 Inch(DN40 thru DN150) 175 psi (12,1 bar) Groove x Groove Test Orifice 5.6K(80K) 'Although the Riser Manifold described in Assembly this data sheet is intended for NFPA 13 nections and/or listed mechanical sprinkler systems,it may be used for NFPA The manifold body of the Figure 513 is grooved connections, as applicable 130 or 13R residential sprinkler systems, ductile iron, whereas the manifold p body of the Figure 13 is cast iron. The Step 2. Connect the drain line, and where a test orifice of 5.6K(80K)is accept- then close the drain valve. able. two assemblies are completely inter- then close the drain valve. changeable in function, application, Step 3. Refer to Figure 3 for wiring The variety of sizes and grooved end and end-to-end laying length. guidance. All wiring must be per- connections allow cost effective and Finish formed in accordance with the Author- easy transition to check valves,control Red painted. ity Having Jurisdiction and/or the Na- valves, and system piping. The Riser tional Electrical Code. Manifolds maybe installed in either the Step 4. Refer to Figure 4 for optional horizontal(flow switch on top)or verti- Installation relief valve. cal (flow going up) for both single sprinkler rises and floor control in high The Riser Manifolds may be installed Step 5. Place the system in service by rises. in either the horizontal (flow switch on filling the system with water.When fill- top) or vertical (flow going up). The ing the system, partially open the con- WARNING inlet of the Riser Manifold may be di- trol valve to slowly fill the system. Fill- The Riser Manifolds described herein rectly connected to a shut-off control ing the system slowly will help avoid must be installed and maintained in valve. damaging the waterflow alarm switch. compliance with this document, as well as with the applicable standards NOTES After the system is fully pressurized, of the National Fire Protection Asso- Where applicable pipe thread sealant completely open the control valve. ciation, in addition to the standards of is to be applied sparingly. Use of a Step 6. Secure all supply valves any other authorities having jurisdic- non-hardening pipe thread sealant is open. tion. Failure to do so may impair the recommended. performance of these devices. Never remove any piping component The owner is responsible for maintain- nor correct or modify any piping defi- ing their fire protection system and de- ciencies without first depressurizing vices in proper operating condition. and draining the system. The installing contractor or sprinkler Step 1. Install the manifold body with manufacturer should be contacted the flow arrow pointing in the down- with any questions. stream position using threaded con- Page 1 of 6 APRIL; 2006 TFP962 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Page 2 of 6 TFP962 NO. DESCRIPTION QTY. P/N 1 1-1/2"Manifold Body, NOTES: Male x Female NPT 1 N/A Groove x Groove 1 N/A 1. Approximate weight,11.2 lbs.(5,1 kg). 2 Waterflow Alarm Switch: 2. ULC Listed Manifolds are equipped with VSR-SF with Paddle, Cover Tamper Switches installed internal ULIFM 1 971-096-00 to the Watertow Alarm Switches. VSR-SF with Paddle and 3. CH:Common Hardware Cover Tamper Switch, ULC/FM 1 976-519-02 3 300 psl/2000 kPa Water Pressure Gauge .. 1 2341 3 / -41> Ili ill- 10'(254,0 mm) mt I —+-D Q II 1I 0r• 14-1/4" Male x Female NPT, <1 P' (362,0 mm) Groove x Groove Manifolds bit) m ot an 11 i 1 L-i 1.1/8"(282,6 mm) I g Drain Valve -■■^� Drain Valve £ Male x Male NPT (Normally set ■ it (Normally Manifolds to"Drain") omma Closed) ,'� r_ ■ NMI O 1 2 5-3/16' y, 3-1/2" 3/4' 1' (131,8 mm) (88,9 mm) (19,1 mm) NPT _ 6-1/8' (155,6 mm) 12-5/8' (320,7 mm) FIGURE 1 1-1/2 INCH(DN40) RISER MANIFOLD ASSEMBLY AND DIMENSIONS 97 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 , TFP962 Page 3 of 6 2 INCH(DN50)MANIFOLD 4 INCH(DN100)MANIFOLD 6 INCH(DN150)MANIFOLD NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY P/N 1 2'Manifold Body, 1 4"Manifold Body, 1 6"Manifold Body, Groove x Groove 1 N/A Groove x Groove 1 N/A Groove x Groove 1 N/A 2 Waterflow Alarm Switch: 2 Waterflow Alarm Switch: 2 Waterflow Alarm Switch: VSC with Paddle, VSC with Paddle, VSC with Paddle, UUFM 1 976-357-01 UL/FM 1 976-357-04 UUFM 1 976-357-05 VSC with Paddle and VSC with Paddle and VSC with Paddle and Cover Tamper Switch, Cover Tamper Switch, Cover Tamper Switch, ULC/FM 1 976-520-01 ULC/FM 1 976-520-04 ULC/FM 1 976-520-05 3 300 psi/2000 kPa 3 300 psi/2000 kPa 3 300 psi/2000 kPa Water Pressure Gauge .. 1 2341 Water Pressure Gauge .. 1 2341 Water Pressure Gauge .. 1 2341 2-1/2 INCH(DN65)MANIFOLD Manifold Nominal Installation Dimensions in Inches and(mm Drain Size Weight NO. DESCRIPTION QTY. P/N Size A B C D E F G H lbs.(kg) 2 Inch 16-3/4 13 9/16 5-3/8 63/8 13-1/16 3-1/2 1"NPT 13.5 1 2-1/2"Manifold Body, (DN50) (425,5) (330,2) (14,3) (136,5) (161,9) (331,8) (88,9) (6.1) Groove x Groove 1 N/A 2-1/2 Inch 17-3/16 13 1 5-3/4 6-7/6 13-3/4 3-1/2 16,8 2 Waterflow Alarm Switch: (DN65) (436,6) (330,2) (25,4) (146,1) 1-1/4"NPT VSC with Paddle, ) (174,6) (349,3) (88,9) (7,6) UL/FM 1 976-357-02 3 Inch 17-3/16 13 1 6 7-1/8 14-1/4 3-1/2 1-1/4"NPT 18.7 VSC with Paddle and (DN80) (436,6) (330,2) (25,4) (152,4) (181,0) (362,0) (88,9) (8,5) Cover Tamper Switch, 4 Inch 20-1/2 13 4-5/16 7-9/16 9-1/16 165/8 4-1/2 2'NPT 32.7 ULC/FM 1 976-520-02 (DN100) (520,7) (330,2) (109,5) (192,1) (230,2) (422,3) (114,3) (14,8) 3 300 psi/2000 kPa 6 Inch 20-1/2 13 4-5/16 8-1/2 10 18-1/2 65/8 41,6 Water Pressure Gauge .. 1 2341 (DN150) (520,7) (330,2) (109,5) (215,9) (254,0) (469,9) (168,3) 2"NPT (18,9) 3 INCH(DN80)MANIFOLD NO. DESCRIPTION QTY P/N 1 3"Manifold Body, 1 3 / Groove x Groove 1 N/A 2 Waterflow Alarm Switch: -- VSC with Paddle, . �,N ■ UUFM 1 976-357-03 VSC with Paddle and d b Cover Tamper Switch, Drain Valve '- hi lilt ULC/FM 1 976-520-03 (Normally It r - 3 300 psi/2000 kPa Closed) Water Pressure Gauge .. 1 2341 55 NOTES: A .. of 2 1. ULC Listed Manifolds are equipped with IIPI' gl Cover Tam per r Swi Switches installed internal B _to the Waterflow Alarm Switches. 2. CH:Common Hardware ■ERIN IM iri I____ i „4; r.,-„, ■ tTest C D &Drain Valve ~G (Normally set - E - - to"Drain") H • - F FIGURE 2 2 thru 6 INCH(DN50 thru DN150) RISER MANIFOLD ASSEMBLY AND DIMENSIONS 98 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Page 4 of 6 TFP962 SWITCH TERMINAL CONNECTIONS UNINSULATED CLAMPING SEVERED LOOPED SECTION CAUTION: PLATE STRIPPED SINGLE An uninsulated section of a TERMINAL ENDS CONDUCTOR single conductor is not SEPARATE . permitted to be looped around '� CONDUCTORS CLAMPING the terminal and serve as two , PLATE separate connections.The TERMINAL wire must be severed to serve INCOMING as two separate connections, �. thereby providing supervision of the connection in the event that the wire becomes dislodged from the terminal. OUTGOING IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS CONTACTS SPOT(Form C) END OF LINE LOCAL RESISTOR CONTACT RATING .... 5A @ 125 VAC SIGNAL 2.5A @ 30 VDC DEVICE /L NC L NO n NC WI NO• n NC M 1 COM COM CONTROL POWER PANEL NO FLOW NON-SUPERVISED STYLE B/CLASS B CONDITION CIRCUIT SUPERVISED CIRCUIT (SEE NOTE) NOTE: For supervised circuits,see"Switch Terminal Connections"above.The Watertlow Alarm Switch has Iwo switches,one can be used to operate a central station,proprietary or remove signaling unit,while the other contact is used to operate a local audible or visual annunciator. COVER TAMPER SWITCH(ULC ASSEMBLIES ONLY) CONTACTS SPOT(Form C) CONTACT RATING .... 3A @ 250 VAC 5A @ 125 VAC !, 1mA@ 5 VDC min. NO • NC COM CONTACTS SHOWN WITH COVER IN PLACE FIGURE 3 WIRING GUIDANCE 99 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • , TFP962 Page 5 of 6 1-1/2"(DN40)Manifold Only: NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. PM To install optional Pressure Relief Trim on 1 3/8"Copper Tubing, 2 Pressure Relief Valve. a 1-1/2"(DN40)Manifold,a 1/2"NPT outlet 2"(0N50)Manifolds .... 1 971-124-01 175 psi,Nonadjustable .. 1 198-066-00 must be provided by the installer on the 2-1/2"(DN65)and 3 90°Compression Fitting system outlet piping,and a connection back 3"(DN80)Manifolds .... 1 971-124-02 Fitting 2 CH to the manifold drain trim must be fabricated 4"(DN100)and 4 1"x 1/2'Reducing Hex with installer supplied 3/8"copper tubing. 6"(DN150)Manifolds ... 1 971-124-03 Bushing 1 CH Discard unused trim components. CH:Common Hardware 3 1/2"NPT Installer Outlet Provided System Outlet aill 1 3 4 N. Piping Installer �'� Fabricated !ir 0 3!8"Copper— Q�� Tubing — 2"(DN50),2-112"(DN65),3"(DN80),4"(DN100),or lllllllllllllllllllllll�P Q II 6"(DN150)Manifold .q P' 3 I Manifold Iu�•``rI, _ Drain Trim a _.0. •r J•c: I__I •4iI 10 1I- 1 (DN40)� Manifold O ,O FIGURE 4 OPTIONAL PRESSURE RELIEF VALVE Riser Manifold component in the field. Alarm/Flow Test Procedure Care and Only the pressure gauge, waterflow Maintenance alarm switch, or relief valve can be Step 1. Place the test&drain Valve in replaced. If any other problems are the "test" position. encountered the entire riser manifold Step 2. Fully open the drain valve. The following inspection procedure must be replaced. Make certain that drainage water will must be performed as indicated,in ad- The alarm/flow test procedure will re- not cause any damage or injury. dition to any specific requirements of the NFPA, and any p impairment must suit in operation of the associated alarms. Consequently, notification Step 3.Verify operation of associated be immediately corrected. must be given to te owner and the fire alarms. The owner is responsible for the in- department, central station, or other Step 4. Close the drain valve. spection, testing, and maintenance of signal station to which the alarms are Step 5. Place the test&drain Valve in their fire protection system and de- connected, and notification must be vices in compliance with this docu- given to the building occupants. the"drain" position. ment, as well as with the applicable Step 6. Verify that the residual flow- standards of the National Fire Protec- Before closing a fire protection system p control valve for inspection or mainte- ing) pressure indicated by the pres- tion Association (e.g., NFPA 25), in sure gauge is no less that originally addition to the standards of any nonce work on the fire protection sys Y recorded for the system when it was authority having jurisdiction. The in- tem that it controls,permission to shut first installed. stalling contractor or product manufac- down the effected fire protection sys- turer should be contacted relative to tern must first be obtained from the Step 7. Close the drain valve. any questions. proper authorities and all personnel Step 8.Verify that the static(not flow- who may be affected by this action ing) pressure indicated by the pres- It is recommended that automatic must be notified. sure gauge is no less that originally sprinkler tested, smain ai d inspected, After placing a fire protection system recorded for the system when it was tested, and maintained by a qualified in service, notify the proper authorities first installed. y Inspection Service in accordance with y local requirements and/or national and advise those responsible for moni- codes. toring proprietary and/or central sta- tion alarms. NOTES No attempt is to be made to repair any 100 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Page 6 of 6 TFP962 Limited Ordering Warranty Information Products manufactured by Tyco Fire& Riser Manifold: Building Products (TFBP) are war- Specify; Size (specify), Figure 513, ranted solely to the original Buyer for (specify connection type inlet x outlet) ten(10)years against defects in mate- Riser Manifold (specify - without or vial and workmanship when paid for with) a cover tamper switch for the and properly installed and maintained waterflow alarm switch, P/N (specify). under normal use and service. This warranty will expire ten (10) years NOTES from date of shipment by TFBP. No Orders for Figure 513 may be filled warranty is given for products or corn- with a Figure 13. The two assemblies ponents manufactured by companies are completely interchangeable in not affiliated by ownership with TFBP function, application, and end-to-end or for products and components which laying length. have been subject to misuse,improper If a ULC Listing is required, the Riser installation, corrosion, or which have Manifold must be ordered with a cover not been installed, maintained, modi- tamper switch for the watertlow alarm fled or repaired in accordance with ap- switch. plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities UL/ULC/FM Assemblies Having Jurisdiction. Materials found with Cover Tamper Switch by TFBP to be defective shall be either 1-1/2 Inch(DN40) repaired or replaced, at TFBP's sole MTx FT P/N 4086 option. TFBP neither assumes, nor 1-1l21nch(DN40) MT x MT P/N 4087 authorizes any person to assume for it, 2 Inch(DN50) any other obligation in connection with G x G P/N 4090 the sale of products or parts of prod- 2-1/2 Inch(DN65) ucts.TFBP shall not be responsible for G x G P/N 4091 3 Inch(DN60) sprinkler system design errors or Mac- G x G P/N 4092 curate or incomplete information sup- 4 Inch(DN100) plied by Buyer or Buyer's repre- GxG P/N4095 sentatives. 6 Inch(DN150) G x G P/N 4096 In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, UL/FM Assemblies Without Cover Tamper Switch indirect,special or consequential dam- 1-1/2 Inch(DN40) ages, including but not limited to labor MTx FT P/N 4055 charges, regardless of whether TFBP 1-1/2 Inch (DN40) was informed about the possibility of MT x MT P/N 4056 such damages, and in no event shall 2 Inch(DN50) G x G PIN 4060 TFBP's liability exceed an amount 2-1/2 Inch(DN65) equal to the sales price. G x G P/N 4061 The foregoing warranty is made in lieu 3 Inch(DN80) 9 9 Y G x G P/N 4062 of any and all other warranties. ex- 4Inch(DN100) press or implied including warranties G x G P/N 4065 of merchantability and fitness fora oar- 6 Inch(DN150) ticular purpose. c x G P/N aoss This limited warranty sets forth the ex- clusive remedy for claims based on Optional Pressure Relief Valve: failure of or defect in products,materi- Specify: Operational Pressure Relief als or components, whether the claim Valve and Trim for use with (specify is made in contract, tort, strict liability size) Figure 513 or 13 Series Riser or any other legal theory. Manifold, P/N (specify). This warranty will apply to the full ex- tent permitted by law.The invalidity,in 1-112"or 2" P/N 4063 whole or part, of any portion of this 4" 6" 3" P/N 4072 or warranty will not affect the remainder. 4"or s" P/N 4073 Replacement Parts: Specify:(description)for use with Fig- ure 513 or 13 Riser Manifold,P/N(Ref. Figure 1 or 2,as applicable). 101 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446 CAMP PARSONS MATERIAL SUBMITTAL • JOB#1406073 SECTION 2. 5 AUTOMATIC DRAIN DEVICE 102 CAMP PARSONS MATERIAL SUBMITTAL ■ I \0 �� �� JOB#1406073 Brass Trim Miscellaneous Brass F P P t Ball Drips, Brass eill FPPI Ball Drips feature two piece brass construction.Their designed use is to prevent moisture accumulation on the"dry"side of Fire , Department Connections when used in conjunction with an approved check valve. ' Part No. Description Box Qty. ' 08-540-00 1/2" IPS Ball Drip 10 08-541-00 3/4" IPS Ball Drip 10 08-542-00 1/4" x 1/2" IPS Ball Drip 20 Extension Nipples, Brass -— Designed to be used to correct sprinkler head elevation without removing or re-cutting sprinkler drop.THIS PRODUCT IS COVERED _ � BY ADDITIONAL DISCLAIMERS REGARDING SUITABILITY AND USE. PURCHASER AND USER TAKE FULL RESPONSIBILITY FOR /".24. '-.s.4-"‘'' . t':":•:' THE USE OF THIS PRODUCT. FPPI WILL NOT BE HELD LIABLE FOR PRODUCT FAILURE OR DAMAGE CAUSED BY USE. SEE -;r. , ,- " MSDS FOR DETAILS. C c Part No. Description Box Qty. .0 08-570-00 1/2" takeout x 1/2" IPS Br. Spr. Ext. 100 c 08-571-00 3/4" takeout x 1/2" IPS Br. Spr. Ext. 75 08-572-00 1" takeout x 1/2" IPS Br. Spr. Ext. 50 08-573-00 11/2" takeout x 1/2" IPS Br. Spr. Ext. 50 • 08-574-00 2" takeout x 1/2" IPS Br. Spr. Ext. 25 n 08-575-00 1/2" takeout x 3/4" IPS Br. Spr. Ext. 50 « r 08-576-00 3/4" takeout x 3A4" IPS Br. Spr. Ext. 50 d Orifice Union a Part No. Description Box Qty. i"r r 08-537-00 Orifice Union 1" IPS x Y" 5 1 08-539-00 Orifice Union 1/2" IPS x 3/3z" 10 i'r' Sight Glass, Brass FPPI Sight Glasses feature brass construction with Lexan view -- windows for observation of flow. Typical use is for the sprinkler systems Inspectors'Test trim.Available in straight and restricted orifice patterns. Part No. Description Box Qty. 08-529-00 1" Sight Glass MxF 3 '' 4 08-530-00 1" IPS Sight, 1/2" Orifice FxF = 5 e�'"" .rI 08-532-00 1" Sight Glass 17/33" Orifice FxF 5 7.� 08-531-00 11/4" IPS Sight Glass MxF 4 08-533-00 11/2" IPS Sight Glass FxF 1 08-535-00 2" IPS Sight Glass FxF 1 103 19 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 a HANGERS AND SWAY BRACING 104 ,, V V FDLCD _ www•tolco.com NIBCO Revision 12/18/2008 Fig. 200 - "Trimline" Adjustable Band Hanger OustsrEa Fig. 200R (Import) - "Trimline" Adjustable Band Hanger w/Retainer Ring Size Range — 1/2" thru 8" pipe Material — Carbon Steel, Mil. Galvanized to G90 ,� specifications ,...--1-.0- --- -- Function — For fire sprinkler and other general piping - ``"J� Q purposes. Knurled swivel nut design permits hanger 8; `1 / adjustment after installation. \ / / = Features — - / ` ' / ! „ • (1/2" thru 2") Flared edges ease installation for B /� j / all pipe types and protect CPVC plastic pipe N I - %1 t I from abrasion. Captured design keeps adjusting ' , nut from separating with hanger. Hanger is eas- A t', ' ily installed around pipe. '-';—"' A ,,ill(s, / / • (21/2" thru 8") Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. Fig.200 1"-2" Fig.200 21h" -8" Approvals — Underwriters' Laboratories listed o (1/2" thru 8") in the USA(UL) and Canada(cUL) _ 'tameo for steel and CPVC plastic pipe and Factory Mutual -' Engineering Approved (3/4" thru 8"). Conforms to U1. Federal Specifications WW-H-171 E, Type 10 and 8 / _� ._ Manufacturers Standardization Society SP-69, Type �`� ,, 1 10. B le, ,/ ; /;' 1I / Maximum Temperature — 650°F I f� B Finish — Mil. Galvanized. Stainless Steel materials will '/ ;+=- /1,,l t 1 it be supplied with (2) hex nuts in place of a knurl nub. jar - ; /,' ;-±'- it Ir Order By — Figure number and pipe size 1 1 ° ;; / Note — Figure 200R (import) with retainer ring and A ,\ \'`; __ non-captured knurl nut. -- Fig.200R 21/2"-8" Fig.200R 1/2"-2' Dimensions •Weights Pipe Rod Size Max. Rec. Approx. Size Inch Metric A B Load Lbs. Wt./100 1/2 3/8 8mm or 10mm 31/4 25/3 400 11 3/4 3/8 8mm or 10mm 31/8 21 400 11 1 3/8 8mm or 10mm 3% 2% 400 12 11/4 3/8 8mm or 10mm 33 2?/8 400 13 11/4 3/8 8mm or 10mm 37/8 21/2 400 14 2 3/8 8mm or 1 Omm 41 3 400 15 21/4 3/8 10mm 5% 41/3 600 27 3 3/8 10mm 57/3 4 600 29 31k 3/8 10mm 7% 51/4 600 34 4 3/8 1 omm 73/8 5 1000 35 5 1/2 12mm 91/2 61/4 1250 66 6 1/2 12mm 101/3 6314 1250 73 8 1/2 12mm 131/8 83/4 1250 136 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON A405 CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737 0330 CUSTOMER SERVICE•800.786.5266 91 www.tolco.com MIIM ' . S SIDEWIHDERSTM i-, M ';m '8� reu dil„y 1( -1 &: `"W1iz r }. ;4 [u ti 'Nntittl lood gut Driver 1/4" 8018957 4016 SWG 100 1/4 X 1 25 9.38 125 e#14SW Nut Diver 1/4 8019957 300 SWG200 1/4X2 25 10.00 125 x Sidewinders and /2"Rod Sammys 3/8" 8020957 18 SWG 10 1/4 X 1 25 7.50 125 e, 3/8" 8021957 19 SWG 20 1/4 X 2 25 8.75 125 I ,` 3/8" 8022925 26 SWG 25-380 3/8 X 2-1/2 25 12.81 125 3/8" 8023925 25 SWG 30 1/4 X 3 25 10.63 125 ?__ 1 �. - � teel � ,_ •max#- «_ .e. ...., 3/8" 8050957 39 SWD 10 114-14 X 1 25 7.50 125 3/8" 8051957 40 SWD 15 1/4-14 X 1-1/2 25 9.38 125 Part 4 8114910 3,0 8052957 41 SWD 20 1/4-14 X 2 25 8.13 125 Item#101 318" 8053957 --42 SWD 516 5/16-18 X 1-114 25 8.75 125 e 3/8" 8054957 46 SWDR 1-1/2" 1/4-20 X 1-1/2 25 9 06 125 3/8" 8055957 43 SWDR 1" 1/4-20 X 1 25 8.75 125 ` £'' 318" 8056957 44 SWDR 516 5/16-18 X 1-1/4 25 10.31 125 3/8" 8057957 45 SWT 15 12-24 X 1-1/2 25 7.81 125 y_._ Rod Screw Box Weight Case Concrete Approvals Size Part# Item # Model Descriptions Qty. (per 125) Qty 1/4" 8062957 1900 SWC 200 5/16 X 1-1/2 25 9.38 125 3/8" 8061957 65 SWC 20 5/16 X 1-1/2 25 9.38 125 • Most Items Available in Stainless Steel • NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! * Use with 3/8" Sammy Swivel HeadTM 10 Screw Box Weight Case Approvals Part# Item# Model Descriptions Qty. (per 125) Qty • 17°deflection from vertical _ U.S.Patent No. t; + .. ., ... :c i:" .. C C° ` ..:t1,'° T., -. $u s. :a 6,4.43,680 • Accommodates up to 8139957 4702 SH-GS7 20 1/4 x 2 25 9.38 125 3-1/2 x 12 pitch roof 8140957 4703 SH-GST 22SS 1/4 x 2 25 9.38 125 • Also available in stainless steel •. 8141957 4704 SH-GST 30 114 x 3 25 10.94 125 8142957 4705 SH-GST 30SS 1/4 x 3 25 10.94 125. ` 1 • Use#14 Nut Driver(black) t�. ..$s r= > .g " , t Y .i." 8137957 4700 SH-DSTR 1 1/4-20 x 1 25 9.38 125 0 8138957 4701 SH-DSTR 1 -SS 1/4-20 x 1 25 9.38 1250 ctl Patent Pending SAMMY X-PRESSTM Threaded Rod Djfe y Steel Screw Box Weight Case slat Approvals Part# Item# Model of om Gao9eM ,r* Ga Descriptions Qty. (per 125) Qty. Thin / m f ... k /� 1/4-20 x 1-1/8 tit" 22-20 8150922 500 XP 20 25 10.3 125 Sammy X-Press 20 " "� 1/4-20 x 1-1/8 �. :-"`"P ,.:: I --. 18-16 8153922 503 XP 35 25 10-3 125 Sammy X-Press 35 Uninstalled,.�,..' - Sammy X-Press It ., _ 8151910 501 XPIT 1 1.02 1 S � r ", s. Installation Tool s yy .y - (Kt Includes:Sleeve,Bit Receiver, Hex Wrench,and 25/64"Drill at) LAL\PRESS TM 8152910 502 XPDB 25/64"Drill Bit 1 0.14 1 Installed 107 SAMMYSTM ' . til3t.� ;., i r F » (il c, &Nr. Lod 1/4" 8001957 20 GST.750 1/4 x 3/4 25 5.93 125 1/4" 8002957 21 GST 100 1/4 x 1 25 6.25 125 4 1/4" 8003957 22 GST 200 1/4 x 2 25 8.13 125 1/4" 8004957 23 GST 300 1/4 x 3 25 9.38 125 1/4" 8005925 24 GST 600 1/4 x 6 25 11.25 125 3/8" 8006957 10 GST.750 1/4 x 3/4 25 5.63 125 3/8" 8007957 11 GST 10 1/4 x 1 25 5.93 125 Oc5 _ NFPA 3/8" 8008957 12 GST 20 1/4 x 2 25 7.50 125 NFPA 3/8" 8009925 27 GST 25-380 3/8 x 2-1/2 25 11.56 125 - '" '~,i NFPA 3/8" 8010957 30 GST 30 1/4 x 3 25 8.75 125 NFPA 3/8" 8011925 403 GST 40 1/4 x 4 25 10.00 125 NFPA 3/8" 8012925 14 GST 60 1/4 x 6 25 11.25 125 1/2" 8013925 8 GST 2 1/4 X2 25 8.75 125 1/2" 8014925 6 GST 2.5-380 3/8 X 2-1/2 25 12.50 125 1/2" 8015925 15 GST 3 1/4 X 3 25 13.13 125 1/2" 8016925 16 GST 4 1/4 X 4 25 13.25 125 1/2" 8017925 17 GST 6 1/4 X 6 25 13.69 125 lob steel Approvals Roo Part# Item# Model Screw' Box Weight Case � Q �Fti Size ,1 ,, Rt, os Qty. (per 125) Qty 1/4" 8024957 50 DSTR 100 1/4-20 X 1 1/4" 8025957 51 DST 100 1/4-14 X 1 25 6.56 125 1/4" 8026957 52 DST 150 1/4-14 X 1-1/2 25 6.88 125 1/4" 8027957 53 DST 200 1/4-14 X 2 25 7.50 125 1/4" 8028957 54 DST 250 1/4-12 X 2-1/2 25 8.44 125 1/4" 8029957 55 DST 300 1/4-14 X 3 25 9.06 125 s 1/4" 8030957 56 TEK 500 12-24 X 1-1/2 25 6.88 125 Nut Drivi (;..1.-= .- NFPA 3/8" 8037957 29 DSTR 1-1/2" 12-24 X 1-1/2 25 7.75 125 Use#14Nu Driv t t, NFPA 3/8" 8038957 30 DSTR 1" 1/4-20 X 1 25 7.19 125 for Sammysanc NFPA 3/8" 8039957 31 DSTR 516 5/16-18 X 1-1/4 25 7.06 125 Sw el Head NFPA 3/8" 8040957 32 DST 10 1/4-14 X 1 25 5.94 125 NFPA 3/8" 8041957 33 DST 15 1/4-12 X 1-1/2 25 6.56 125 I. NFPA 3/8" 8042957 34 DST 20 1/4-14 X 2 25 6.88 125 NFPA 3/8" 8043957 35 DST 25 1/4-14 X 2-1/2 25 7.81 125 NFPA 3/8" 8044957 36 DST 30 1/4-14 X 3 25 8.44 125 r1 NFPA 3/8" 8045957 37 DST 516 5/16-18 X 1-1/4 25 7.50 125 NFPA 3/8" 8046957 38 TEK 50 12-24 X 1-1/2 25 6.88 125 1/2" 8031925 601 DST 2.0 1/4-14 X 2 25 8.44 125 Part#811391 1/2" 8032925 1113 DST 2.5 1/4-14 X 2-1/2 25 9.06 125 Item#100 1/2" 8033925 422 DSTR 1.0 1/4-20 X 1 25 6.25 125 1/2" 8034925 28 DSTR 5.16 5/16-18 X 1-1/4 25 10.00 125 1/2" 8035925 443 DST 5.16 5/16-18 X 1-1/4 25 8.44 125 1/2" 8036925 5 TEK 5.0 12-24 X 1-1/2 25 7.50 125 11Y1 1� * Approvals Rod Part# Item# Model Screw Box Weight Case { onc1 e l I1 e Size Descriptions Qty. (per 125) Qty ja 1/4" 8058957 64 CST 200 5/16 x 1-1/2 25 8.44 125 3/8" 8059957 61 CST 20 5/16 X 1-1/2 25 1.81 125 NFPA 1/2" 8060925 66 108 CST 2 5/16 X 1-1/2 25 8.75 125 y o TOLCO www.tolco.com nn, NIBCO Revision 3/7/2007 Fig. 4 - Standard Pipe Clamp Component of State of California OSHPD Approved CO US USTEO Fig. 4F - Standard Pipe Clamp Felt Lined Seismic RestaiMSSystem Fig. 4PVC - Standard Pipe Clamp PVC Coated Size Range — (Fig. 4) Size 1/2" thru 30" pipe. B Size Range — (Fig. 4F) Size 1/2" thru 21/2" copper tubing _,.._ „ l • Material — Carbon Steel Function — Recommended for the suspension of non-insulated pipe or insulated pipe with ,` '' Y. Fig. 220 shields. (Use Fig. 330 Weldless Eye Nut, Fig. 102 Eye Rod or Fig. 101 Welded Eye '”- r ) '\ A Rod.) Also recommended for attachment of sway bracing up to 31/2" pipe size, for larger ; �J pipe sizes use Fig. 4A. Fig. 4F and Fig. 4PVC are designed to reduce noise and vibration o �' r7 1 and/or prevent electrolysis. /f ({ Approvals — Underwriters' Laboratories Listed in the USA(UL), Canada(cUL) 1/2" -8", and approved by Factory Mutual Engineering, 3/4" - 8". Federal Specification WW-H-171 E, Type 4, 1'/2" thru 24" and Manufacturers Standardization Society SP 69,Type 4. Included cI{. in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development(OSHPD). For additional load. spac- Fig. 4 ing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note — When the Fig. 4 is used as a sway brace, to ensure performance, ' the UL Listing requires that it must be used with other TOLCO® ; brace products. f / Maximum Temperature — 750°F ',„ il Finish — Plain ,, Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, pipe size and finish. Fig. 4F Order Note — When ordering Fig. 4F allow for 3/16" felt on each half of clamp. g Fig. 4PVC Dimensions •Weights Pipe Max. Design Load Lbs. Size A B C D For Service Temp. Approx. Bolt Size 650° 750°F Wt./100 1/2 37/6 1/4 11/2 11/a 5/16 500 445 29 3/4 39/is 1/4 11/4 11/4 5/16 500 445 31 1 39A13 1/4 11/4 15/16 5/16 500 445 35 11/4 4e 3/8 1% 111/i s 5/16 500 445 40 11/2 49A6 3/8 15/6 17/8 5/16 800 715 42 2* 59/16 3/8 2 21/4 3/8 1040 930 93 21/2* 67/6 3/8 21/2 23/4 1/2 1040 930 126 3* 7 3/8 23/4 31/6 1/2 1040 930 141 31/2* 711/6 3/8 31/8 3% 1/2 1040 930 154 4 81/2 5/8 35/16 311/6 1/2 1040 930 229 5 93/4 3/4 37/s 43/8 5/8 1040 930 261 6 115/6 3/4 47/8 51/2 3/4 1615 1440 537 8 135/16 1 5% 6 3/4 1615 1440 625 10 161 1 71/4 71/4 7/8 2490 2220 1378 12 181/2 1 81/4 81/4 7/8 2490 2220 1574 14 20 11/2 9 9 7/8 2490 2220 2103 16 23 11/2 101/4 101/4 7/8 2490 2220 2314 18 251/2 11/4 111/2 111/2 1 3060 2730 3276 20 28 1% 121/2 121/2 11/2 3060 2730 3863 24 331/2 1% 151/4 151/4 11/4 3060 2730 5222 30 411/2 2 19 19 1% 3500 3360 10511 'Meets UL 203A requirements for attachment of sway bracing. Horizontal design load for 1/2"-2"-380#,21/2'-395#,3'-435#,31/2'-540# OFFICE/MANUFACTURING FACIUTY•1375 SAMPSON MG CORONA.CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.786.5266 El wwwrolco.com (2)TOLCO Fig. 4A - Pipe Clamp for Sway Bracing Component of State of California OSHPD Approved C C) IRS Seismic Restraints System Size Range — 4"thru 8" pipe. For sizes smaller than 4" use TOLCO® Fig.4. LISTED Material — Carbon Steel B Function — For bracing pipe against sway and seismic disturbance. Approvals — Underwriters' Laboratories Listed in the USA(UL)and Canada(cUL) 4"thru 8". Included in our Seismic Restraints Catalog approved by the State of ' California Office of Statewide Health Planning and Development(OSHPD). // it Installation Instructions —The Fig.4A is the"braced pipe"attachment ! component of a longitudinal, lateral or riser brace assembly. It is intended to be combined with the"bracing pipe"and TOLCO transitional and structural a attachment component(s)to form a complete bracing assembly. NFPA 13 and/or i OSHPD guidelines should be followed. 4 To Install — Place the Fig.4A over the pipe to be braced.Attach TOLCO ",,., 13 transitional fitting,either Fig.980, 910 or 909,to the clamp ears.Tighten bolts and nuts;torque requirement is a minimum of 50 ft.lbs.Transitional fitting attachment can pivot for adjustment to proper brace angle. Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. C 41,4 Order By— Figure number,pipe size and finish ,.4/.,102. . ../iAltlik:.:i 1 Fig.4A-Longitudinal Brace 5 Fig.4A-Lateral Brace Cooper B-Line,Inc.'s("Cooper B-Line")seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components, resulting in a listed seismic bracing assembly.Cooper B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty, Cooper B-Line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. Dimensions •Weights Pipe Max.Horizontal Approx. Sizes A B C D Bolt Size Design Load WtJ100 4 81/2 9A6 3 3 3% 1600 221 5 93k •As 3'A 4/ Y 1600 253 6 111 sA 5 5'A V 2015 513 8 13''A '/4 6% 6 V th 2015 601 COOPER B-LINE 1375 Sampson Ave•Corona,CA 92879•800.786.5266•FAX:951.737.0330 www.tolco.com 12 COOPER B-Line a To Lco www.tolco.c.m, NIBCO Revision 12/3/2008 Fig. 1001 - Sway Brace Attachment Component of State of CO US LIMO California OSHPD Approved Size Range — Pipe size to be braced: 2W thru 8" IPS.* Pipe size Seismic Restraints System used for bracing: 1" and 11/4" Schedule 40 IPS. Material — Carbon Steel (- Function — For bracing pipe against sway and seismic distur- bance. The pipe attachment component of a sway brace system: The Fig. 1001 is used in conjunction with a TOLCO 900 Series fitting and joined together with bracing pipe per NFPA 13, forming a com- plete sway brace assembly. f...1 Features — Can be used to brace schedules 7 through 40 IPS. I ` Field adjustable, making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no threading of brac- ." ing pipe. Can be used as a component of a four-way riser brace. A Comes assembled and ready for installation. Fig. 1001 has built-in \‘'.i visual verification of correct installation. See installation note below. Installation Note — Position Fig. 1001 over the pipe to be braced and tighten two hex head cone point set bolts until heads bottom out. A minimum of 1" pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Approvals — Underwriters Laboratories Listed in the USA(UL) Maximum Design Load and Canada(cUL). Approved by Factory Mutual Engineering (FM). Sch. 7 1600 lbs. Included in our Seismic Restraints Catalog approved by the State Sch. 10 &40 w/1" Brace Pipe 2015 lbs. of California Office of Statewide Health Planning and Development Sch. 10 &40 w/1 /a Brace Pipe 2765 lbs. (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic FM Approved Design Loads* Restraint Systems Guidelines. 21/2" - 2400 lbs. Finish — Plain 3 4„ 2500 lbs. Note — Available in Electro-Galvanized and HDG finish. 5 8 1500 lbs. Order By — Indicate pipe size to be braced followed by pipe size used for bracing, figure number and finish. Important Note — The Fig. 1001 is precision manufactured to perform its function as a critical component of a complete brac- ing assembly. To ensure performance,the UL Listing requires that the Fig. 1001 must be used only with other TOLCO bracing products. The Fig 1001 is not intended for use with the Fig.907 4-Way Longitudinal Brace Attachment. \ r 11667\ II 1 i WI • • r ,+ if l It I 1 / I ® OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE1440RONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.785.5256 www.tolco.com V TOLCO www.tolco.com , -- NI @CO Revision 3/10/2010 Component of State of Fig. 906 - Sway Brace Multi-Fastener Adapter California OSHPD Approved ct 1.1S LISTED Seismic Restraints System Size Range — Use with 1" and 11/4" TOLCO UL listed Fig. 900 Series Earthquake Brace Attachments. Material — Carbon Steel Application — Allows sway brace fittings to develop greater load carrying ability by providing multiple fastener attachments. The National Fire Protection (NFPA) provides information on fastener loads to various structures. Refer to NFPA 13 (2010) 9.3.5.9.1. Approvals — Underwriters Laboratories Listed in the USA (UL)and Canada(cUL) only when used with TOLCO 900 ill H1 Series Earthquake Brace Attachments. Included in our Seismic Restraints Catalog approved by the State of California H2 Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement infor- mation relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Installation Instructions — The Fig. 906 is a multiple fastener structural attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with a H1 TOLCO transitional attachment, "bracing pipe" and a TOLCO "braced pipe" attachment to form a complete bracing assem- A bly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Attach the Fig. 906 to the structural surface as per fastener design guidelines. Attach other TOLCO transi- tional attachment fitting Fig. 909, 910, 980 or 986. Transitional fitting attachment can pivot for adjustment to proper brace angle. Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number and specify dimensions H1 and H2. Dimensions •Weights Approx. A B C D H1 H2 Wt./100 12 9 2 1/4 Specify Specify Varies TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components, in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON A1?I1.•CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.786.5266 144 www.toleo.com U TOLCO www.rolco.6om NIBCO Revision 1/21/2011 Fig. 980 - Universal Swivel Sway Brace Attachment c LIS LISTED Size Range — One size fits bracing pipe 1" thru 2", TOLCO 12 gauge channel, and all structural steel up to 1/4" thick. ^^ ° Material — Carbon Steel IM Component of State of California OSHPD Approved Function — Multi functional attachment to structure or Seismic Restraints System braced pipe fitting. Features — This product's design incorporates a concen- tric attachment opening which is critical to the performance of structural seismic connections. NFPA 13 (2010) 9.3.5.8.4 �� indicates clearly that fastener table load values are based only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. Installation — The Fig.980 is the structural or transitional A ‘41k4' attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until set bolt head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals — Underwriters Laboratories Listed in the USA(UL) and Canada (cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000, Fig. 2002, Fig. 4A, Fig. 4B or Fig. 4L Pipe Clamp make up a sway brace system of UL Listed attachments and bracing materials which satisfies the require- ments of Underwriters' Laboratories and the National Fire Protection Association (NFPA) Finish — Plain Note — Available in Electro-Galvanized finish. Order By — Figure number and finish. Pat.#6,273,372, Pat. #6,517,030, Pat.#6,953,174, 7 i~\ ' r Pat.#6,708,930, Pat. #7,191,987, Pat. #7,441,730, \\, - • r. . Pat.#7,669,806 Lateral Brace Dimensions •Weights Max. Design Max. Design Approx. A B H* Load Lbs. Load Lbs.** (cULus) (FM) Wt./100 5t/a 17/s 17/32 2765 2800 132 Available with hole sizes to accommodate up to 3/4"fastener. Consult factory. "The loads listed are axial loads on the brace.The horizontal load capacity, H,of the brace is: H= F x sin 0,where 0 is the installation angle measured from the vertical. TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER - NIBCO does NOT warrant against the failure of TOLCO®brand bracing components, in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•13Th SAMPSON AVM CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.786.5266 150 www.tolcu.com CAMP PARSONS MATERIAL SUBMITTAL a, • JOB#1406073 SUPERVISORY DEVICES 119 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 P POTTER BELLS The Symbol of Protection PBA-AC & MBA-DC UL,ULC,and FM Approved Sizes Available: 6" (150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC I2VDC(10.2 to 15.6)Polarized 24VDC(20.4 to 31.2)Polarized Service Use Fire Alarm General Signaling Burglar Alarm " F Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWG stranded wires OL ® -" DC Bells-Terminal strip * - a' Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA-6-12 1750070 .12A 85 76 8(200) 12VDC MBA-8-12 1750080 .12A 90 77 10(250) 12VDC MBA-10-12 1750060 .12A 92 78 6(150) 24VDC MBA-6-24 1750100 .06A 87 77 8(200) 24VDC MBA-8-24 1750110 .06A 91 79 10(250) 24VDC MBA-10-24 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC P13A12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing tglnbh11h1 In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company, LLC • St. Louis, MO, • Phone: 866-572-3005/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400776-REV Y-1 PAGE 1 OF 2 01/13 120 CAMP PARSONS MATERIAL SUBMITTAL • JOB#1406073 P POTTER BELLS e The Symbol of Protection PBA-AC & MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. 1 Fig.3 A.C.BELLS w""'cm) ■ WHITE.rom a lo^ 12\_ MO I FROM CONTROL ' (200) 6�� 1 I CEDING B PANEL t t'01 I (� I PRECEDING BELL 1 �� ��T BLACK(DO "gill MP' BLACK loon 1 CALTION: WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. 2 11/16" F._ t8) NOTES: owca n61 I.WHEN USING AC BELLS.TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2.END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS. Oven Nwl Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP Box has one threaded 1/2"conduit entrance 11_ iti ' I -� II I' O + To Next S(146) — 3(96 /27) Device or (IAA) End-of-Line Resistor 3 86)"......_ lu■.■=0,,,,_wi 15/8" 114 4l) 6114' (108) Installation DwGo n[-2 1. The bell shall be installed in accordance with NFPA 13, 72,or local AHJ.The top of the device shall be no less than 90"AFF and not less than 6"below the ceiling. I2. Remove the gong. a 3. Connect wiring(See Fig.3). 4. Mount bell mechanism to backbox(bell mechanism must be mounted with the striker pointing down). 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). .��`� 6. Test all bells for proper operation and observe that they can BEx-t ti be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). ! WARNINGS` . ;., Failure to install striker down will prevent bell from operating. 4 PRINTED IN USA MFG.#5400776-REV Y-1 PAGE 2 I)I 2 01/13 121 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 s 58 COJtp PCUPCS()K1 C FIRE SPRINKLER EQUIPMENT SUBMITTAL FOR FILE COPY Camp Parsons 970 Bee Mill Road , Brinnon, WA 98320 MAR 1 ')^15 L • COLUMBIA FIRE Job #1406073 11/ 1 3/' 13, S /. z 1 L 3/1 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TABLE OF CONTENTS Section 2.1 - Pipe and Fittings 1. Allied Schedule-10 black steel pipe 21/2"Grooved 2. Allied Schedule-40 black steel pipe 1/z"-2"Threaded 3. Ductile Iron Threaded Fittings 4. Grooved Fittings, Couplings & Mechanical Tees —Victaulic 5. 6x4 Cement linked, Flanged Reducing 900 Elbow 6. EZ Flex, Flex drop— Victaulic Section 2.2 - Fire Sprinklers 1. Extended Coverage, Dry Horz. Sidewall, K=11.2,SR,155°,16'x20'—Tyco Model TY5339 2. Globe GL5615, STD, BR, SSU , 1/2" 5.6K, 155° 3. Globe GL5615, STD, BR, SSU , 1/2" 5.6K, 200° 4. Globe GL5606 concealed SSP BR/White 1/2"5.6K, 155° 5. Globe GL5606 concealed SSP BR/White 1/2"5.6K, 200° 6. Globe Dry Pendant 7. Globe Dry Horizontal Sidewall Section 2.3 - Valves and Accessories 1. FDC 4"X 21/2"X 2'/2"— FPPI Straight Model# 09-000 • 2. W/P 4 IPS Auto Sprinkler Red ALU - FPPI 3. Backflow— Wilkins 350A BGVIC 4. 4"Grooved to Grooved Swing Check Valve 5. 4"Tyco #513 Riser Manifold Section 2.5—Automatic Drain Device 1. Automatic Drain (Ball Drip) valve Model# F789 Hangers and Sway Bracing 1. Hanger Ring —Tolco Fig. 200 2. Sammy Screws—Vertical, Horizontal & X-Press (Wood) 3. Earthquake Pipe Clamps —Tolco Fig. 4 & 4A 4. Earthquake Fast clamps —Tolco 1001 5. Tolo Fig. 980 Earthquake attachments 6. Tolco Fig. 906 Sway Brace Multi fastener adapter Supervisory Devices 1. 10" Electric Bell - Potter Electric PB Series • 2 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • SECTION 2. 1 • PIPE & FITTINGS • 3 Schedule 10 / Schedule 40 M-COAT Fully Listed and FM Approved Sprinkler Pipe When you specify Allied Schedule-10/Schedule-40-M-COAT sprinkler pipe you get a UL listed and FM approved product.Although these products do not require separate approvals,Schedule-10/Schedule-40-M-COAT gives you the extra quality assurance you demand.Our Sch-10(11/4"-8")pipe and Sch-40 (1"-21/2")pipe have passed the same thorough lab testing as our other listed pipe products,and receive periodic mill inspections from both UL and FM agents to ensure consistent quality. Sch-40 ASTM A135/A795 ® Galvanized Pipe M-COAT Specifications Schedule-10/Schedule-40-M-COAT product can NPS Nominal Nominal I.D. Nominal Wt. Wt.(H20 Filled) CRR In;mm 0.0.In;mm In;mm Wall In;mm Lbs/ft;kq/m Lbs/Ft;kq/m be"hot-dip"galvanized to meet FM requirements 1" 1.315 1.049 0.133 1.680 2.05 1 for dry systems in accordance with the zinc coating 25 33.4 26.6 3.38 2.5 3.05 specifications of ASTM A-123. t'ia" 1.660 380 0.140 2.270 2.93 32 42.1 35.1 3.56 3.39 4.36 - O Superior Coating 11/2" 1.900 1.610 0.145 2.720 3.61 1 40 48.3 40.9 3.68 4.0 5.37 - Our advanced formula mill coating offers a clean, 2" 2.375 2.067 0.154 3.656 5.13 1 durable surface.It is also paint-ready for custom 50 60.3 52.5 3.91 51 7.63 - 1 color applications without special preparation. 21/2" 2.875 2.469 0.203 5.80 7.86 The internal surface of all black Allied Tube& 65 73 62.7 5.16 8.6 t 1.73 - Conduit fire sprinkler pipe products up to 4,500" • in diameter are coated with M-COAT,an advanced Sch-10 ASTM A135/A795 MIC coating that is FM approved for use in M-COAT Specifications hybrid sprinkle systems. NPs Nominal Nominal I.D. Nominal Wt. Wt.(H20 Filled) CRR In;mm 0.D.In;mm In;mm Wall In;mm Lbs/Ft;kg/m Lhs/Ft;kg/m - 1'/<" 1.660 1.442 0.109 1.810 2.525 7.0955 American made 32 42.2 36.6 2.77 2.7 3.75 11/2" 1.900 1.682 0.109 2.09 3.04 5.6570 Able to meet"Buy American"requirement and 40 48.3 42.7 2,77 3.1 4.52 - is available through distributors in the USA, 2.. 2.375 2.157 0.109 2.640 4.22 4.5827 - Canada,Mexico and Latin America. 50 60.3 54.8 2.77 3.9 6.28 21/2" 2.875 2.635 0.120 3.530 5.89 3.5196 65 73 66.9 3.05 5.26 8.77 - 3" 3.500 3.260 0.120 4.34 7.94 2.5550 0 Specifications & Approvals 75 88.9 82.8 3.05 6.4 11,82 - Schedule-10/Schedule-40-M-COAT pipe are in 4" 4.500 4.260 0.120 5.62 1.78 1.6020 compliance with the following:ASTM A-135,Type 100 114,3 108.20 3.05 8.3 17.53 - E Grade A,and NEPA 13,All pipe products have a 5" 141.3 5.295 3.4 0 7,78 17.33 1.4874- p p p 125 141.3 134.5 3.40 11.58 25.80 rated working pressure of 300 psi maximum and 6" 6.625 6.351 0.134 9.3 23.03 1.0251 also meet the stringent requirements for the 150 168.3 161,5 3.40 13.8 34.27 - following applications and tests: 8" 8.625 8.249 0.188 16.96 40.15 1,8365 •Welded Outlets 200 219 _ 209.50 4,78 25.2 59.75 - • Hydrostatic Pressure L c 0 APPROVED ^' III+ Customer Service(800)882-5543 Fax: (800)659-7730 www,alliedtube-sprinkler.com •r le/ •16100 S Lathrop Ave. •11350 Norcom Rd. •2525 N 27th Ave. TUBE & CONDUIT° Harvey,IL 60426 Philadelphia 4 PA 19154 Phoenix,A7 85009 •PART OFAatkure 672013 Atkore International,Inc_All Rights Reserved.STP-S4-3-1301 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Specification & D . • 1 . :.ac: ANSI B r.- NPT /1-ter;el: Dc ;: e Iron ASTM A536 Pad a ','-ax l' orking Pressure: SrY.t, Si F : w.V.pa diCo COM N ,:ro dais: FM s :-, ULC ,,,,',-:ry.si`i: Standard Pipe Wrench irtstaitation Apply Teflon tape or 1:q^e.aai•I'• Teflon pipe joint ca'r:.puy:r 31 the: pipe threads end t.griteu three and one-halt ;a`tit.r:urns __.tin:: hand tight. Note -_::d-!.r o Ductile Iron l' -a;fec Fittings provide more strength il:PJ Coinosion resistor:: non cant iron fittings- Pa. _o dJ^2 z ' o rips are 1110+? .JJ,rLJi: iue to the extra precious e Weeln .I1�1- = ?Cit' ; during the rCnCes5 Of a s, a^: T trs provides an .;,,, -. .�, a �-•. over cant iron as the`.Ittlr*.a5 are not is sJsceptib'E:tO ,'RK Tr :i crack.ng. Paddice ductile it n tnrgs are lightei It�:fr:cast . .r' making them easier 1° ndrr r and install. 1,2...J i ATTENTION : ' :• Caution_ rstallers who have n::::t used it.;mtile iron fittings before should be c:auttore.d inat the ' j:-.;11.4-?.. have a higher tense strength than alit.. Therefore, c ' :i 1'g the fitting ~ may _ar-age the p tae thread and cause leaks. There should be rho : -.: to `ait a turn riiVeren^n , : between cast trrrr ,cod_-ds on the thread cat cs st f -. i._n `ittings`i and :?..ictila :roc fittings. Apply Teri•:;n :ace h * .. _r high duality pipe ;pint ce. ipound on the pipe threae and .ithten three and one-half turns beyond hany tight. No more than four turns! Caution for automatic make-on machine users: ` c rase soecial cant - n scatting the mach:ne 10 .. .'�' ; rper pararnete-6 _ .- to t!gntening fittings e male pipe threads. r' .- D s. ,•';gated By • 6 • CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 is am readed Fittings 3% Air-Tested In A Water Soluable OH Solution. Ductile Iron Hex Reducer Ductile iron Hex Bushing Model T-106 $ M Wrench Wt Box Mr.c.F1 T-110 Size A V‘et Box ! Size Los. Oty Lbs. , Qty 41, 15.1,. 17 0 *4841 1 X 4 159 1 x ', , 1 '' 4 i / 17D .:. 1 1 t 1 1 Ductile Iron Cross .A 2 x 1 75 ao Model T-107 Size A 8 WI Box , Uos, Ctv 21 I 89 at) -r 17; 1 1 ',', 1 1 " , 1 1.:1 11. 4 .54 zs Ductile Iron Extension Piece 2 , 2 .'., 2 /„ 294 10 WI 00x - a ,7-,, IVIociel T-111* Size L ._bs.. Ot Reducing y IIIII .1,t A .. ,,, K t •.":L 1 1 /.4.1 i I -... —7 11111 ' 7L 2 27 , 250 K. '1... "..." ''‘. =.". 148 24 lttV - — 2 ,. , 9.94 to __ L x.9L L 2 .21 202 Ductile Iron Straight Coupling Ductile iron Plug T - 'gVrench '10 t;ze Sizo Lts Qty i Wt. Box Model T-112" Size , Lbs Qty ■ , L___ _ , --_,-,,,,,,P•,„ , . f, .,,,„ 2,/,/ 89 ,,, '-'—i- ' • , „ 19 3.80 _ 28 230 1 ' ^ '' - 11 r -.." ....,. 1 ,I ;;,0 .1 5 37' 2-29 IMIN —— ' '1 Ductile Iron Cap 2 #i, CIVIC 109 Mod 1 T- Size A Weight Box Lb . °WM be available in earl'," 1998 .... _ .. 1 ,' 1 3 180 ,. , .... ..- C ..., 110 . . .... , ao illii t , ... _96 45 7 Speclications s.Mject ic change without notice. ,.-. Ocrober 1997 Packlico. Printed in the U.S.A. CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 k ,4 Paddico Ductile Iron 11 Paddico Ductile Iron Threaded Fittings Are Ductile Iron 90 Degree Elbow Ductile iron Reducing Tee Mo T 01 Weight Box 1 del -1 Stze A Wil ' .1:... L: Lin Oty Model T-105 — „ ,,,; „ ';',.4. i size 4 7 C %VI iLoi5 i Box Oty .3 i 26 97 1 1 s15 40 ,v' "'”' -.OM 1 _ H ., ; , 5", 8 ■ ,11... 2 2 , 1 74 30;0 , 1 1 1 , ■ 1 ' - 4 5-i ■ 1 55 65 7: q 1 Ductile Iron Reducing 90 Degree Elbow r...IX 1' ' Model I-102 Size A S WI B 1 a Lis. •:DT'y 1 . 1 I 1 x e l 1 ' 44 S I:: „ 1 1 ' i -t.:, ..J._,•? 4140/11*11 I x" 1 1 ' ,. 53 90 1 E- .5 - 1 , , 1 I 64 7:: t /j I , I 4-----__,- ' I , I - 1 ''' 4, 75 60 1 1' , • , 1 " ‘ 1 1 1.4 96 IE I r.,...1.1 1 0 .J. i 1 . t E 9 4E • 1 al i i , i4 2z 1 1 ii 1 _ i I' 1 52 1 ' i 1 1 ". 1 '", i ,, amors. 1 .._ I 2 -58 2i2 1 1 1 1 , - 1 21 2. 2 1 ; 1 - ' LI 7 2: 1 I•1 1 1° 1- 1 I 1 ¶.2 Ductile Iron 45 Degree Elbow 1 1 1 1 1 .3.' Z 1,,i1A i kiOdii217-103 Sae A Lts : Oty I I 2 2 2 2 1r2 1 1 48 35 9-0 1 .--, 3■11 1,, /4...... .._ ' I 2 I il 25 50 1 ',.. 2 1 ' ii, 2 , -2""'• 2, 2'" 1 /4, •, .1 cla 2 ' • rr.1 16 . .= 2 i 1 I 2 ■ , 2ii Ductile Iron Straight Tee ‘. 1 - , ., 0 WQ. Box T-'c14 . I Oty Ductile Iron Bullhead Tee Mill MIMI - t , I 1 - " ) EZ1 i 1111111111 ' ,.. .. .1 - •>5 ',, 1 , , 1 _ 1.42 _tilo .. -I-- 1 63 94 1 / imeli 3 2 '-- [ 4. ' illnk' 2 _ 263 12 , 2 I/4 2 4 g: , 2 1 ,..-.._ _ 1 'IV 2 2 2 .2'- iilici 2 2 2 2 6 2 567 1' IPS CARBON STEEL PIPE.. GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL 07.01 _ ._.. _..... ---. JOB#14©6073.........__ __.. ..... _.. Grooved End Fittings • " I r, NO.10 ELBOW NO.20 TEE MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12.Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. • Or:Segmentally welded steel as shown under nipples Nipples:(adapter,swaged&hose) • 3/3--4720-100mm Carbon steel,Schedule 40,conforming to ASTM A 53,Type F • 5-67125-150mm:Carbon steel,Schedule 40, conforming to AS FM A-53.Type E or S,Gr. B • 8-127200-300mm: Carbon steel, Schedule 30 or 40,conforming to ASTM A-53,Type E or S, Gr. B Flanged Adapter Nipples:(Nipple-see above) • Class 125 Flange:Cast iron conforming to ANSI B-16.1 • Class 150 Flange:Carbon steel conforming to ANSI B-16.5, raised or flat face • Class 300 Flange:Carbon steel conforming to ANSI B-16.5,raised or flat face • Fitting Coatings:Orange enamel • Optional:Hot dip galvanized and others.Some fittings supplied electroplated as standard-see product specifications. Flanged Adapter Nipple Coating:None(Unfinished) • Optional:Orange enamel, hot dip galvanized and others. • • www.victaulic.com 10 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY ALL RIGHTS RESERVED.PRINTED IN THE USA_ rCt�V�I� REV L D7.OI.3 • iPS CARBON STEt i O1f7VL D?ITT..- CAMP PARSONS MATERIAL SUBMITTAL 07.01 JOB#1406073 .-_... Grooved (i1 ' ''igs • °* d NO.10 ELBOW NO.20 TEE DIMENSIONS Elbows NO. 10 90°Elbow NO. 11 45°Elbow NO. 12 2211°Elbow NO. 13 111 Elbow \a-f p.--C co E- N0. 100 90°Long Radius E_to E N0. 110 45°Long Radius t°e i•■■ 1 #11 ctIN o (Ductile Iron I 1= ' K CtoE y r li <, , CtoE CE o F T ro 04- t .NO. 10 NO.11 NO.12 NO.13 NO.100 NO.110 No.10 l No.11 No.12 No.13 No.100T No 110t Size 90°Elbow 45°Elbow 22V Elbow(owl 114'Elbow low) 90 Long Radius Elbow 151 45`Long Radius Elbow(S) I 1 "'1 C to E Wg1 Each 1 C to E Wet 1 . lL l 2.25 Spa 0.5 1f50 „- 0.5 163 ew 1.385w k8� inmmes Los. . lnen Lkil r' 1 • 20 26.9 37 0.2 38 0._ 41 35 - - ....._. _. 1 1.315 25 0.6 175 0.6 3.25 c@ 0.6 1.38sw 0.3 25 33.7 57 03 44 0.3 83 0.3 35 0.1 - _._. - IW 1660 T15 1.0 1.75 09 1.75 0.8 1.38 sw 05 37 42.4 70 0.5 44 0.4 44 04 35 0.7 - - - - 1/ I 1.900 2.75 1.2 1.75 0.9 1.75 0.8 138 5w 0.5 - - - 40 483 70 0.5 44 0.4 44 0.4 35 0.2 - 2 2.375 3.15 1.8 2.00 1.3 37514 1.4 1.38 1.0 4.38 2.5 275 1.8- 50 60.3 83 0.8 51 06 95 06 35 0.5 111 I.1 70 0.8 .......21/2 2.875 1i5 3.2 2.25 2.2 40052 2.3 1.50 1.1 ... 5.00 4.1 100 2.8 65 73.0 95 1.5 57 1.0 102 1.0 38 as 12/ 19 76 1.3 76.1 mm 3.000 3.75 3.2 2.25 3.4 - _ - - 5 76.1 95 1 7 57 1. 3 < 1500 4.7`, 45 2.50 11 '50@ 31 150 71 588 6.0 638 49 80 88.9 108 2.0 64 1 4 114 (4 38 1.0 149 2.7 86 2.2 3h 4.000 4.2,0 5.6 2.75 4.3 250sw 4.0 1755w 2.7 90 101.6 0'4 25 70 2.0 64 I8 44 12 - - - 4 ' 4.500 3 00 7.1 3.00 5.6 2 88 5.6 1.75 3.6 7.50 12.3 4.00 7.3 100 1143 12 3.2 76 2.5 73 25 44 1.6 191 5.6 102 3.3 105 rJmm ,.. 4.256 5.00 110 3.00 5.6 L, - 1 08 0 07 50 76 ...........422 ''. 5.000 5.25=.r, 100 3.13 sw 6.0 350 66 - 188sw 42 - 120 127.0 133 4.5 79 2.7 89 3.0 48 1.9 _-- _-- 5 5.563 5.50 117 3.25 8.3 288 sw 7.8 2.00sw 50 18.2 14.8 5 125 141.3 140 5.3 83 3.8 73 3 51 2.2 + 8.3 67 733.0 nvn 5.250 550 11.7 3.25 8.3 1333.0 140 5.3 83 38 139 7 mm 5.500 550 11.7 3.25 8.3 _ _ _ 139./ 14'J 5.3 83 3.8 6 ''. 6625 F,'.9, 17.2 330 10.8 625@ 12.2 700 7.0 1025 324 5.50 174 150 1683 165 78 89 49 159 5.5 51 3.2 273 13.8 140 79 ...... 6.250 650 18.6 3.50 10.8 . 1590 mm 15'90 165 8.4 89 49 - - - - 1651 mm 6500 C.30 15.5 3.50 9.8 313 114 200 74 10.75 290 5.50 190 • 1651 165 7,0 89 4.4 79 5.2 '', 51 34 :i 273 13.2 140 8.6 www.victaulic.com 11 VICTALILIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2006 VICTALILIC COMPANY ALL RIGHTS RESERVED.PRINTED IN THE LISA. �Ct au�It,r 07.41 4 RV_L IPS CARSON STEEL PIPE-GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL 07.01 JOB#4406073.- Grooved Eno Fittings • Er E� 1 , NO.10 ELBOW NO.20 TEE •Argit,......- ''-C.rori Etof r-CtOLml ill i�� C C[()\ < Cto4 C I 1, CtoE to t z� NO.10 NO.11 NO.12 NO,13 NO.100 NO.110 No 10 No 11 No 12 I No 13 N 1001 No 11) 90 Elbow 15 Elbow 22 Elbow row 11 , E bow svo 90 I ong Red us Elbow ISl It I wl,R.A■ f11 3.g.IS Nofitnal 1 At twat I A43dr8x. Ap0*ou. _ .[ Avoca, • EnEr+ . 1 Site Outside DIa. C to E I Wgt.Each 1 C to£ Wgt Each C tot Wet.Each G to E. Wgt.Each E to E� " C to E WSI.tooh Inched Inches Inches Lbs. lobes Lbs. Inches Lbs motes Lbs. Inches t 344,, totem Lbs. mre me new kg [ nun kg mm kg rrua o kg rem ..... am kg 8 8.625 775 29.9 4.25 20.4 7.75@ 20.0 2.00 10.1 14,25 66.0 7.75 360 200 219.1 197 13.6 108 9.3 197 9,1 - 51 4.6 362 30.3 184 16.3 10 10.750 9.00 63.3 4.75 37.5 4.38sw 300 213sw 11.8 15.00 1370 6.25 570 250 273.0 229 287 121 17.0 Ill 13.6 54 5.3 381 48.5 159 25.9 12 12.750 10.00 74.0 5.25 - 66.7 4.88 sw 40.0 2.25 sw 29.3 18.00 15E.0 750 90.0 300 i 323.9 254 33.6 133 . 303 124 18.1 57 13.3 457 7.8 191 40.8 • 148 4000 1400 1360 5.75 650 500sw 460 3.50sw 32.0 21.00s 0,4 ri 8755 82.0 350 3556 3556 61.7 146 29.5 127 209 89 14,5 533 '44 722 37.2 3770 mm t 14.843 14.84 149.3 6.15 82 0 3770 376.9 67./ 156.2 37.2 164 16.000 16.00 171.0 6.63 88.0 5.00 sw 580 4.00 sw 42.0 24.005 2110 10005 100.0 400 406.4 406.4 776 168 39.9 177 26.3 102 19.1 610 95.3 254 45.4 426.0 mm t. 16.772 16.77 198.6 695 101.3 426.0 426.0 90.1 176.5 459 I 188 18.000 1800 2240 746 1080 5.50 sw _ 65.0 4.50 sw 53.2 U.00S 13.0 11.755 13°J . 450 4570 457.2 103.4 189 50.0 140 - 29.5 114 24.1 686 1238 286 61.2 480.0 mm t' 18.898 1890 291.0 783 141.7 • 480.0 4E0,0 132.0 198.8 64 3 - - 208 20.000 2000 2980 8.28 138.0 6.00 sw 78.6 5.001w 650 30.00s 3.'130 12.50s 1740 ,._ 500 508,0 508.0 135.2 210 626 152 36.0 127 295 762 155.6 318 789 530.0 mm t 20666 3550 8.64 179.0 530.0 530.0 2087 1610 219.4 81.2 248 ", 24.000 24.00 438.0 9.94 221.0 7.00 sw 1400 6.00 sw 60.0 36.005 316.0 15005 251.0 550 610.0 609.6 198.7 252 100.2 178 63.5 15? 272 914 234.1 381 113.9 6300mm t. 24.803 24.80 545.0 10.27 255.2 630.0 630.0 2472 261.0 115.7 - - - - - 14-24 ,®, 350-600 For AGS fitting information,see publication 20.05 @ Gooseneck design,end-to-end dimension *(sw)Segmentally welded steel #For use on cut grooved systems only,For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. t Chinese standard sizes • www.victaulic.com 12 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA tats 0-- REV L 07.01. 5 ' iPS CARBON STEEL P7 '.. GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL 07.01 J08401-06073 ro ,1- _hinge • NO.10 ELBOW NO.20 TEE Tees, Crosses and True Wyes ,Ct.E ..r_ CtoL ^ Cto N0. 20 Tee I`CtoE 7 GE 71 N0. 35 Cross �� II N0.33 True Wye + 11 01 NO.29M Tee with I 1 to It. c to E Threaded Branch --1 =� _ (Ductile Iron') NO.20 NO 35 No.33 NO.29M N, 20 No.35 No.33 Na 29M True Wye Isw) Tee with Threaded Branch Size Tee Cross(sw) : 5-. t Y;;;ra:xa wight E. 6;tea` ,.e C to LE C to SE Waiht Each C to GE 1 C to lE I Weight Eeeh irK%M5 Itches Ills. Inches • tnchPS tbs. >°t.`. mm row kg. mai ntm. kg. mat Mal . Ng mRi 2.25 2.25 0.6 22 0 21.050 225 0.6 2.25 09 _ - 57 57 D.3 6 9 57 03 57 0.4 -. _.. 1.31, 2 25 10 2.25..... 13 225 2.25 11 2.25 2.25 1;0.. 25 33.7 57 05 57 0.6 57 5/ 0.5 57. 57 0.5 ..._ 2.50 1.5 2.75 2.75 15 1•2 1.2.4 2 1) L7 2.75 1.0 2.75 64 0.7 70 70 0.7 32 , 42.4 70 U7 70 . _. 1'4 1.900 275 2.0 2.75 2.5 2.75 7.75 1.8 2.75 7p 00 -. • 40 483 .2 _ 1 1. 3.25 .7 2.5 70. 0 � 2.375 325 3.0 3.25 38 325 775 25 3.29 425 3.00 2 4 50 j 60.3 83 1.4 83 17 83 70 11 83 108 _-- 71 2.873 375 4.3 375 6.1 3.75 3.00 4.3 3.75 3.75 4.3 55 73.0 95 2.0 ..... 95 2.8 95 76 20 95 95 2.0.. 9.75 375 5.2(sw4 ... 3.000 375 2.4 - - - - 95 95 j4 10 I mm 76.1 ri lG 3 3500 .15 6.8 4.25 10.5 4.25 3.25 6.1 425 6.00 6.8 108 83 2.8 108 152 3.1-- -. 80 88 108 3.0 108 4.8 4.50 79(sw) -... 31/2 4.000 4 50(5w) 79 450 11 5 4 50 3.50 96 4.50 90 101.6 114 3.6 114_... 52_.. 114 89_.. 4.4 114 114 73.6 _ 5.00 5.00 15.5 108.0 127 1080mm 4250 127 15 7.0 5.... - - - - 127 ', 127 7.0 4 4.500 5.00 11.9 5.00 15.8 5.00 ', 3.75 100 5.00 7.25 119 72 127 95 s 4.5 127 184 5.4 41/2 100 ...i, 114.3 127 5.4 127 20 5.000 5.25(sw) 15.0 5 25 18.5 5 25 5 25 '5.0(5w1 120 1270 133 6.8 133 8 133 133 6 8 4 5.50 5.50 1/.8 5330 940 81 - __ _.. 140 140 81 1330mm ! 1330 14G 81 550 5.50 17.8 1397 mm i 1397 140 81 - - _. - 140 ! 140 8.1 5 1317 140 8.1 .._ 5.563 5.50 17.8 .5.50 20.0 5-50 400 150 550 5.50 17.8(5w) 125 . .413 140 81 140 9,1 140 102 6.8 140 140 8.1 _- 6.50 5.50 27.1 1590mm + 1590 �l50 12 -_ __ 165 165 123...... 1590 165 12.3 5.50 6.50 22.0 165 1 mm 6.500 G-50 22.0 6,50 165 10.0 165 28.0 - - - 165 165 10.0 165.1 12.7 6 6.65 050 25.7 6.50 28.0 6.50 4.50 22.3 6-50 6.50 25.7(1w) 150 158.3 '65 117 165 12.7 165. 114 10.1 165 165 7T5 6.00 36.0 775 775 47.6(1w) 8 ! 2191 175 476 --- 197 288 197 200 2191 197 11.6 197 218. 197: 152 16.3 19/ 197 21.6 10 10 750 9.00 99.0 900. .. 1215 9.00 ....6.50 69.9 9.00 9000 33.0 250 2730 229 449 129 55.1 229 155 31.7 229 1 12 12.750 1000 133.0 10,00 110.0 10.00 7.00 80,0 10.00 10.00 99.0 300 323.9 254 60.3 254 49.9 254 178 363 254 254 449 www.victaulic.com 73 CteUllie VICTAULIC IS A REGISTERED TRACEM.ARK Of VICTAULIC COMPANY-'9 22006 VICTAULIC COMPANY,ALL RIGHTS RESERVED.PRINTED IN THE USA. REV L 67.01 6 IPS CARBON STEEL PIPE -GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL 07.01 JOB#140603.... Grooved End Fittings • 1 N0. 10 FL ROW NO.20 TEE _.__._.................._......._... Tees, Crosses and True Wyes "ctoz., No. 20 N0. 35 Teens P C to F 1 rm� o L C t0 GE -I N0.33 True Wye I N0.29M Tee with �= c II Threaded Branch to II T cro (Ductile Iron `) �� � E ct°r NO.20 NO 35 �- ND.33 NO.29M No .eU Na 35 No.33 . Size Tee Cross(Owl : Trim W No.29M 350 �c. 14.000 rni mow,mod; `"' aie.'a&mT k .. ' w�, ,6 r mm mm mm - kg mm 14 8 1100 145.0 1100 198.0 r i.OU iSU 134 2 279 65,8 779 89.8 279 191 608 - - 377Umm 14000 11.00 1450 --- --- -- __ . 355.ti 279 65,8 16 5....._.. 16.000 1700 186.0 12.00 250.0 11.00 400 406.4 305 84.4 305 1134 305 203 167,0 --- - 203 75.7 - _- 4160mmt 4064 1200 186.0 • 406.4 305 84.4 - 185 18.000 1400 256.0 1550 350.0 15.50 8.50 _._ 450 4570 356 116.1 394 158.8 394 7.06.1 _.... 216 106.1 4800mmt 18 000 14,00 256.0 _. 45:0 356 116.1 - _- -- 20#.____. 20.000 15.00 339.0 1725 452.0 1725 900 500 381 153.8 438 205.0 438 12.5 229 127.5 - -- - 530.0mm I 20.000 15.00 3390 508,0 381 153.8 24# 24.000 1700 473.0 20.00 795.0 20.00 1000 523.0 550 6100 432 214.5 508 36G.6 508 254 2377 • 6300mm f 24.000 17.00 473.0 614.0 432 214.5 - 14-24 zp• For AGS fitting in brmation,see 20.05 350-600 *(sw)Segmentally welded steel S For use on cut grooved systems only.For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. t Chinese standard sizes IMPORTANT NOTE: Fittings size 26-487650-1050mm are available roll grooved for installation with Style 770 large diameter pipe couplings,Contact Victaulic for details. .._._.....................................___.. • ._.__...................................__._ .._..........................___. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE LISA. REV 1 IPS CARBON STEE 3 ..`. GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL 07 01 J0B41406073 . Fittings • NO.10 ELBOW NO.20 TEE Cap NO.60 (Ductile Iron) NO.60 No oo No.60 S¢e cap Sicc Cnp tkmtt• pp T Away,. .Nominal Actom T Appray. S1Yq ■ eter rfticNnacs Welght Each. See Outside.Diameter I Thickness weight Each hx`he " Lbs Inches Inche: inches lbs. mm:_ 1t8 mm mm_ rem kg ..... j si, 1.050 88 0.2 0 6.500 1.00 73 20 !i'..9 22 O1 1651 mm 165.1 25 3.3 _... 1I 315 0.88 0.3 __. 6 6625...... 1.00 6.1 25 33.; 22 01 _.. .__ 150 '., 168.3._ 25 2.8 ' 4... '66C 0.88 _...0.3 8 L 8.625 1.19 131 32 I 424 22 01 200 219.1... 30 5.9 • I a..__ 1.800 0.88 0.5 __. 10 10.750 1.25 21.0• 40 i 48.3 22 0.2 ......., 250 273.0 32 9.5 .. . ....._. _1%5 0.88 0.6 12 ' 12.'750 1.25 35.6 50 err 22 .... 0.3 ........ 300 323.9 32 16.2. • 2 ..... 675 088.. ._ 1.0 1 8 14000 9.50 ,. 4 65 0 22 0.5 350 355.6 241 0 088 1.2 16 8 16.000 10 00 , 76.1 mm ,u.I 22 05 400 406.4 254 3 3`00 ! 0.88 1.2 .... 18 8 i 18.000 11.00 , 80 8;0 22 0.5 450 4570. 279 3 la 000 0.88. 2.5 _... 10` 20.000 12.00 !. , 90 01.0 22 11 __. 500 508.0 305 108.Omm 4.250 1.00 2.3 240 24.000 « 108:0 25 1.0 600 610.0 4 ^`00 1.00 2.5 14-24 For ABS fitting information,see publication 20.05 100 114.3 25 1.1 350-600 ■ 416 5000 1.00 2.5 IMPORTANT NOTES: 120 17.0 25 1.1 o 1.00 q,5 'Steel dish caps available through 247600mm,contact Victaulic. 133.0 mm 113 0 25 2.0 No.60 cap is not suitable for use in vacuum service with Style 72 or 750 couplings. 5 500 1.00 45 No.61 bull plugs should be used,see pg.35. 139.7 mm 7397 25 2 0 8 For use on cut grooved systems only.For roll grooved systems,Victaulic 5.563 100 4.6 offers the Advanced Groove System(AGS).For pricing and availability of cut 125 141.3 25 2.1 groove fittings in this size,contact your nearest Victaulic sales office. li90mm ,., 6.250 1.00 6.8 159.0 25 3.1 www.victaulic.com 15 CtBUlliC: VICTAULIC IS A REGISTERED TRADEMARK OF V!CTAIILIC COMPANY,0 2006VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ^-- REV L 0701 19 iPS CARBON STEEL PIPE GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL 07.01 _ _.......... __. _......JOB-#1406073-- _._ .._. _... Grooved End Fittings • k�H N0.10 ELBOW NO.20 TEE Concentric/Eccentric Reducer NO. 50 Concentric E NO. 51 Eccentric l'to�E l (Ductile Iron t) 011 � E to=- � [E- Ell NO.50 NO.51 No 50 No.51 No So Na 51 Size Concentric Reducer Eccentric Reducer T Size Concent ric centrc R educer Eccentric entrc Red 111411: ,. � I. -1111L. ( i n � I 1 n 1 r= iI2 102 t rt 'E (, F1 a G HJ 37 x 20 * 1.9 - 3'/'- X 3 250(sw) 2.0 950 7.0 90 80 ' 64 0.9 241 3.2 25 1 + j9 _ 4 1 j 300'(sw) 3.0 13.00 6.5 0.9 x 100 25 76 - 14 330 2.9 1/z ' 40 X 20 + 06 - _- 12. ' 2.6 20 32 2.1 1 -1 2.50`(sw) 0.8 5.50 45 I h 1000 6.9 10.10 8.1 • 25 64 0.4 216 20 40 ' 254 3.1 254 3.7 1'A 2.50'(sw) 1.0 2 3.00'(ow) 2,4 4.00(swi 3.3 32 64 0 5 50 1 /6 1.1 102 IS 11 250*s 9.00 2.0 w) 09 x 1' :... 3 00`(sw) 27 4.00 1 5 50 20 64 03 229 09... 65 5 76 1.2 102 L5 1 2.50*(sw) 0.7 9.00 2.3 3 , 300'(sw) 3.2 4.00(sw) 3.5 25 I 64 0.3 229 1.0 80 1 76 1.4 102 1.6 11/2 2 50*(sw) 1.2 9.00 4.6 31/2 : 3.00(sw) 2.9 10.00 8.0 32 64 05 229 2.1 90 76 1.3 254 3o 117, 25(1'(sw) 1.0 900 4.6 5 2 - 11.00 9.0 11.00 5.2 40 64 0.5 229... 2.1 125 X 50 279 4.1 279 2.4 65 x 20 + 0.6 + 1.5 2'/2 `; 1170 11.0 1100 10.8 65 1 279 5.0 279 49 _7_4 1 9.50 3.6 9.50 3.5 3 ' 4.00(sw) 55 11.00 11.1 29 64 1.5 241 1.6 80 i 102 2.5 779 5D 1'/4 2.50•(sw) 3 3 950 + t 3 50(sw) 4.3 5I J0(sw) 12.0 32 64 15 241 100 . 89 1.9 127 5.4 1'h 2 70*(sw) 36 950 3.7 5 1 ' 400*(sw) 5.0 11.50 14.5 40 64. 16 241 1 7 150 X 25 102 2.3 297 6 6 2 . 250(sw) 3.9 9.50 4.3 1:4 9,5 50 64 18 241 2.0 40 1 + 2.5 + + 3 '1/4 15 + 4.5 2 .....4.00'(sw) 66 11.50 14.5 80 X 20 + 07 20 50 i 102 10 z92 6.6 1 2.50'(sw) 13 9.50 4.8 2A • 4.00"(ow) 54 11.50 14.2 25 64 06 241 22 65 i 102 2.9 292 6.4 'G 1 _.. 30 4.8 3 400"(sw) 6.4 '.50(sw) 15.0 32 1.4 + 2.2 80 I 102 29 140 6.8 11/2 1.30•(sw) 51 9.50 5.1 t 400(sw) 6.5 550(sw) 17,0 40 64 2.3 241 2.3 100 102 2.9 140 ?.7 2 2.50*(sw) 1.6 3.50(sw) 6.0 5 4006w) 6,4 550(sw( 17.0 50 64 0.7 89 2.7 125 102 2.9 140 '7/ __ ............ 147 2.50*(sw) 1.8 3.50(sw) ,0 8 21/2 16 n0"(sw) 79 12.00 26.1 X 65 64 0.8 89 3.2 200 65 406 3 6 305 11.8 70.1 2.50(sw) 2.1 _ _ 3 5.00(sw) 9.3 12!r00 22.0 64 10 80 117 4.2 305 10.0 • www.victaulic.com 16 VICTAIJIJC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.02006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. �C1LalJ�1IC" REV,,,,L 07.01. 23 _ IPS CARBON STEEL PIPE GROOVED FITTINGS CAMP PARSONS MATERIAL SUBMITTAL 1 07" .01 JOB#1406073 Grooved End Fittings • . .. ... . . . .. : .., ., .: NO.10 ELBOW NO.20 TEE Concentric/Eccentric Reducer NO.50 Concentric r NO. 51 Eccentric "t -1 r-t to e (Ductile Iron t) DI -xi nd NO.50 NO.51 No.50 No.51 Na.50 No.51 5.r Concentric Reducer Frcentr r Reducer Size Concentric Reducer Eccentric Reducer Nominal 11) Approa Approx. 1 WA 11161 1 Sue E;D#„,"'41 Weight Each E toE Weight Each Inahes 1 Inehee r k6S. Inches Lbs 8 4 5.00:skit 10 4 ! 12.00 23.0 8 18 x 12 : 15.00 91.0 15.00 91.0 200 x 100 '''. 127 4.8 305 10.4 450 300 381 41.3 381 41.3 5...."" 5 00 38") 11.6 12.00 23.0 14 15.00 91.0 15.00 910 125 . 127 5.2 305 10.4 350 . 381 41.3 381 41 3 6 500 3kit 119 6.00(5w) 24.0 16 15.00 91.0 15.00 91.0 150 t2' 54 152 10.9 400 1 381 41.3 381 41.3 • 10 4.. 6(0"rs^:1 197 1300 32.0 14.5 #20 10 2000 1100 2000 1770 250 x 100 I 8.9 330 500 x 250 : 508 49.9 508 80.3 5 34.3 34.6 12 2000 120.0 20.00 1700 125 �" 156 * 15.7 300 508 .544 508 544 6 6D 373 20.0 13.00 569 14 2000 1490 2000 149.0 150 I 152 9.1 330 1E E7 350 508 679 506 679 it ' 600!s.+ 22.0 7.00(sw) 21.6 16 20.0o 120.0 20.00 120.0 200 152 10.0 178 9.8 400 508 54.4 508 54.4 12 4..: 440 14,00 48.0 18 7000 136.0 20.00 136.0 300 x 100 ` 20.0 356 21.8 450 508 611 508..... 61.7 €.... _r1' (SA' 24.6 14.00 50.0 #24 10 20.00 142.0 20.00 142.0 150 178 11.2 356 22.7 600 x 250 508 64.4 508.... 644 8_._. 700 B'.+) 52.0 400..... 53.5 12 ' 20.00 150.0 20.00 150.0 200 178 23.6 356 24.3 300 1 508 68.0 508 630 10 700(34') 39.0 ! 14.00 5/.0 14--1 20.00 162.0 20.00 162.0 250 178 17.7 356 25.9 350 i 508 735 508 73.5...... .3„, I #14 6 13:00 65.0 13.00 60.0 lfi 2000 162D 2000 162.0 350 x 330 27.2 150 400 508 /5.5 508 73.5 330 295 8..,.. .. ..13.00 650 13.00 . 60.0 IB ,� 20.00 162.0 20.00 162 0 200 330 29.5 330 27.2 450 508 73.5 508 735 10 13.00 66.0 13.00 65.0 20 , 20.8 68.5 2508 1900 250 ! 330 29.9 330 295 500 508 68.5 508 86.2 12 13.00 68.0 13 00 66 0 50- For ABS fitting information,see publication 20.05 300 ; 330 30.8 330 29.9 350-6 600 0 it »#16 8 14.00 73.0 14.00 73 0 -I- Contact Victaulic for details. 400 x 200 356 331 355 33.1 t0§ 1000 73.0 14.00 73.0 * Available with male threaded small end No.52. 250 356 33.1 355 331 # Ductile Iron except those marked(sw)which are segmentally welded steel. 12 . 1400 13.0 14.00 73 0 IMPORTANT NOTE: 300 356 33.1 355 33.1 14 t4OO 73.0 1400 73.0 Steel eccentric reducers available through 307750mm,contact Victaulic for 350 :. 356 33.1 355 33.1 dimensions. If 18 10 1500 91.0 1500 91.0 #for use on cut grooved systems only.For roll grooved systems,Victaulic 450 x 250 381 41.3 381 41.3 offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. • §cast fitting available for J.I.S.size.Contact Victaulic for details. www.victaulic.com 17 VICTALILIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY A 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE LISA. tlfrtaiu��� 07.01 24 REV L Grooved End Fittirtgs • WOW. ti NO.10 ELBOW NO.20 TEE WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. • _................ US&WORLD HEADQUARTERS CANADA CENTRAL AND SOUTH AMERICA P.O. Box 31 905-884-7444 1-610-559-3300 Easton,PA 18044-0031 USA 905-884-9774(fax) 1-610-559-3608(fax) 4901 Kesslersville Road viccanada @victaulic.com vical @victaulic.com Easton, PA 18040 USA EUROPE ASIA PACIFIC 1-800-PICK-VIC(1-800-742-5842) 32-9-381-15-00 86-21-54253300 1-610-559-3300 32-9-380-44-38(fax) 86-21-54253671 (fax) 1-610-250-8817(fax) viceuro®victaulic.be vicap®victaulic.corn p i c kv i c Q v i cta u I i c.c o m UNITED KINGDOM wpm..F FAST www.victaulic.com _ 44(0)1438741100 971-4-883-88-70 III 1111111111111111111111111111111111111 44(0) 1438313883(fax) 971-4-883-88-60(fax) WCAS-6M8PF7 • viceuro4victaulic.be UPDATED 9/2006 07.01 1449 REV L 18 jet8Ulia VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY ALL R'CHTS RESERVED.PRINTED IN THE USA. 07,01 JO11#1406073 rIII O FM ® (MI VOS iFI' n L l , oles on noeeG • SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS • STYLE 005 WITH VIC-PLUS"4 GASKET SYSTEM(NORTH AMERICA ONLY) FireLock°Style 005 rigid coupling has a unique, patented angle-pad design which allows the housings to offset while clamping the grooves.By permitting the housings to slide on the angled bolt pads, rigidity is obtained. Support and hanging requirements correspond to NFPA 13 Sprinkler Systems.Angle-pad design permits assembly by removing one nut/bolt and swinging the housing over the gasket.This PATENTED reduces components to handle during assembly. Style 005 FireLock couplin g are designed and recommended for use ONLY on fire VIC $ne an Gasket system protection systems. Vic-Plus"' Gasket System: .` In North America,Victaulic�'offers a gasket system which requires no field lubrication on wet '' i pipe systems that are hydrostatically tested.The Vic-PlusTM System(patented)is dry,clean,and non-toxic. It reduces assembly time substantially and eliminates the mess and chance of over- � 7 lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook(I-100)for I supplemental lubrication requirements and dry pipe fire protection system notes. 11111 Exaggerated far clarity LISTING/APPROVALS The information provided below is based on the latest listing and approval data at the time of • publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Re:.1 Wo k ng Rrrw,ru psi Routed'uVor6 t Pr .,.n. Ir. R lo,i'Nnr ku�;Y c=vrr ps 1 � I Pipe Size Pipe Size Pipe Size Sch. h,CAes UL Ut.0 FM Sch. teolrea to ULC,i FM Sett Wthes Elk QLG FM 5 115-3 175 175 175 El I Y<-7 300 N/A N/A M- 14 300 N/A N/A 1.7-4 350 350 350 ET 115-2 300 N/A N/A STf I< = N/A N/A 300 10,40 5-8 300 300 300 EZ 4-y 3001 N/A 300 Ste d ady 1 yi-2 WA NIA 300 3 i b5-2 300 300 N/A F F 118-4. N/A N/A 300 T F 3 d N/A N/r+ 300 3f t o-4 300 300 300 GAL 7.1!/<-2 300 N/A N/A WLS 1:4-2 300 300 N/A 1'/-2 300 300 N/A MT I'/a-2 300 N/A N/A XL I/x-3 300 300 300 FF 1Y-4 175P N/A 175 MF 1 4 4 700 N/A 300' "FM approved for service in 1'/x-4"pipe- s UL Listed for service up to 4"pipe only. C:IL Listed for service up to 3"only. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para • Location Date Approved Date www.victaulic.com 19 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY,ALL RIGHTS RESERVED.PRINTED IN THE USA. r81LJ�IC REV I 10.02 1 IPS CARBON STEEL PIPE- FIRE PROTECTION PR8ROTISARSONS MATERIAL SUBMITTAL 1®.02 ...JOB-#1466879- --.. ,1:i-et ock'D Rigid CoupPriPi STYLE 005 • WITH 1/1C-PLUSTm GASKET SYSTEM(NORTH AMERICA ONLY) DIMENSIONS Max.Work Max.End Allow.Pipe 6olt7Nute Approx. Size Pressure 4`'. Load` End Sep.I No-Size Dimensions-Inches/mm W;t.Ears a-Z ` i.Al�lll rl .I1JILL Sine OM8Wfee P83 Lbe, 1w leS t Encper T;. 083 I I i( wee 1 1 6b0 2 103 3370 i Ome r19t ,7 h x 1 x&, �� .OS 2-°/xx2A 20� a (. 188 15 -r Inchaetmtn Inchesrmm kPa N n 1.2 70 1- 148 OS Ph 1900 350 990 005 3.00 c.,5 1.88 1.2 2-Yn52', 40 46.3 2413 4415 1.2 76 121 148 0.5 Rated for wet and dry sprinkler systems at 2 2 375 350 1550 0.07 7-'.k x 1r/}i... 3.50 5 25 1.88 1.6 350 psi/2413 kPa for I!a-4"/32-100 mm 50 60 3 2413 6900 1.7 89 I/1 148 a7 sizes and 300 psi/2068kPa for 454-8'7108 21/2 2.875 350 2270 0.07 3... r 4.00 375 1.88 1.9 200mrn sizes;Schedule 10 roll grooved or 65 730 2413 10110 17 2-h x 2 h 102 146 148 .09 Schedule 40 cut or roll grooved steel pipe - Style 005 is rigid and does not accommodate 761 mm 3.000 350 2775 0.07 �, r 4.13 /5 1.88 19 expansion,contraction or angular deflection. 76.1 2413 11010 L7 2- a x 2 1z 105 40 148 0.9 3 3.500 350 3365 0.07 7-55 z 2 r 4 4.63 6.13 188 2.1 80 88.9 2413 14985 1,7 118 156 148 10 4 4.500 '. 350 5565 _...0.16 5.75 /25 2.13 3.1 100 1143 2413 24770 4.1 2-',8 x 2 h 146 164 54 1.4 1080mm 4250 300 4255 0.16 p a 5.63 7.25 2.13 3.1 xx 216 1080 2068 18940 4.1 143 184 54 14 5 5.563 300 7290 0.16 6.38 500 113 4.5 125 1413 7068 32445 4.1 2 19 -' x3 175 229 54 20 1330nun 5250 300 6495 016 2-64x2'3 6.63 900 2.13 4.5 133.0 2068. 28900 4.1 168 220 54 20 5500 : 300 7125 0.16 2--�hx 2Ya 139.7mm 688 9.061 213 4.8 139.7 2068 31715 4.1 175 229 54 2.2 6 6.625 300 10340 0.16 8.00 10.00 2.13 5.0 150 168.3 2068 46020 41 2-'/r x 3 203 754 53 2.3 1590mm 6.250 300 9200 0,15 763 10.00 2.13 55 15 • x1 0 2068 40955 4.1 194 254 54 2.5 2--'/''x 2a/. 6.500 300 ' 9955 0,16 2-./z x 3 4.1 5 5 1651 mm , 8115 10,00 2.13 1651 2068 44295 20/ 254 54 2.5 8 8.625 300 U525 0.19 Z-Yex4Ya' 10.50 13.14 2.63 11.3 200 219.1 2068 78000 4.8 767 334 67 5.1 ' Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI) steel pipe,standard roll or cut grooved in accordance with Victaulic specification;,Contact Victaulic for per for mance on other pipe, WARNING:FOR ONETIME FIELD TESTON'_Y,the Maximum Joint Working Pressure may've increased to 11/2 times the figures shown. t The allowable pipe separation dimension shown is for system layout purposes only Style 005 couplings are con' sidered rigid connections and will not accommodate expansion or contractor of me piping system. @ Number of bolts required equals number of housing segments.Metric thread sire bolts are available(color coded gold)for all coupling sizes upon request Contact Victaulic for details. § Style 005 couplings are VdS and_PC Approved to 12 Bar/175 psi. • www.victaulic.com 20 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE LISA. �♦'.tnaLA�1[i 10.02 2 REV I • STEEL -- FIRE PROTECTION I CFXf i'ARSONS MATERIAL SUBMITTAL 10.02 JOB#1406073 STYLE 005 WITH VIC-PLUS'"GASKET SYSTEM (NORTH AMERICA ONLY) MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Housing Coating: Orange enamel(North America);red enamel(Europe) • Optional: Hot dipped galvanized Gasket: • Grade`E" EPDM-Type A Vic-Plus-Gasket System A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Vic-Plus"Gasket System,requiring no field lubrication for most installation conditions. • Grade"L"Silicone Recommended for dry heat,air without hydrocarbons to+350°F and certain chemical services. For dry services,Victaulic continues to recommend the use of Grade"E"Type A FlushSeale Gasket. Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-I83. A Standard gasket and FlushSeal gasket approved for dry pipe systems to-40`F/-40°C.Based on "typical"pipe surface conditions,supplemental lubricant is recommended for services installed below O"F/-18°C and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water.Supplemental lubrication may also be required on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams.Victaulic continues to • recommend the use of FlushSeal gaskets for dry services. • www.victaulic.com 21 \CtaL1IIIC° VICTAULIC i5 A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA -- ---- REV 1 IPS CARBON STEEL PIPE FIRE PROTECTION ci: �f b .. Rip.,id Coupling STYLE 005 WITH VIC-PLUST"'GASKET SYSTEM (NORTH AMERICA ONLY) GENERAL NOTES WARNING: Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. IIIIIIIIIIIIIIININIuIiIImiIIIIII • WCAS-697KR4 For complete contact information,visit www.victaulic.com 10.02 1538 REV I UPDATED 9/2006 22 ICt9Uitic VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA . •••• --•-----•-•_• 10.02 M I vds) LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 77 Style 77 couplings are designed with cross-ribbed construction to provide a strong r component for pressure piping systems.Sizes 3/4-12720-300mm are two-piece a "� housings.For 14-24 7350--600mm sizes,Victaulic offers the Advanced Groove System(AGS)line of products. Request publication 20.03 for information on the flexible Style W77 AGS coupling. All sizes are provided with plated bolts and nuts.Galvanized and stainless steel housings are also available. Independent testing has shown the Style 77 coupling to be an effective stress relief and vibration attenuation device providing performance superior to braided steel and elastomeric arch-type connectors when used in close proximity to the source of vibration. Z. .®. Refer to ent testing sti vibration information. Vic �_ Independent testing has shown that Victaulic Style 77 flexible couplings provide exceptional functionality during and after earthquake conditions. Refer to 26.12 for further information. 111 I11 Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. • Housing Coating:Orange enamel. • Optional: Hot dipped galvanized and others. Coupling Gasket: (specify choice°)t • Grade"E"EPDM(All other sizes) EPDM(Green color code).Temperature range--30°F to+230°F/-34°C to+110°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service.NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrite Nit rile(Orange color code).Temperature range-20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range.Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. Services listed are General Service Recommendations only.It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. • Optional:Type 316 stainless steel,Grade 8-8M,Class 2. f Supplemental lubricant is recommended for services installed at or continuously operating below 0°F/--18°C. JOB/OWNER CONTRACTOR ENGINEER • System No. _ Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAUUC IS A REGISTERED TRADEMARK OF VICTAUUC COMPANY©2007 VICrAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. -CtaUIi� REV I 06.04 1 23 CAMP PARSONS MA I ERIAL SUbMI I I AL JOB#1406073 06.04 CARBON STEEL.PIPE--GROOVED COUPLINGS Standard Flexible Coup lin 4, STYLE 77 • . .., DIMENSIONS r4 u.bvc 1. 41:rv,_I p 1 Bolt/Nut@ Approx. Deflect.Fr.CO No Size Dimensions-dnchathnm Wgt Each Actual 1 1 "'""` Nottdnal Outside ' Size Diameter Per Pipe Inches Inches psi Ohs. Inches 6piq. In 081 lnehes g nun mm Ws N I trim On moan mm X T Z kg 44 1050 1,000 865 0 0 2.13 072 2.13 4.00 175 1.1 . 3'-24 2-3/8x1 20 26.7 6900 3850 0-16 60 54 102 44 05 1 1315 1,000 1,360 0-006 057 2.38 4.12 175 1.2 o -43' 2-3/ 8 x 2 61 105 44 0.5 25 33.4 6900 6050 0-16 48 1'b 1.660 1,000 2,160 0-0.06 7•-10 ....045 _..2-8' 2. 265 500 .88.... 20.... 32 42.2 6900 9610 0-1.6 3d 67 127 48 as 11/2 I 1.900 1,000 2,835 0-0.06 6 0.40 2-'n z 2;^. 3'3 5.38 1.88 2.1 46 48.3 6900 12615 C-1 0 33 79 137 --8 1 0 2 2.375 1,000 4,430 0-0.06 032 ;88 188 6 1°-91' 2-V1i x2!h 3.63 2 50 60.3 6900 19715 0-1.6 26 92 149 49 1 1 570mm 2.664 1000 3955 0-0.16 0.33 3:13 5.73 1.9 3.0 57.0 6900 17592 0-1.6 1°-34' Z7 2-hx2, 87 146 48 14 21/2 i 2875 1,000 6,490 0-0.06 0.26 426 650 1.88 31 65 73.0 6900 28880 0-1,6 I - ' 27 2-�/z z2'µ 105 165 48 1t 3.000 7,070 0-0.06 0.26 .438 6r,' /61mm 1'-12 2-%2x20 188 3,2 761 6900 31460 0 22 111 168 48 1 3 3.500 1,000 9,620 0-0.06 a 022 1 500 '1? 80 88.9 6900 46810 0-16 1 18 ....2-6x24 127 181 48 I7 31/2 I 4.000 1,000 12,565 0-0.06 0°-S4, 0.19 2-5/8x3 I 563 3.25 1.88 35 90 1016 6900 55915 0-1.6 16 143 2'U 415 2.5 4 4.500 1,000 15,900 0-0.13 1° 36' 0.34 .. g_5/8 x 3'7i 613 ".58 7.1.3 6.7 100 r 114.3 6900 /0755 0-3.2 28 156 26 34 3.0 108 Cr^n' 4.250 1,000 14,180 0-0.13 0.35 6.00 13.63 .'1.12 110 1°-4.' 2-16582.` 152 108.0 6900 63100 0-3.2 29 ' 219 _,1 5.0 5 5563 1,000 24,300 0-0.13 7' 1B 0.27 7.75 105 _13 10.6 - 2-1'4x41' 125 141.3 6900 108135 0-3.2 23 197 2 14 .q 8 • 13�Omm 5230 1,000 21,635 0-0.13 0.28 763 1033 '_13 19.0 __.-. 133.0 6')00... 96275 0-3.2 -21' 24 2-202108 194 264 54 4.5 5.500 1,000 23,745 0-0.13 0.28 139.7 rnr- I 18 2-20x108 : 210 10.63 Z13 10.0 139.7 6900 105665 0-12 24 219 3-n 54 45 6 � 6.625 1,000 34,470 0-0.13 1° 073 2-yrx4A 8.63 158 '. 3 12,0 -5 150 168.3 6900 153390 0-3.2 18 219 30 54 5 4 1590mn 6.250 1,000 30,665 0-0.13 0.24 863 1150 113 13.2 "-9' ' 2-20x108 1590 6900 136460 0-3.2 20 ° 219 292 54 6.0 165.I mm 6500 1000 33,185 0-0.13 i" 6, 07 1-!4x44 8.58 110.3 2.13 13.7 165.1 6900 147660 0-3.2 19 726 6.0 Table continued on page 3. See notes on page 3. -mil h i rr .. � _' . - l4-22'SIZES 24"SIZES www.victaulic.com • VICIAULC IS A REGIS It RED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY ALL RIGHTS RESERVED.PRINTED IN THE USA. �./"r'tau�l�i 06.04...2 24 REV_( CAMP PARSONS MATERIAL SUBMITTAL A ;u JOB#1406073 o6.Q�F CARBON STEEL f'F .. :-3OVED CUUPLINCS • _5.555................................. 5555._._ -._ .-.. ................. -5.555 _ . 17-_- 1�Bible Coupling STYLE 77 ........................-... _._..-........................-._.. ._._.................._......-5555. ..._._......_..............-5.555 DIMENSIONS BoItINut® Appre'. �}�x.Work kftmv.Pipe Dimensions-brrJu lrom: Wgt.,Each dam.- t+ +.,5.,. ; e-fur,.L.�.i.F }• € -- . baMCnai _ ,.5.. " a g Psi i 310, tndre CP1g. la,-^' z 1 x Y Z k8 18' N mm .-; .G 1-.°�" 11H 11.00 1a.LS 2.50 208 20 8 0 1! I BW 207995 0-3.2 U=_,0� t4 /8x5 279 315 63 94 200 2140 5500 207995 0-3.2 13.63 17.13 2.63 31.7 10' 1015C 800 73,280 0-0.13 0'-40' 0 14 250 273.0' 5500 326100 0-3.2 5555 5555. .'' 2-1x6 346 435 67 14.1. 15.63 1925 2.63 278 23.... 12750 800 102,000 0-013 0,_, U 2 2-1x65, 39z 489 6i 12.6... .. 300 2 c 5500 353909 0 _.. . -. 0.11 4 l z3'h 1663 1988 288 355 14# Ia NO 300 46,180 0-U.13 0°-31' 9 422 505 73 16.1 350 355,6 2065 205500 0-3.2 - --- 011 4-1 x3Y. 1739 2096 2.8 48.8 14.8"2 300 51,575 0 0.13 0°-3i 9 442 531 71 22.1 377u nrmp 32/0 2065 230,845 0-32 5555. 2 53,000 0-0.13 17.88 21.63 3.00 488 15 3 15 1i(i0 300 0^ 29 0.10 4-1 x 5!5 454 549 76 221 375 3811; 2065 235850 0-3.2 1900 22.13 3.00 51.1 164 16000 300 60,320 0-0.13 0.10 4-1x3'6 23? 0° 2i' 9 482 562 76 LOG nC6.' 2Ub5 268425 0-32 5555 _.. 1,172 300 66,245 0-0.13 010 4 Iz334 1969 22.92 292 567 426Cr"e.p 0°-27 9 500 581 74 25.7.. 426 2065 294/95 0 3.2 _-. 5555.. 08 4-1x3'6 21 38 2450 3.13 64.4 18# i ,}(. 300 76,340 0-0.13 0°-24' 0. 543 622 80 29.2 450 453 2065 339710 0-3.2 ' 5 5_5 5 .2 2 300 5425 0-32 008 r 22.38 2586 3.04 77.2 4800mmµ 48 2065 374,265 0 32 0 24 7 4 1x3' 569 655 77 35 • 0,08 4-11/8x4 2363 2125 3.13 91.2 700 20.07 i 300 94,000 0 013 0` 72' 600 692 80 41 a 500 0.0 0 2 00 94000 0 32 008 4-I x4 2429 278 3.07 91/ 10.805 3GU 152,280 0 0.3 0° 22' 7 617 704 77 41 6 S30.0 019112 53C 2065 456,280 0-3.2 -.. 5555. 5555 5_555 229 ',000 300 114,000 0-0.13 0°-19 6 65' 00/ 4-11/8x4 25,4 749 80 41.7 75 29.50 3.13 92.6 5555 550 59 0 2065 507300 0 32 _5555 ... ............. 5.. 5555.. 007 26.75 3001 312 92.R 18' 300 102,380 0-0.13 0°-19' 6 4-11/8 x4 680 762 79 422 580 0 mm p 380 2065 455,591 0-3.2 --_--- ' 0.07 27.75 31.25 3.13 94.0 24 9 24.000 250 113,000 0-0.13 0°_18. 6 6-1 1!8 x 4 704 794 80 42.6 600 6096 1725 502850 0-3.2 _ 5555 6 2842 3216 312 96.8 1 24803 250 102,790 0- 3.2 0" 18, 0.07 727 817 79 Ac 630.0 mr^µ i:30 1T5 457,416 0-3.2 5555.. 14-24 4st Style W77,Publication 20.03 350-600 §Couplings 8,'•0,17"/.''30.250,300mm sizes available to 115 standards.Refer to Section 06.17 for details. 'Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. Vd.ARNING:FOR ONE i'Wit FIELD I EST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by;50%for 3!.-31/2"/20-90mm;25%for 4"/100mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolls are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. t For cut groove systems only.For 14-24"/350-600 mm Roll Groove systems Victaulic offers the Advanced Groove System(AGS)line of products.Request Publication 20.03 for information on the Style W77 flexible AGS coupling. µas size product is designed with two housings and requires two bolts. Imo__._.._.._y___--e -7-'1 Y • sl Z f S. Y---�'' 1 Z r- '1� 4 bV►1� 1 i r ��w *4'74. ` J )1F • Nh-12'SIZES ♦� 1 1 Ville' 1`1144-22"SIZES 24"SIZES ..._ .�........... _-5555. 5555_..___ www.victaulic.com jCt9Ulid VICIACLIC IS A PEG 1 11 HED I RAN MARK OF VICTAULIC COMPANY.®2007 VICTAULIC COMPANY.AL RIGHTS RESERVED.PRIMED IN 1'HE USA. 06.04_3 REV_I 25 t Flexible Coupling STYLE 77 INSTALLATION _..............................._.... Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. .............. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for cetails. NOTE -_ __ _..... _............. This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. • 1111111111111111M1111111 111111 WCAS-6UBJ5N For complete contact information,visit www.victaulic.com • 06.04 1469 REV I UPDATED 6/2007 VICTAULIC ISA REGISTERED TRADEMARK OF VICTALILIC COMPANY.C 2007 VICTAULIC COMPANY ALL RIGHTS RESERVED.PRINTED IN THE USA i 'dLl�- 06.04 - 26 II • : �gg��yyyy gggg��ggpp� { g SO84f1406073' l 6wciu6,ePSP "° k:�Sw�;.>. UL FM Vds 0 SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS • STYLE 750 ap The Style 750 Reducing Coupling permits direct reduction on the piping run. Designed to replace two couplings and a reducing fitting,the Style 750 features a special reducing gasket for pressure responsive sealing.A steel washer which prevents telescoping of the gib smaller pipe inside the larger pipe during vertical systems assembly is available upon request. wit Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating:Orange enamel • • Optional: Hot dipped galvanized and others Gasket: (Specify choice°): • Grade"E"EPDM(All other sizes) EPDM(Green color code).Temperature range-30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold +86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range-20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional:Assembly Washer:Galvanized,carbon steel Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para • Location Date Approved Date www.victaulic.com 27 ictaul.0 VICTAULIC IS A RESISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ---------- - REV 11 06,08....1 IPS CARBON STEEL PIPE GROOVED COUPLINGSCAMP PARSONS MATERIAL SUBMITTAL 06.08 JOB#14 06073 Reducing Coupling UL <0> ® F SEE VICTAULIC PUBLICATION 10.01 FOR oE Lan_S • STYLE 750 4 i. DIMENSIONS Max.Work Allow.Pipe Boll/Nut6 Approx. Size Pressure• Max.End Load" End Sep.t Deflect.Fr.CL-1 No-Size Dimensions-Inches/mm Wal Each 1! 1 -3?[- 5�it) at 1I if• _`t III 1 Et,, - ':I ` "'� �7 I =PPP': I I. �Ilh �I .i�. IT1II 11 `PII p it " 11 1 ( , I -(ICI I r = ',t it r 1: w 1 t' .. .■1' qi lu • C 1718, '0" "•..env SRpr: s uC , ;��1 3.38 5.28 L88 - 27 ,D 0 44 J 0 I.(--, 1 _- nF2 85 I34 48 1.2 1'/r 350 1000 0-007 0.20 338 i:'3 198 2.0 40 2410 4450 0-1.8 0°-5T 17 2-?bx2 85 134 48 10 65 50 3450 9850 0-01.87 0"-47' 0.16 14 7 3/w x, 4.00 02 S5; 188 3.1 x 48 IA 76.1 mm x 2 350 1550 0-0.07 0.16 438 6.ri3 1,88 4.6 50 2410 6900 0-1.8 C'-4' 14 2-Kix21/2 111 144 3 48 2.1 3 2 350 1550 0-0,07 013 4.75 i.I3 188 4.9 80 x 50 2410 6900 0 L8 C"-39' t 1 2-;h x 23/4 121 18• 48 22 21/2 500 3250 0-0.07 0 39, 013 4.75 7.13 1.88 4.3 65 3450 14460 0-1.8 - 11 2-'/x 2'A 121 110 48 2.0 88.9mm x 76.1mm 350 2275 0--0.07 0°-39' 013 2-,4x2'/ 4.75 7.13 1.88 4.2 250 10125 U- 1 11 2 159 226 48 1.1 •. 121 181 4 2 350 1550 0-0.13 1"-19' 0.28 7-to x333 159 ;,1k' 225 8.1 100 x 50 2410 6900 0-3.2 25 5/ 3.7 2'h 350 2275 0-0.13 0.28 625 +S.9C 2.25 - 86 1"-19' 2-s/x43'.5 65 2410 10125 0-3.2 - 25 159 22s 57 3.9 3 500 4810 0-0.13 1,-19, 0.28 .,-�ex3 600 8.90 2.25 67 80 3450 21400 0-3.2 25 _ - IS 226 57 33 114.3mm x 76.1 mm 350 2275 0-0.13 1•-1rr, 028 2-,/ 6.5 8.90 225 6.9 2410 10125 0-3.2 25 x375 ',. 159 226 57 3.1 5 4 350 5565 0-0.13 0.22 7.18 10.30 2.13 11.2 125 v 100 l 2410 24765 0-3.2 I - 19 2-§G x 4 ii '82 272 54 5.1 6 4 350 5565 0 -0.13 0.18 Uvx 4'!n 853 11.90 215 150 x 100 2410 24765 0-3 2 C -ee 2- 1b.7 _... -.. 15 181 302 51 Z6 6 5 350 8500 0-0.13 0,18 831 11;30 225 129 125. 2410 37825 0-3.2 0 -S2 15 2 3/4 x 4 A 211 303 57 59 165.1 mm x 4 350 - 5565 0-0.13 0.19 863 1 140 225 15.2 0'-SS' 2 'ux4'/ 219 302 57 69 100 2410 24765 0-3.2 16 ' 8 6 350 12000 0 0.13 0 -38, 013 , 10.81 14.E,8 2.50 22.4 200 x 150 2410 53400 0-3.2 11 - ,a x 5 275 373 64 10 r2 Refer to notes on back cover. Style 750 Reducing couplings should not be used with end caps(#60)in systems where a vacuum may be developed.Contact Victaulic for details. r v _.. .I L-7-31 �__.__..._.y-.._..._..._._ z ( r■ x n) �L! (1,:11 1 �, 11.11 ■ www.victaulic.com 28 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. .t�lJf1(�.- 06,08 2 06.08 WS CARBON STLL s,4P_' -tCROOVED COUPLIN MP PARSONS MATERIAL SUBMITTAL JOB#1 dfl6073...__.... O U FM VdS SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS • STYLE 750 • figl FLOW DATA HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables.All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING Equiv.Pipe Equiv.Pipe �. L- .� E Ma4R§ E sue;. .;. WO :... ,lnche3�mrt� 2 2.7 50 x 25 �.� _.. 25 x_.. 50 03_. '..h.._ 20 1 Vi 1 ' 1.9 40 06 40 x 50 0b 1.9 2 2'h 1.0 245 2 50 65 0.3 65 x 50 0.6 2.. 1.9_. _ . 76.1 mm 1.0 • 76.1 mm x 50... 0.6_. _... 03 3 2 55 3 35 80 50 17 80 1. 2I5 3 8 4 3. 65 1.2 100 0. 889mm x 76.1 mm 2 65 80 0 4 2 60... c 3. 100... x 50 18 100 0. 2'S fic. .. 2.5 76.1mm x 889mm OS g. 6.0 1143 mm 30 8U 1.8 _. 0 3 114.3mm x 76.1 mm 1.8 g0 x 100_ _ 0 4 5.. 3411. 5 4 125 . x 100 0.9 100 x 125_ 1 6 6 4 150 x 100 68 150 109185.79098:634_._. ... 5 _._4.5_ 165.1 mm 4.6 125 14 14. e 6,0 5 x 6 2.3 165.1 mm x 100 1.8 125 150 0.7 6 8 60 8 6 7.3 1,8 200 x 150 2.2 150 200 www.victaulic.com 29 �CtaU,..,,..id VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 06 08 3 REV H �' `� J176#1406073 - Tr �L FM uLC` Hs) STYLE 750 SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS • An � t art GENERAL NOTES - __.._ - .__ - __._ ...__. __. .........._. _....... Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size. WARNING: FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. f Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by 50%for 3-3 V/20-90 mm;25%for 47100mm and larger. Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request. Contact Victaulic for details. WARNING: Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. •WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE ...... This product shall be manufactured by Victaulic or to Victaulic specifications, All products to be installed n accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications,designs arid standard equipment without notice and without incurring obligations. US&WORLD HEADQUARTERS CANADA CENTRAL AND SOUTH AMERICA P.O. Box 31 905-884-7444 1-610-559-3300 Easton, PA 18044-0031 USA 905-884-9774(fax) 1-610-559-3608(fax) 4901 Kesslersville Road viccanada®victaulic.cam vital©victaulic.corn Easton,PA 18040 USA EUROPE ASIA PACIFIC 1-800-PICK-VIC(1-800-742-5842) 1-610-559-3300 32-9-381-15-00 86-21-54253300 1-610-250-8817(fax) 32-9-380-44-38(fax) 86-21-54253671 (fax) pickvicwictaulic.cam viceurowictaulic.be vicap®victaulic.com www.victaufic.com UNITED KINGDOM MIDDLE EAST 44(0) 1438741100 971-4-883-88-70 1111111111111111111111111111111111111111 44(0)1438313883(fax) 971-4-883-88-60(fax) viceuro@victaulic.be WCAS 6QA 1RU ._......_.__ UPDATED 6/2006 06.08 1536 REV H 30 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED,PRINTED IN THE USA. �/ "Ct9L1�r C� 06.08 IPS CARBON STEEL PIPE- FIRE PROTECTION PRODUCTS 10.04 VICTAULIC'x IS AN ISO 9001 CERIIFIEU COMPANY • Style 744 FireLock® Flange Adapter VICP/t1's with Vic-PIusTM Gasket System casket System PRODUCT DESCRIPTION Style 744 FireLock Flange adapter is designed for directly incorporating flanged components with ANSI CL. 125 or CL. 150 bolt hole patterns into a grooved pipe system. Sizes 2-8"(50 -200 mm)are hinged • for easy handling with integral end tabs which facilitate assembly. zAm "`� The design incorporates small teeth inside the key shoulder I.D.to prevent rotation. • r 40 r Because of the outside flange dimension, FireLock Flange adapters should not be used on FireLock fittings.When wafer or lug-type valves are used adjoining a Victaulic fitting,check disc dimensions to • _ �k► assure proper clearance. FireLock Flange adapters should not be used as anchor points for tie-rods across nonrestrained joints. Mating rubber faced flanges.valves,etc.,require the use of a FireLock Flange washer. 2.8"Sizes FireLock Flange adapters with Vic-Plus gaskets do not require lubrication.The gasket must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. y try Style 744 FireLock Flange Adapters with the Vic-Plus TM Gasket System are designed and 1�rll! recommended for use ONLY on fire protection systems. r4 EMI Vic-Plus Gasket offers gasket Victaulic now offers a gasket system which requires no field lubrication on wet pipe systems.The Vic- PlusT"" System(patented)is dry,clean,and non-toxic. It reduces assembly time substantially and eliminates the mess and chance of over-lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook(I-100)for supplemental lubrication requirements. ■ 1 S �L®® NE See Victaulic (Exaggerated for c/.nay) publication 10.01 for details. DIMENSIONS Style 744 sealing Sizes 2-8" 50-200 mm) Surface Dimensions ( ) Pi Size Intl esImm Inches/millimeters A ANSI Class 125 and 150 Flange Max. Malt. pra' Actual Work End E _ Nominal Outside Press.' Load' No Bolt z Diameter Diameter PSI Lbs. Botts f Size t "A" "B" Lbs. 4 In.lmm In/mm kPa N Regd. Inches Max. kin. W X Y Z kg .7 Q Q 2 2.375 175 775 2.38 3.41 6.75 6.00 4.75 0.75 2.7 �� 50 60.3 1200 3450 4 ,irk X 25., 6o 87 172 152 121 19 1,2 *\,..131.Q I Y W 65 2.875 175 1135 4 'la X 3 2.88 3.91 7,88 7.00 5.50 0.88 4.2 65 73,0 1200 5050 73 99 200 170 140 22 1,9 Or., -��O 3 3.500 175 1685 4 X 3 3.50 4.53 8.44 7.50 6.00 0.94 4 8 80 88,9 1200 7500 89 115 214 191 152 24 2,2 ■ 4 4.500 175 2780 a 4.50 5.53 9.94 9.00 7.50 0.94 71 100 114,3 1200 11045 8 iy X 3 114 141 252 229 191 24 3.2 Note:Gray area of mating face must 5 5.563 175 4250 5.56 6.71 11.00 10.00 8.50 1.00 8.3 be free from gouges,undulations or 125 141,3 1200 18920 8 3/a X 3'/i 141 171 279 254 216 25 3.6 deformities of any type for effective sealing. 6# 6.625 175 6030 8 3l<X 3'1; 6.63 7.78 12.00 11.00 9.50 1.00 9.3 150 168,3 1200 26840 168 198 305 279 241 25 4,2 8# 8.625 175 10219 8.63 9.94 14.63 13.50 11.75 1.13 13.9 200 219.1 1200 45475 8 /a X 3'/z 219 252 372 343 298 29 6,3 'Refer to notes below. 1 Total bolts required to be supplied by installer.Bolt sizes for conventional flange-to-flange connection.Larger bolts are required when Vic-Flange adapter is utilized with wafer-type valves. n Not available with Vic-Plus gasket system.Lubrication is required. NOTES 'Working Pressure and End Load are total,from all internal and external loads,based on standard weight steel pipe,standard roll or cut grooved In accordance with Victaulic specifications.Contact Victaulic.for performance on other pipe. WARNING:FOR ONE TIME F 1E1 D TEST ONLY,the Maximum Joint Working Pressure may be increased to 1'!z times the figures shown. Style 744 FireLock Flange adapters provide rigid joints when used on pipe with standard roll or cut groove dimensions and consequently allow no linear or angurar movement at the joint. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. • .REGISTERED TRADEMARK OFVICTAULIC-'4,COPYRIGHT 2004 VICTAULIC-PRINTED IN U.S.A. 1177 REVD Victaulic Company of America• Phone:1-800-PICK-VIC(1-800-742-5842)- Fax 610-250-8817• e-mail.pickvic @vidaulic.com Victaulic Company of Canada• Phone-905-884-7444• Fax:905-884.9774• e-mail:viccanada @victaulic.com Victattllc Europe• Phone:32 9-381-1500• Fax.32-9-380-4438• e-mail viceuroaPvidaulic.be Victaulic America Latina• Phone:610-559-3300• Fax:610-559.3608• e-mail.vital @victaulic39n C t a V 1 l C o Victaulic Asia Pacific Phone 65-6235-3035• Fax:65.6235-0535- a-mil.vicap @viclaulic.com __. CAMP PARSONS MATERIAL SUBMITTAL 10I04 JOB#1406073 VIC-FLANGE ADAPTER NOTES • The Style 744(2-8'150-200 mm)design incorporates small teeth inside the key shoulder I.D.to prevent rotation. 2 FireLock Flange adapter should not be used on FireLock fittings.When wafer or lug-type valves are used adjoining a Victaulic fitting,check disc dimensions to assure proper clearance. 3 FireLock Flange adapters should not be used as anchor points for tie-rods across nonrestrained joints. Mating rubber faced flanges,valves,etc.require the use of a FireLock Flange washer. 4 Area A-B noted in the above drawing must be free from gouges,undulations or deformities of any type for effective sealing. 5 FireLock Flange adapter gaskets must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. s Flange Washers:FireLock Flange adapters require a smooth hard surface at the mating flange face for effective sealing.Some applications for which the Vic-Flange adapter is otherwise well suited do not provide an adequate mating surface.In such cases,it is recommended that a metal Flange Washer be inserted between the FireLock Flange adapter and the mating flange to provide the necessary sealing surface. Typical applications where a Flange Washer should be used are: A When mating to a serrated flange:a standard flat flange gasket should be used adjacent to the serrated flange and then the Flange Washer is inserted between the FireLock Flange adapter and the flange gasket. B When mating to a wafer valve:where typical valves are rubber lined and partially rubber faced(smooth or not),the Flange Washer is placed between the valve and the FireLock Flange adapter. C When mating a rubber faced flange:the Flange Washer is placed between the FireLock Flange adapters and the rubber faced flange. o When mating AWWA cast flanges to IPS flanges:the Flange Washer is placed between two FireLock Flanges.The hinge points must be oriented approximately 90'to each other. If one flange is not a FireLock Flange adapter(e.g.flanged valve),then a standard flat flange gasket must be placed adjacent to that flange and the Flange Washer inserted between the flange gasket and the FireLock • Flange adapter. E When mating to components(valves,strainers,etc.)where the component flange face has an insert: follow the same arrangement as in Application 1. F When mating to a Series 705-W Butterfly valve, Style 744 may only be used on one side of the connection. When ordering Flange Washers,always specify product style(Style 744)and size to assure proper Flange Washer is supplied. MATERIAL SPECIFICATIONS Flange Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Coating: Black enamel • Optional: Hot dipped galvanized Bolts/Nuts:Supplied by installer Gasket: • Grade"E"EPDM-Type A Vic-Plus Gasket System u (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Ap- proved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated work- ing pressure using the Grade"E"Type A Vic-Plus Gasket System,requiring no field lubrication for most installation conditions. A Standard gasket approved for dry pipe systems to-40°F(-40'C).Based on"typical"pipe surface conditions.supplemental lubricant is recommended for services installed below O'F(-18°C)and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water.Supplemental lubrication may also be rquired on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams. This product shall be manufactured by Victaulic Company.All products to be installed in accordance with current Victaulic installationlessembly instructions. • Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring abhgeamns. 2 32 Style 744 FireLock' Flange Adaptor - - - •- IPS CARBON STEEL PIPE- FIRE PnU i EL i ION FITTINGS 10.21 VICTAULIC1 IS AN ISO 9001 CERTIFIED COMPANY • No. 67 Vic®-End II End of Run Fitting PRODUCT DESCRIPTION The fitting ion 67, alls easily with standard uFi el Locgk''Scoupings and allows direct head to connection,branch ion,sprigs The or drops, Available in 1'/4, 11/2, 2 and 21/2° (32-65 mm)sizes,the fittings can be supplied with 1/7,3/4,or 1"(15, 20 or 25 mm)female threaded (NPT)outlet(BSPT option available). The 90°reducing outlet fitting is UL/ULC Listed and FM Approved for a maximum rated working pressure of 500 psi(3450 kPa). UL See Victaulic publication 10.01 for details. DIMENSIONS, PERFORMANCE SIZE Weight Approx. Equivalent Nominal nches Incheslmm L .Jkg Feetlmeters of Pipe mm m 2.8 CIOE I 13/.1 X V2 NPT 2.39 1 0.9 32 X 15 NPT 61 0.6 4_ .------ X '1.NPT 2.38 14 2.9 1 X 20 NPT 61 0.6 2.8 X 1 NPT 2.36 1.4 2.8 I I X 25 NPT 61 0,6 0.9 • (a--CtoE-1 1x12 X '12 NPT 2.50 1.6 209 40 X 15 NPT 64 0,7 X 32n NPT 2.40 �6 29 X 20 NPT 0.9 29 X 1 NPT 2.50 06 2. 9 X 25 NPT 64 1 7 4.0 2 X ' NPT 2 0�6 1,2 50 X 1 I5 15 NPT 70 4.0 2 X NPI 2. 5 0,8 1.2 X 20 NP 70 0 4.0 X 1 NPT 2.75 1,2 X 25 NPT 70 0,7 5,2 2,12 X '72 NPT 3.00 2,0 1.7 65 X 15 NPT 76 5 7 X '2n NPT 3.00 X 20 NPT 76 0,9 1,7 X 1 NPT 370 2.0 5.7 1,7 X 25 NPT 76 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12,painted Orange Enamel. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. • Optional: Galvanized-hot dipped. Outlet: NPT • Optional: BSPT This product shall be rnanuieclureo by Victaulic or to■ictttlic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions, Virtaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. aloe REV C • W REGISTERED TRADEMARK OF VICTAULIC-O COPYRIGHT 2005 VICTAULIC-PRINTED IN U.SA.-SKU M'NCASEDCGPw United States• Phone:1-800-PICK-VIC(1-800-742-5842)• Fax:610-250-8817• e-mail:pickvic @victaulic.com Canada• Phone:905-884-7444• Fax 905-884-9774• e-mail:viccanada@viclaulic.com Europe Phone:32-9-381-1500• Fax.32-9-380-4438• e-mail:viceuro@viclaulic.be '����',Ca UK• Phone:44(0)1438741100- Fax:44(0)1438313883- e-mall:viceuro�Victaulicbe Central and South America• Phone.610-559-3300• Fax:610-559-3608• e-mail.vical@victauhg.Om Australasia• Phone.86-21-58855151• Fax:86-21-58851298• e-mail.vicap @victaulic.om • ® Hose Sol 5 UL listed (Braided or Unbraided)and FM approved (Braided only). This system includes: • Flexible stainless steel hose of various lengths • Nipples for attaching to rigid piping • Reducers for connecting sprinklers • Patented, light-weight mounting bracket systems The EasyFlex system installs without tools and allows complete lateral alignment of sprinklers during installation. Mounting bracket assemblies are available in 25"and 50'lengths.Each length can include a set of short or long T-Bar brackets.TBL brackets(long)are 1•/25 mm higher than TBS(short)ones for recessed applications. The system accommodates'"or 14'712.7mm or 19.05mm sprinklers with flexible length hoses ranging from 24"-72"/60.9cm-182.8cm The stainless steel flexible hose is available in both braided and unbraided styles. The system requires no welding for assembly. MATERIAL SPECIFICATIONS Flexible Hose Composition:Stainless Steel 304(available braided and unbraided) Lengths Available:24',36",48',60',72760.9cm,91.4cm, 121.92cm,152.4cm, 182.8cm Pipe Openings Available:1"or 3/4712.7mm or 19.05mm • Seal Material:EPDM Optional Components: 25"Bracket Assembly 50"Bracket Assembly` Nylon isolation ring EPDM gasket Upright reducers for rigid pipe(4',5",6",7",8'/101 mm, 127mm, 152mm, 178 mm,203mm) *50"bracket not UL Listed or FM approved Minimum Bend Radius: 3"176 mm(UL Listing) 87203 mm(FM Approval) Do not bend within 21/2"/63.5 mm from connection nut. Maximum Number of Bends per drop:3 JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Pars Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.02008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. rct9l1�IC REV B 35 CAMP PARSONS MA I EHIAL SUI3MI I IAL JOB#1406073 FIRE PROTECTION PRODUCTS -ACCESSORIES 40.90 EasyFiex Flexible Hose Assemblies PERFORMANCE DATA Friction Loss for 1 712.7mm Flexible Hose* 100.00 9000 C 80.00 a d 70.00 . _.. ▪ 60 00 SOHO C7 4000..... La• 30.00 J ▪ 20.00 O i 10.00 .._.1.-. 0.00 ..._.. ...........__. 0 20 40 60 BO 100 120 HOSE LENGTH(inches) UL -11— FM —M— 'Test Standard NI 14/4 and FM Global Testing Class Number 1637 Friction Loss for 3/4714.47 mm Flexible Hose* 90.00 8000 _ . . • co w w 7000'... .. 0- • 6000 0 L5 z 40.00 —._ ...._. .... .. 2 30.00 i 2000... .1 CI 14 10.00... ... 0.00 0 20 40 60 80 100 120 HOSE LENGTH(inches) UL FM -M- 'Test Standard UL 1474 and FM Global Test ng Class Number 1637 Note:Factory Mutual tests the flexible hose both straight and with the maximum number of allow- able bends.The pressure loss is then based on the average of the two tests at each of several pres- sures,using C=100.The pressure is varied from 15 psi to 175 psi in 10 psi intervals. Underwriter's Laboratory bases their test on five difference water velocities from 10—18 tt/sec using C=120.UL does not average the straight and multiple bend results to calculate an overall friction loss. ............. . www.victaulic.com • VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2008 VICTAULIC COMPANY ALL RIGHTS RESERVED. \J 'aV�I�i 10.90 2 36 REY...B CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 (}Q 9 O EIRE PROTECTIC?P_.j PI?C:IOC,:.TS--ACCESSORIES ............................... .. • S ay , i ;. `i . H1,I'-'7 , I .i W s n i PRODUCT WEIGHT BY MODEL Hoses I EasyFlex P/N I We 1 4h 24 'h X BRAIDED FLEX HOSE EFB221 1.852 1 826 24 X 3"BRAIDED FLEX HOSE EFB324 2.119 EFB236 36'X'k"BRAIDED HCX HOSc �„ � 2.093 AIDED FELL HOSE EFB336 46 'd X "BR 2.414 48 X h'BRAIDED EFB248 ED FLEX HOSE 2.388 48 X36 BRAIDED FLEX HOSE EFB348 - - - - EFB260 2.714 50'X 3b"BRAIDED FLEX HOSE 2.688 ED FLEX HOSE 60'X'h"BRAIDED HOSE EFB360 _ - - -- 72'XW BRAIDED FLEX HOSE EFB272 3.032 ID EFB372 3.005 72'X 36'BRAIDED FLEX HOSE 1482 24'X11 UNBRAIDED FLEX HOSE EFU224 1.455 24'X 3 UNBRAIDED FLEX HOSE EFU324 ..._. 36 X'h EFU236 1.667 UNBRAIDED FLEX HOSE 1 641 - - 36 X 36 UN BRAIDED FLEX HOSE EF0336 48"X V+'UNBRAIDED FLEX HOSE EFU248 1.861 48'X 8'UNBRAIDED FLEX HOSE EFU348 1.835 AI FFU260 2.026 60'X`h'UNBRAIDED FLEX HOSE 2.000 60 X 36"UNBRAIDED FLEX HOSE EFU360 -- - BRA EFU272 2.165 72"X'h'UNBRAIDED FLEX HOSE 2.139 72"X 36"UNBRAIDED FLEX HOSE !. EFU372 Backets Lasy Flex PIN Weight 55801 0.161 _. Snap Clamp 0.148 • Wall Mount Bracket 5513W01 Metal Stud End Bracket M5603 0.062 Wood Stud End Bracket W5B01 0.0^9 Snap On T-Bar Recessed Bracket T3501 0.232 0.287 Snap On T-Bar Concealed Bracket TBLO2 -- ---- 25'Stock Bar 5025 0.518 50"Stock Bar 5060 1.036 Reducers EasyFlez PIN iu3 edu C2... 1 114 Elbow/Reduut >i'.oi i. 1114 Elbow/Reducer'h'Long 0.626 Reducer'/.X 4Y. (MXF) --- 1.067 Elbow/Reducer'Short 18D343 - .-- -- - Elbow/Reducer 36 Long LRD34L 1.506! 0.318 Nipple 1'X 2s/"TXT(MXM) NP01 Reducer Y'X 4'R TXT(MXF) RD1 0.650 Pxt. EasyFlez P'N Wvght Nylon Isolation Ring PR01 0.013 0022 Gasket GRO1 "- 'h Plastic TP1 .,. "Reducer Plasc Lid 2 0.002 34"Reducer Plastic Lid TP34 • www.victaulic.com Niet9 U 1 r C- VICTAULIC IS A REGISI FR ED TRADEMARK OF VICTAULIC COMPANY.C 2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV B 37 Easynex Flexible Hose Sprinkler Assemblies • WARRANTY ........_. ............_ _..-. _.. Refer to the Warranty section of the current Price List or contact Victaulic for details. .._-.............._-....._._-.. .._-......._..................._. ._-.........................._._- NOTE _..... _._..._ _ EasyFlex is a registered trademark of Kofulso Co., Ltd. • III 1111 1 111111111 111111111111111 1111 1 1F1 V'CA$-7C80JU .-._........................._... ._-_.............. .............. For complete contact information,visit www.victaulic.corn 40.90 4594 REV B UPDATED 312008 • VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY ED 2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.90 38 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • VicFlex' Sprinkler Fittings J taul,c° Series AH1, AH2 and AH4 Braided Flexible Hose Assemblies 10.85 • Brackets: Style ABl for suspended and hard-lid ceilings, allows installation before ceiling tiles in place Style AB2 for hard-lid ceilings, allows for vertical sprinkler adjustment Style AB4 for hard-lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment Approvals/Listings: Style AB7 for suspended ceilings and hard-lid ceilings <C>. GO us (vds ILPCB Style AB7 Adjustable for suspended and hard-lid ceilings MUD G412024 1041-01 Style AB8 for hard-lid ceilings (regionally available) ,,I ;r more rhstails. Style AB9 for hard-lid ceilings with hat furring channel grid systems Product Description: Style AB10 for Armstrong®TechZone`" ceilings VicFlex sprinkler fittings provide sprinkler installation on suspended ceiling grids, wood or metal stud/joist or hat furring channel hard-lid ceilings utilizing a flexible, stainless steel hose and steel bracket assembly. Refer to the Installation Manual for all applicable ASTM ceiling material and installation standards. • System Components • Hoses: Series AH1 Braided Hose Series AH2 Braided Hose Series AH4 Braided Hose Assembly lengths: 31, 36,48, 60, 72"/90, 914, 1220, 1525, 1830mm. Note: length includes branch-line nipple and 5.757140mm straight reducer. • Sprinkler Reducers: 1/2" and 3/4715 and 20 mm sprinkler connections and 5.751140mm,9"/230mm, 137330mm straight lengths and short, long 90° elbows. Note: The short 90° elbow is typically used with concealed sprinklers while the long 90°elbow is typically used in the installation of recessed pendent sprinklers. • Branch Connections: 1"/25mm NPT or BSPT branch line nipples for attaching to rigid pipe. 3/4720mm NPT or BSPT available for VdS. Job/Owner Engineer System No. Spec Section Location j Paragraph Contractor Approved • Submitted By Date Date victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. 1 lctauI,c° 40 GAM"I'AHSUNS MA I tit IAL SUbMI I I AL JOB#1406073 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Technical Specifications: Material Specifications: Maximum Working Temperature:225°F/107°C • Series AH1 Maximum Working Pressure: Flexible Hose:300-series Stainless Steel • • 200 psi/1375 kPa (FM Approval) Collar/Weld Fitting:300-series Stainless Steel • 175 psi/1206 kPa (cULus Listed -Series AH2 only) • 1600 kPa/232 psi (VdS/LPCB Approved) Gasket Seal:Victaulic EPDM Connections: Isolation Ring: Nylon To branch line (inlet)via 1725.4 mm NPT or BSPT male Nut and Nipple: Carbon Steel, Zinc Plated thread OR Reducers(1/2 or 3/4"): Carbon Steel, Zinc-Plated To branch line (inlet) via 3/4i20 mm BSPT male thread • Series AH2 (VdS only) To sprinkler head (outlet) via 1" or 3/4715 mm or 20 mm Flexible Hose: 300-series Stainless Steel NPT or BSPT female thread Collar/Weld Fitting:300-series Stainless Steel Minimum Bend Radius: Gasket Seal: Victaulic EPDM • 7"/178 mm (FM Approval) • 2751 mm (cULus Listed - Series AH2 only) Isolation Ring: Nylon •3776.2 mm (cULus Listed -Series AH1 only) Nut and Nipple: Carbon Steel, Zinc Plated •3776.2 mm (VdS/LPCB Approved) Reducers (1/2 or 3/4"): Carbon Steel, Zinc-Plated Maximum Allowable Sprinkler K-Factors: • Series AH4 • FM (1 715mm reducer) K5.6/8,1 (S.I.) (3/4"/20mm reducer) K14.0/20,2(S.I.) Flexible Hose: 300-series Stainless Steel • • cULus (1/2715mm reducer) K8.0/11,5 (S.I.) Collar/Weld Fitting:300-series Stainless Steel (3/4720mm reducer) K14.0/20,2 (S.I.) •VdS/LPCB (1/2"/15mm reducer) K5.6/8,1 (S.I.) Gasket Seal: EPDM per ASTM D2000 (3/4720mm reducer) K8.0/11,5 (S.I.) Isolation Ring: N/A Nut and Nipple: Carbon Steel, Zinc-Plated Reducers(1/2 or 3/4"): Carbon Steel, Zinc-Plated • Brackets: Carbon Steel, Zinc-Plated 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved • victaulic.com 2 ✓CtauliC 41 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 c UL us FRICTION LOSS DATA: LISTED -Series AH2 Braided Hose with Straight 5.75" Reducers -Style AB1 and AB10 Brackets Series AH2 Hose Maximum Length of Equivalent Length Number of Stainless Steel ' of 1"/33.7mm 90°Bends at 2"/51mm Flexible Hose Outlet Size Sch.40 Pipe(C=120) Bend Radius inches inches/type feet/meters 9:'/Straight 16/4.9 ..... .. i 31 ............ 3/4"/Straight 17/5.2 4 ....... 1/21/Straight -- 21/6.4 5 ... 36 ?6'/Straight i 23/7.0 _... 5 ........ 1,51/Straight 32/98 8 _._ as i ... 3/41/Straight _. 37/113 ... 8 .. __..._i .. _ 3/4”/Straight .... 46/14.0 10 60 aid/Straight 46/14.0 10 �_.._... ' __. _... . . __ ,h"/Straight 55/16.8. 12 • 72 'k '/Straight 53/16.2 12 Series AH2 Braided Hose Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2151mm center line bend radius Length of• Stainless',. • • • • Steel • Flexible Outlet 1 2 3 4 5 6 7 8 9 10 11 12 Hose Size Bend / Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends inches I inches 1 31 'h 8.5/26 11.0/3.4 13.0/40 16.0/49 NA NA NA NA NA NA NA NAII 3 4' 10.0/30 12.5/3.8 14.0/4 3 17.0/5.2 N.A N.A NA N.A N.A N.A N.A N.A 36 rh' 13.5/4.1 16.0/4.9 18.0/5.5 19.0/5.8 21.0/6.4 N.A N.A N.A ...,N.A N.A N.A N.A• 3/4 14.0/4.3 17.0/5.2 19.5/5.9 20.0/6.1 23.0/7.0 N.A N A N.A NA . N A N.A NA 1/2 ' 15.5/4.7 17.0/5.2 19.5/5.9 _ 20.0/61 ' 21.0/6.4 22.0/6.7 28.0/8.5 32.0/9.8 NA N.A N.A N.A 48 3,a 17.0/5.2 19.0/5.8 21.5/6.6 24.5/7.5 l 26.0/7.9 27.0/8.2 30.0/9.1 37 0/11.3 N.A N.A N.A NA 1/21 215/6.6 24.0/7.3 27.0/8.2 28.5/8.7 30.0/9.1 31.0/9.4 37.0/11.3 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A 60 3a' 23.0/70 24.0/7.3 28.0/85 29.5/9.0 30.5/9.3 31.0/9.4 38.0/11.6 42.0/12.8 44.0/13.4 46.0/140 N.A N.A 72 f 300/91 320/9.8 36.5/11.1 37.5/11.4 40.5/12.5841.0/12..8. 420/12.8]46.0/140 490/149,52.0/158,54.0/165 55.0/16.8 o/4 r " 32.0.9.8 32.5/9.9 :35.0/103 35.5/108 40.0/12.3140.5/123 41.0/12.51460/14.0 50.0/15.2115113715.5'52.0/15.8 53.0/1.62 Note:Values for use with 5.75'straight reducers. How to use this Design Guide: 1 For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends.In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. 2 It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected.When this happens,the design guide'nay be used lu rind equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. • 10.85 5839 Rev V Updated 11/2014 C 2014 Victaulic Company.All rights reserved. �Ct:9lJ�iC victaulic.com 3 ....____....... 42 UAMY YAHSUNS MA I EKIAL SUBMI I I AL JOB#1406073 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 • c Ut us FRICTION LOSS DATA: D -Series AH1 Braided Hose with Straight 5.75"Reducers -Style AB1 and AB10 Brackets • Series AH1 Hose • • Length of Maximum • • • • Equivalent Length Number of • S • tainless Steel of 1"/33.7mm • 90°Bends at 3"/76.2mm Flexible Hose Outlet Size Sch.40 Pipe(C=120) Bend Radius 1 inches inches/type feet/meters • 'h'/Stra ight .._............. 52/15.8 ..........-. ._..._.. • 3.-..31 3/4"/Straight 55/16.8 _.. • • •• 36 '7T/Straight 63/19.2 4 -- " • -Y/Straight 66/20.1 4 • 16"/Straight ht 78/238 q 48 /Straight _............ 80/24.4 35 _... 4 • 60 ._ le/Straight _.. 88/26.8 .__ .. .__...—......-.-.._-..._- __ ....... • .d/Straight 90/27.4 4-*--- _ 1/2"/Straight 112/341 5/2 Ye/Straight 118136.0 _.- _.. s --. ...._ ! .__._._............ Series AH1 Braided Hose Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 3"/75mm center line bend radius Length of • Stainless Steel Flexible Outlet 1 2 3 4 5 Hose Size Bend Bends Bends Bends Bends inches inches • ii i 31 Y 32 42 57 N.A N A 34 33 44 55 N.A NA ! • Y 33 43 53 63 t N A 36 ' 36 46 56 66 N.A 48 1/2 i 46 57 68 78--- N.A -- i. '4 51 60 71 80 N A i y` 56 67 77 88 N.A 60 I 'A 58 69 80 90 N A i y -..... 69 79 91 102 112 72 i r/a' i 73 84 95 106 118 Note:Values for use with 5.75'straight reducers_ How to use this Design Guide: 1 For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends.In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. 2 It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected.When this happens,the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. 10.85 5839 Rev V Updated 11/2014 C 2014 Victaulic Company All rights reserved. • victaulic.com 4 ✓ctaulrc° 43 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 • ern+ FRICTION LOSS DATA: -Series AH1, AH2 and AH4 Braided Hose -Various brackets specific to hose Series AH1 Hose Series AH2 Hose Series AH4 Hose For use with Style AB1,AB2, For use with Style AB1,AB2, AB4,AB7,AB7 Adj.,ABB,AB9 A134,AB7,AB7 Adj.,AB8,AB9 For use with Style AB1,AB7,AB8, and AB10 VicFlex Brackets and AB10 VicFlex Brackets and AB9 VicFlex Brackets Maximum Stainless Equivalent Number of Maximum , Maximum Length of'. Number Equivalent Number Equivalent Steel Length of 90°Bends at Length of of 90°Bends at Length of of 90'Bends at Flexible Sprinkler Outlet 1133.7mm 71178mm Bend 1"/33.7mm 7'7178mm 1'733.7mm ; 71178mm Hose* K-Factor Size Sch.40 Pipe i Radius Sch.40 Pipe Bend Radius : Sch.40 Pipe Bend Radius feet/meters i feet/meters inches/type feet/meters � ...._ 2 - - -2 .... 20.6/6.3 inches Impenal/S.I. me 23.5/71 ,z 15traight 53.8/164 2 31 5.6/8.1 + 23/70 21,7/6.6 '90 Elbow 53.flr16.4 --- ....._. .._ 27.8/85 29.7/9.0 2 2/i/Straight 63.7/194 2 - 29.8/90 36 5.6/8.1 1/90"Elbow 63.1/19 7 27.7/8.4 _. ------ .- 27.5/8 3 _-- _-- _ 1/2"/Straight 87.9/26.8 3 L- 38.2/11.6 3 3 48 5.6/8.1 37.4/11 4_ ._._. 29.218 9 i ___-..._ ■r 1/2"./Straight Elbow 8531231 35.7,10 9 .z/Straight 112.2/341 i „42.4/129 4 4 z 4 43/131 372/113 60 5.6/8.1 ,, 90.'Elbow 108.4/33 0 }. 1........ , -• -- r;z 45.9/14.0 46.6114.2_„_' 4 4 /Straight 136.8/41 6 4 - 47.5/14.5 ._ • 72 5.6/8.1 16 790°Elbow 131 1/399 l 48.5/147 .-`-.--- 13.3/4 0 '/a75traight 44.4/135 . . 20.7/63 2 - 2 31 8.0/11.5 2 20.5/62 .,...... ......-........ , 14.6/44 -...... - m/90°Elbow 476/14 S _.._ - ` 21.7/66 2 2 25.0!7 6 � - - -.--- 'a Straight 55.6/169 i i___ --- -- 1 2 22.4/6.8 !• 36 8.0/1 LS =4 90°Elbow 575/17.5 5 24.6/7.5 --- -- 35.5/108 212264 3 48 8.0/11.5 /Straight 82.8/252 „ 3 34.7/106 22.2/6.7 ,-- _.._ 1;4790"Elbow 81.7/24.9 .. + 3 - • - -- - 43.5113.2 27.9185 4 3/0 Straight 110.1/335 40,1/122 , 289/88 60 8.0/11.5 ,,4/90°Elbow 105.9/32 2 - _- -----�'-- 4 --._.. ---- 38.8/118 39.6/12 'a/Straight 1373/418 4 4 72 80/11.5 - 45.2/137 394/120 ...._. 1/2",/90`Elbow 130.2/39.7 4 -{- 178154 --...... 16.4/50 2 3/4/Straight 45.5/13.8 2 I- 2 _ 19.9161 i 31 11.2/16.1 1,°'i90'Elbow 471114.3 18/55 _ -_. - - 21.7/66 1,4'/Straight 66.3/20.2 --.-2 1 222/67 J 2 247/6.6 2 • 36 11.2/16.1 , - _-- i 221/67 1/4"/90' 57.5/17.5 -;- ----- ' -... - .......-._ 1 32.9/100 285/87 '4/Straight 82.7/25 2 3 - 3 29.9/ 1 9 , 3 48 11 2/16.1 , 90'Elbow 828/252 321/98 ._ - 3/4"/Straight 34.7/10 5 ro"/!Straight 109.1/332 4 -- 3.68/112 4 _.- 4• 60 11.2/16.1 - - .. - _ 303/92 •Elbow 1 1081/329 37.1/113 -3 __... . 38.6/116 405/123 -.- 3/4"/Straight 135 5/41.3 4 --- ' 4 -1' 38.6/117 _ 72 11.2/16.1 1/4790°Elbow 1334/406 �• 4 • 419/127_ .__ t -_......... .149/45 .__ 163/50 2 �/°/Straight 44.3/13.5 � 2 _ 31 14.0/20.2 2 155/A72 72 __- 19.9/6.1 3/4!90°Elbow 46.4/14.1 I " 21 8/6.7 --- - ---- 3'n/Straight 55.5/16.9 . 194/5.9__-._..� 2 - 2 24 2/7.4 2 36 14.0/20.2 '/4/90°Elbow 567/1/3 19.6/5.9 1 - 28.3/8.6 3/4/Straight 83.0/253 r _ 303/92 3 3 48 14.0/20.2 29.5/8.9 29.9/9.1 „-....,-, ... '/4 790°Elbow 82 1/25 0 _ - -- 3..- 1 339/103 ._, 349/10.6 • - - 3/i/Straight 110 4/33.6 4 4 � -� 4 60 14.0/20.2 1 34.1/10.4 30.3/9.2 '/4/90"Elbow 10/5/32 i -_ -" 415/12.6 _-- - - 'A/Straight 1379/420 i 375/114 4 __._ 72 : 14.0/20.2 3 . - - 38.6/117 366!11.7 ... 4..._._ /4/90°Elbow 132 8/40A ---- - - - 1 FM Notes: Series AH1,AH2 and AH4 have been tested and Approved by FM Global for use in wet,dry and preaction systems per NF PA 13,13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 163/and Vds standards for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance,leakage,mechanical and hydrostatic strength. Differences in equivalent lengths are due to varying test methods,per FM 1637 and VdS standards.Refer to these standards for additional information regarding friction loss test methods. EXAMPLE:A 48-inch hose installed with two 30°bends and two90°bends at a 7-inch bend radius is permitted and considered equivalent to the data in the table • shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. 10.85 5839 Rev V Updated 11/2014 C 2014 Victaulic Company.All rights reserved. CtBU�IC' victaulic.com 44 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 victaufic.cam I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 ep r RICTION LOSS DATA: -Series AH1, AH2 and AH4 Braided Hose -Style AB1, AB2, AB4, AB7, AB7 Adj., AB8,AB9,and AB1O Brackets . _.. • Series AH1 Hose Series Hose AH2 ase Series AH4 Hose Equivalent Length of Equivalent Length of Equivalent Length of steel pipe according to steel pipe according to steel pipe according to EN 10255 DN 20 EN 10255 DN 25 EN 10255 DN 25 Maximum Number Length of Stainless (26,9 x 2,65)and (33,7 x 3,25)and (33,7 x 3,25)and of 90°Bends at Outlet relating to a flow relating to a flow relating to a flow 3'776.2mm Bend Steel Flexible Hose Size velocity of 5 m/s - velocity of 5 m/s velocity of 5 m/s Radius mm/inches mm/inches type meters/feet meters/feet meters/feet 790/31 15mm/1/2 /Straight 20 mm/33a /Straigh[ 4.0/12.9 5.5/18.0 5.5/18.0 3 915/36 15mm/1 /straight _... • _.-... _.._ _............. _,. 20 mm 4.6/15.0 46/15.0 6.4/21.0 6.4/21.0 15mm/1"/Straight _-- •----.._.__ 1220/48 , - ---..... 3.._..._...-..._ 20 mm/3/4"/straight 6.1/20.0 -_- 6.5/27.9 8.5/27.9 • 1525/60 15mm/rfi"/Straight 20 mm/'/e /Straight ..._,_.-.,. 7.6/25.0 10.7/35.1 10.7/35.1 4 ---_ 15mm/1/2 /Straight 1830/72 __..... .. .. ...... _- 20mm/3/4'/Straight -._ 92/30.0 12.8/42.0 12.8/42.0 4 VdS Ceiling Manufacturers List -- --- - --- - _. _ AB1,AB2,AB7,AB10 1.AMF AB4/9 AB8 2.Armstrong No specific approval 1.Hilt 3.Chicago Metallic 2.Knauf 4.Dipling 3.Lafarge 5.Durlum 4,Lindner 6.Geipel 5.Rigips 7.Gema-Armstrong 8.Hilt! 9.Knauf 10.Lafarge 11.Linder 12.Odenwald 13.Richter • 14.Rigips 15.Rockfon Pagos 16.Suckow&Fischer 17.USG Donn ILPCB FRICTION LOSS DATA: -Series AH2 Braided Hose -Style AB1 Bracket Series AH2 Hose ' --- Series AH2 Hose Equivalent Length - Equivalent Length of steel pipe of steel Length of according to Maximum Length of pipe Stainless EN 10255 DN 20 Number of Stainless a10255 D to 25 Maximum ' Steel (33,7 x5 DN 25 Number°Bend of I Steel (26,9 x 2,65)and 90°Bends at Flexible ele Outlet ' relating to a flow 3 f76.2mm Flexible (33,ti x 3o a)and 90° 6.2m at Size velocity of 5 m/s Bend Radius Hose Outlet Size relating of a flow Bend Size : velocity of 5 m/s ,Bend Radius mm/inches mm/inches/type meters/feet mm/inches mm/inches/type ..__ ---- ---- tyP meters/feet 790/31 15mm Ph /Straight 12.65/41.5 2 790/31 15mm/rfz'/90°Elbow 20 mm/3/. /Straight __,., 20 mm/#"/90°Elbow 14.4/47.2 2 915/36 15mm/1/2 /Straight _-- _ 15mm/yin"/90°Elbow - 20 mm/3/4"/Straight 14.8/486 9._-_. ......_ a....... 3 915/36 20 mm/3H'/90°Elbow 14.3/46 9 3 1220/48 1$mm 11h /Straight 15/492 3 1220/48 15mm/%z'/90°Elbow .-- 20 mm/It /Straight 20 mm/3/4'/90°Elbow 15.3/50.2 : 3 1525/60 15mm/1 /Straight 15mm/Y: /90°Elbow - - 20 mm/3/. /Strai ht 15.3/50 2 l 3 1525/60 - -- 16.0/52.5 9.-. -..._.._. 20 mm/3'. /90°Elbow 3 15mm/�h /Straight; _ ,........-__ .. 1830/72 r i5mm/�h /90°Elbow _ ..._ 20 mm/3/1 /Straights 175/574 3 1830/72 20 mm/3/e"/90"Elbow 17.1/;6.1 z 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. • victaulic.com 6 ✓ctaulrc` 45 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 victaulic.com I Vic Flex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Product Details - Series AH1 Braided Hose Series AH2 Braided Hose Series AH4 Braided Hose Item Description , ® 0 (1' 0 ID 1 Flexible Hose 2 Isolation Ring(Series AH1 and AH2 only 4 NMI 11111111.111IMMI II eliiiill1111111 Hu All 3 Gasket , —.I —J 4 Nut A B 5 Branch Line Nipple 6 Braid 7 Collar/Weld Fng Hose Length Dimensions 8 Sleeve(AH2 Only) t .... Hose Length ! A B Inches i inches inches • .• mm I mm mm 31/790 25.25 31/790 . 36/915 31.25 36/915 48/1220 4225 48/1220 60/1525 54.25 60/1525 72/1830 66.25 72/1830 Standard C I 1'I I IIMIIIIIIIIIIIhr--- II 5 P5"7140 rrim straight reducer Ill Optional 1 1 111 111 mil — 411 km 1 114 Id 9.07229 mm straight reduce' 4!11111111111111111111111111 )] 13.0733D mm straight reducer 2 627 —136t6.5 686 66.5 mm r .__ T ink 1 _..,. Ill E I=- E.I 53(k, =, 4.837 2-1121 I60.0 mm E 122.7 mm = 7 f 1 7 = = MW "NW M. MN Short 90°elbow reducer Long 90°elbow reducer Note:The Short 90°elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers. 110 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 7 Nictaulic° 46 CAMP PARSONS MATERIAL SUBMIT I AL JOB#1406073 victaulic.com I Vic Flex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Vic Flex Brackets Style AB1 OD • Suspended Ceilings ...-„A • Hard-Lid Ceilings (FM Only) i 41) Item Description Ji i 1 I 24"/610mm or 48"/1219mm Square Bar* __I • r 0 2 I Patented 1-Bee•Center Bracket I 1 3 I End Bracket i ..... —....24:■ ., *Both sizes FM/VdS/LPCB approved,cllLus listed 0 0 1...1% 41101) Style AB2 0 • Hard-Lid Ceilings Item Description IllirN*‘.."4.%1111441114114111 0 f 1 247610mm or 4871219mm Square Bar* 2 Patent-Pending adjustable Center bracket 0 3 I End Bracket *Both sizes FM/VdS approved. ar -,f....%., Note: 542'/4mm hex key required for adjustment I.Pt li .0. III At, 00 Style AB4 • Hard-Lid Ceilings with Hat furring channel "r•• grid system , , . 's,,,,s 1 Item Description ,%\\\. 'N<,,,N1 r - 1 1 24/610mm or 48/1219mm Square Bar" 0 i 2 Patent-Pending adjustable Center bracket ! 1 3 [ End Bracket for Hat Furring Channel I 'Both sizes FM/VdS approved Note.14 /4mm hex key required for adjustment _ 144 z 4"."11.111 e 10.85 5839 Rev V Updated 11/2014 C 2014 Vietaulic Company.All rights reserved. 4111 victaulic.com 8 s jerctaulic 47 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 IIIVicFlex Brackets Style AB7 0 4% • Suspended Ceilings • Hard-Lid Ceilings Item Description 1 24"/610mm or 48'/1219mm Square Bar" _ 2 Patented 1-Bee"Center Bracket ;`^`f 3 _., End Bracket ,., ;�... , 0 `Both sizes FM/VdS approved. Style AB7 Adjustable © .,, • Suspended Ceilings I 0• Hard-Lid Ceilings +F Item Description 0 1 700mm or 1400mm Square Bar* 2 Patented 1-Bee"Center Bracket 3 End Bracket(adjustable) "Both sizes FM and VDS approved. I Style AB8 © II:Flo • Hard-Lid Ceilings \A+ 1'• • Item Descrmtm S 1 700mm or 1400mm Square Bar" i 11111, 2 Patented 1 Bee"Center Bracket 3 End Bracket(adjustable) 'Both sizes FM/VdS approved- : y o Style AB9 • Hard-Lid ceilings with Hat furring channel ` 0 \� grid system AA' �\� Item Description 1 24"/610mm or 48'/1219mm Square Bar* 2 Patented 1-Bee"Center Bracket ^ 3 End Bracket for Hat Furring Channel V "Both sizes FM/VdS approved, i O , 3 Style AB10 1='� l `• Suspended ceilings � ;1\ • Armstrong®TechZone'" �� > Pi 0 �Iie perk% 0 • Item Description r� 1 1•1 • r! 1 6/152mm Square Bar* V " 2 Patented 1-BeeCenter Bracket t • 3 End Bracket •FM/VdS approved,cULus listed. 10.85 5839 Rev V Updated 11/2014 ®2014 Viclaulic Company.All rights reserved. �CtaU�rC" victaulic.com 9 48 CAMP PARSONS MATERIAL SUBMIT I AL JOB#1406073 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Braided Hose Assembly Suspended Ceiling Grid with Recessed Sprinkler -Clearances above ceiling tile at various center-line bend radii IIIHose Clearance Chart / R Dimension inches/mm ' see d,a Minimum Bend Radius R - 6/150 7/175 __.._ .. .... 4/100 ...._ 5/125 ' see cnr„ 3/80 Minimum A 1075/273 1175/298.51275/324 13.75/349 14.75/375 15.75/400; �� RlMSelessmnory waga i SlyIe ARI s 10.= Miert..._;=. 1=111i71.11 II lti le �.,.� rTO_I II V'/13m / 11 .. tall wl ��^ u j_n ym.(sa.� r";"I6e11 9916 9F IkkliI; dr6`s, ° ;� See nolej �a ,-,,,,n a :olimnface �we)1 one ti or rzl9 HIM nO lenlp, V2707411/19 MM MAX.RECESS V2707 Ye/19mm Max.Recess Suspended el In g Grid with 90°Elbow(Long) 7 ' , 1 BleEeaie,b'r Style PEI � Hose Clearance Chart l _._ I 111/ inches/ See Cnzil MME �O—. Dimension mm — • A Min. 8/200 ; N I — 13 mm a II — _ '=i6„ I mm ri r Note: Style A81 and Series AH2 figures shown. /,3m �' Ems■ �';� Variations of ceiling grids, sprinkler heads, brackets, pKxlcelRn00 d � �1�fG�+1�1 a 1 and hoses are permitted but may result in clearance see nme differences from the figures above. o,aifi101gmm on Cenlel V2707 34719mm Max.Recess 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. • victaulic.com 10 iCtaulic' 49 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 victaulic.com I Vic Flex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 411 Series AQB Braided Hose Assembly Suspended Ceiling Grid with Hat Furring Channel Hose Clearance Chart '- - — , .---- 7 Dimension inches/mm / Minimum Bend Radius R 2/50 ' 3/80 4/100 5/125 6/150 7/175 ' / See Man ■ \ Minimum"A" 10.3/262 11.3/287 12.3/313 13.3/338 !14.3/363.5 153/389 1 See Chart MN. SiOn .twm. gm, tlf qmP M[al! IMMEMIII 3 4/ 99 mrn ..-- I ■ 1 •'''''''''''',..ftalY 7.7-/ re-- --.--- I _I 11'..*■!- [ 11 V2708 1/2712.7mm Max.Recess 11110 Suspended Ceiling Grid with 90°Elbow(Short) 01113111•IL .• Hose Clearance Chart inches/ RIO' III Ism. Dimension mm 11.0■11W ii)i = r Amim■klimi ,,,, ,„ A . Min. 8/200 r,.=- .■.. 7 'N. See Wile \t/ = poilliii.'-----"°"..• I .0 Note: Style AB9 and Series AH2 figures shown. I—%' i lar—"ri ...,.—t, Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance - -- differences from the figures above. V3802 1/2712 7mm Max.Recess III 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 11 xictEaulie 50 UAMI'PARSONS MA I EHIAL SUHMI I I AL JOB#1406073 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Flexible Hose In-Plane Bend Characteristics ONE BEND TWO BENDS • 2X 2X Minimum Minimum Minimum bend radius bend radius ( bend radius Minimum -- bend radius I OR OR •\90° Minimum Minimum bend radius bend radius Minimum Minimum bend radius bend radius `\ Minimum I bend maids Note:For out-of-plane(three-dimensional)bends,care must be taken to avoid imparting torsional stress on the hose- Model Number Correlation AquaFlex4'Designation ,Li="1i."r.,_'1 -.—s� 'F.— . `, V III signati '',WQRN(N(i Designation Series AH4 Outlet Series AQB Series AFB Hose Size Hose Hose • It is the responsibility of the system designer Assembly inches Assembly Assembly to verify suitability of 300-series stainless steel AH4-31 -- 1/2 ..... AQB3IHLD AFB31HLD flexible hose for use with the intended fluid 44 AQB3ITLD AFB3ITLD AH4-36 '' _J AQB36HLD AFB36HLD media within the piping system and external ak AQB36TLD AFB36TLD environments. AH4-48 K I AQB48HLD AFB48HLD • The effect of chemical composition, pH level, _ r AQB48TLD AFB48TLD 'h AQ660HLD AF660HLD operating temperature, chloride level, oxygen AH4-60 _.. -- -.• -- level 44 AQB6OTLD AFB6OTLD , and flow rate on 300-SeYIQS stainless steel AH4-72 r---_- 1/2 AQB72HLD AFB72HLD flexible hose must be evaluated by the material 14 . AQB72TLD AFB72TLD specifier to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or property damage. ........._................. Installation ---- _--- - --- -- Note Reference should always be made to I-VICFLEX-ABI-AB2-AB10,I-VICFLEX-AB4-A9.9, I-VICFLEX-AB7,or 1-VICFI FX-AB8 for the product you are installing.Handbooks are This product in t installed shall c rdance with current ry nt Viet c or to Victaulic asseb instructions.tr All orsd ucts to included with each shipment of Victaulic products for complete installation and assembl Vi to installed ie the rdanco cha ge pr Victaulic installation/assembly cation , e s n ndar data,and arc available in PDF format on our website at www.victauhc.com. assembly equip lie equipment without the right to without product specifications designs and standard equipment withcui notice and witheut m<urrmg obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic and VicFlex are registered trademarks of Victaulic Company. 10.85 5839 Rev V Updated 11/2014 ®2014 Victaulic Company.All rights reserved. • victaulic.com 12 jCtauliC 51 mm CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • SECTION 2. 2 • FIRE SPRINKLERS S 52 CAMP PARSONS MATERIAL SUBMITTAL Vli 1418°g'1 11IL , u1 800-381-9312 • Technical Services I +1-401-781-8220 www.tyco-fire.com Series DS-3 Dry-Type Sprinklers 11.2K* Horizontal Sidewall, Extended Coverage, Standard Response General Owners are responsible for maintaining their fire protection system and devices Description in proper operating condition. The installing contractor or sprinkler menu- 1 f TYCO Series DS-3 Dry-Type Sprinklers, facturer should be contacted with any "e► 11.2K Horizontal Sidewall, Standard questions. r ;; Response, Extended Coverage, Series DS-3 Dry-Type Sprinklers must ` �^ N, Ordinary Hazard, are decorative glass only be installed in fittings that meet bulb automatic sprinklers. They are the requirements of the Design Criteria intended for use in applications where section. Installation of Series DS-3 -°_ the sprinklers and/or a portion of the Dry-Type Sprinklers in a recessed connecting piping may be exposed to installation will void all sprinkler warren- freezing temperatures; for example, ties,as well as void the sprinkler's labo- Finishes horizontal piping extensions through a ratoryapprovals. Sprinkler: Natural Brass, Chrome wall to protect an unheated area of a Plated,White Polyester building. Model/Sprinkler Escutcheon: White Coated or Chrome Series DS-3 Extended Coverage Plated, Brass Plated Ordinary Hazard Horizontal Sidewall, Identification Physical Characteristics Dry-Type Sprinklers are designed for Number (SIN) Inlet extended coverage use in ordinary Copper hazard occupancies(ECOH)per NFPA Plug Copper 13. TY5339 Yoke Stainless Steel • Series DS-3 Dry Type Sprinklers Technical Casing Galvanized provide protection of coverage areas up Carbon Steel to 16 ft.x 20 ft. (320 ft�as compared Data Insert Bronze to standard coverage horizontal Bulb Seat Bronze sidewall sprinklers having a m aximum Bulb coverage area of 10 ft.x 10 ft.(100 ft 2) Approvals Glass(3 mm) for ordinary hazard occupancies. UL and C-UL Listed Compression Screw Bronze Refer to Table A and the Design Criteria Deflector Bronze NOTICE Section. Frame Bronze Series DS-3 Dry-Type Sprinklers Guide Tube Stainless Steel Maximum Working Pressure described herein must be installed Water Tube Stainless Steel and maintained in compliance with this 175 psi(12,1 bar) document, as well as with the appli- Spring Stainless Steel cable standards of the National Fire Inlet Thread Connections Gasketed Spring Protection Association, in addition to 1-Inch NPT Plate Seal Beryllium Nickel the standards of any other Authorities (Standard) w/TEFLON Having Jurisdiction. Failure to do .so •ISO 7-RI Pin Stainless Steel may impair the performance of these (For information on ISO Inlet Thread Button Spring Stainless Steel devices. Connections, contact your Tyco Helper Spring Stainless Steel Sales Representative.) Escutcheon Carbon Steel Discharge Coefficient IMPORTANT Refer to Table B. Always refer to Technical Data Sheet TFP700 for the "INSTALLER Temperature Ratings WARNING"that provides cautions 155°F(68°C)and 200°F(93°C) with respect to handling and instal- lation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail • to operate in a fire situation or cause it to operate prematurely. •Refer to Table B for info on discharge coefficients. Page 1 of 8 SEPTEMBER 2011 TFP55O CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 2 of 8 • PLUG WITH YOKE PLUG CASING INSERT FRAME BULB DEFLECTOR GASKETED \ SPRING SPRING SEAL ) / ■ PLATE .eaq..a.�.4 — lill� -. � I f iii �____ aili 1 t \ / INLET WATER GUIDE BULB COMPRESSION INLET 1"NPT SPRING BAND TUBE TUBE SEAT SCREW FIGURE 1 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER TY5339(ECOH) — ASSEMBLY- SPRINKLER FINISH Temperature Bulb K-Factor K-Factor Rating Color Code Natural Chrome White LENGTH GPM/psit2 Brass Plated Polyester Inches(mm) (LPM/bar"2) 155°F(68°C) Red Listed by Underwriters Laboratories,Inc. 2-1/2 to 14-3/4 11.2 (maximum order length of 48 inches) (63 mm to 375 mm) (161,3) 200°F(93°C) Green Listed by Underwriters Laboratories for use in Canada 15 to 18-3/4 10.9 (maximum order length of 46 inches) (381 mm to 476 mm) (157,0) 19 to 23 10.8 TABLE A (483 mm to 584 mm) (155,5) SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS 23-1/4 to 26-3/4 10.7 III EXTENDED COVERAGE, ORDINARY HAZARD(TY5339) (591 mm to 679 mm) (154,1) — LABORATORY LISTINGS AND APPROVALS — 27-1/4 to 31-1/4 10.8 (692 mm to 794 mm) (152,6) Operation 31-1/2 to 35-1/4 10.5 (800 mm to 895 mm) (151,2) When TYCO Series DS-3 Dry-Type 35-1/2 to 39-1/2 10.4 Sprinklers are in service, water is (902 mm to 1003 mm) (149,8) prevented from entering the assembly by the Plug with Gasketed Spring 39-3/4 to 43-1/2 10.3 Seal Plate(Figure 1) in the Inlet of the (1010 mm to 1105 mm) (148,3) Sprinkler. 43-3/4 to 48 10.2 The glass bulb contains a fluid that (111 mm to 1219 mm) (146,9) expands when exposed to heat.When the rated temperature is reached, the Notes fluid expands sufficiently to shatter K-Factor Length is determined as follows: the glass bulb, and the Bulb Seat is • Flush:Order Length from Figure 2 plus released. 1/2 inch(12,7 mm) The compressed Spring is then able • Deeo:Order Length from Figure 4 plus to expand and push the Water Tube as 3-1/4 inch(82,6 mm) well as the Guide Tube outward.This • Without Escutcheon:Order Length from action simultaneously pulls inward on Figure 5 minus 2-1/4 inches(57,2 mm) the Yoke, withdrawing the Plug with Gasketed Spring Seal Plate from the TABLE B Inlet allowing the sprinkler to activate — DISCHARGE COEFFICIENTS - and flow water. • 54 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 3 of 8 • Coverage Top Of Application Areal W x L Minimum Flow2 Min Pressure2 Deflector-to-Ceiling Temperature Minimum Ft.x Ft. GPM(LPM) PSI(bar) Distance3, Rating°F(°C) Spacing° (m x m) Inches(mm) Ft.(m) 16 x 16 38(144) 11.5 Series DS-3(TY5339) (4,9 x 4,4) (0,79) Horizontal Sidewall 16 x 18 Dry-Type Sprinkler(ECOH) 4 9 x 5,5 43(163) 14.7 OH Group 1(0.15 gpm/sq.ft) ( ) (1,01) Standard Response 16 x 20 18.4 (4,9 x 6,1) 48(182) (1,27) 6 to 12 (150 to 300) 155,200 8 16 x 16 51 (193) 20.7 (68,93) (2,4) Series DS-3(TY5339) (4,9 x 4,4) (1,43) Horizontal Sidewall 16 x 16 Dry-Type Sprinkler(ECOH) (4,9 x 5,5) 58(220) 26.8 OH Group 2(0.20 gpm/sq.ft) (1,85) Standard Response 16 x 20 32,7 (4,9 x 6,1) 64(242) (2,25) Notes 1. Backwall(where sprinkler is located)by sidewall(length of throw). 2. Requirement is based on minimum flow in GPM from each sprinkler.The indicated residual pressures are based on the nominal K-Factor of 11.2. 3. The centerline of the sprinkler waterway is located below the deflector as shown in Figures 2,3,and 4. 4. Minimum spacing is for lateral distance between sprinklers located along a single wall.Otherwise adjacent sprinklers(that is,sidewall sprinklers on an adjacent wall,on an opposite wall,or pendent sprinklers)must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized, TABLE C SERIES DS-3 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS — UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA — • Temperatures for Heated Areal Ambient Temperature Exposed to Discharge End 40°F(4°C) I 50°F(10°C) I 60°F(16°C) of Sprinkler Minimum Exposed Barrel Length, Inches(mm)2 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE D EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS — MINIMUM RECOMMENDED LENGTHS — • 55 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 4 of 8 i Design ORDER LENGTHS: FACE OF Criteria 3"to 45-1/4"(76,2 to 1149,4 mm) MOUNTING IN 1/4"(6,4 mm)INCREMENTS SURFACE 2"*1/8" TYCO Series DS-3, Standard FACE OF (50,8:3,2 mm) Response, Extended Coverage SPRINKLER FITTING Ordinary Hazard, Horizontal Sidewall, 2-3/a°DIA. 9/16"(14,3 mm) Dry Type Sprinklers (ECOH) are for 1"NPT, (69,9 mm) \ use in ordinary hazard occupancies NOMINAL MAKE-IN `� with non-combustible unobstructed 9/1 s"(14.3 mm) construction and with a ceiling slope III ■'� , 3-11/16"DIA. not exceeding 2 inches per foot(9.2°), � I,'I'� ,, f (93,7Imm) using the design criteria provided U IIPj\ t in Table C, as well as any additional I 711 1 requirements specified in NFPA 13 for SPRINKLER FITTING Extended Coverage Sidewall Spray (REFER TO DESIGN CENTERLINE CRITERIA SECTION) OF WATERWAY Sprinklers. A 36-inch (914 mm) clearance must FIGURE 2 be maintained between the top of the SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER sprinkler deflector and any miscella- WITH FLUSH ESCUTCHEON(TY5339) neous storage. Series DS-3 Dry Type Sprinklers may be installed on sloped ceilings in loading docks with a maximum roof slope of 4 inches per foot (18.4°) as ORDER LENGTHS:t1117 FAUN IN shown in Figure 8 and using the design 1"/4 (6,4(25m to INCREMENTS NT MOUNTING criteria provided in Table C. IN 1/4"(6,4 mm)INCREMENTS SURFACE 4_1/8"±3/8" FACE OF (104,8±9,5 mm) Sprinkler Fittings Install 1-Inch NPT Series DS-3 SPRINKLER FITTING 2.3/4"DIA. 9/16"(14,3 mm) Dry Type Sprinklers in the 1-Inch NPT f 1"NPT, (69,9 mm) \\ outlet or run of the following fittings: NOMINAL MAKE-IN \� +I • 9/16"(14,3 mm) Rill •malleable or ductile iron threaded 3-1/2" I DIA. tee fittings that meet the dimen- �INI sional requirements of ANSI B16.3 I��IN��ull�l� ,�"" (88,9 mm) (Class 150) ---.. L� ` f •cast iron threaded tee fittings that SPRINKLER FITTING -- _--_ --"-"- meet the dimensional requirements (REFER TO DESIGN CENTERLINE of ANSI B16.4(Class 125). CRITERIA SECTION) OF WATERWAY Do not install Series DS-3 Dry Type Sprinklers into elbow fittings.The Inlet of the sprinkler can contact the interior FIGURE 3 of the elbow. SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER The unused outlet of the threaded tee is WITH DEEP ESCUTCHEON(TY5339) plugged as shown in Figure 6. Series DS-3 Dry-Type Sprinklers can also be installed in the 1-Inch NPT ORDER LENGTHS: outlet of a GRINNELL Figure 730 ----- ---5-1/4"to 48"(133,4 to 1219,2 mm) Mechanical Tee. However, the use of IN 1/4"(6,4 mm)INCREMENTS MINIMUM the Figure 730 Tee for this arrangement 2-1/4"(57,2 mm) is limited to wet pipe systems. FACE OF SPRINKLER FITTING DEFLECTOR TO MOUNTING The configuration shown in Figure 7 is 1"NPT, SURFACE only applicable for wet pipe systems NOMINAL MAKE-IN where the sprinkler fitting and water- 9/16"(14,3 mm) i + filled pipe above the sprinkler fitting are not subject to freezing and where the , IIN � u length of the Dry Type Sprinkler has the �NII� �' minimum exposure length depicted in 9/16' Figure 10.Refer to the Exposure Length (14,3 mm) section. SPRINKLER FITTING (REFER TO DESIGN CENTERLINE CRITERIA SECTION) OF WATERWAY • FIGURE 4 SERIES DS-3 ECOH THO HORIZONTAL ESCUTCHEON DRY-TYPE YPE SPRINKLER WI I 56 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 5of8 o TO DRY li NOTICE • SYSTEM �\ Do not install Series DS-3 Dry-Type kilit --- MAXIMUM Sprinkler into any other type fitting THROW without first consulting the Technical Services Department.Failure to use the O L S appropriate fitting may result in one of the following: ", •Failure of the sprinkler to operate prop- INTENDED DSB 2 erly due to formation of ice over the FOR FREEZER s"(152,4 mm) T Inlet Plug or binding of the Inlet Plug. STRUCTURES "e TO 12"(304,8 mm) •Insufficient engagement CEILING TO TOP 4/12 g gemegt n the Inlet AREA OF SPRINKLER SLOPE pipe-threads with copse consequent leakage. SUBJECT ri. DEFLECTOR MAXIMUM :i Drainage TO DISTANCE In accordance with the minimum FREEZING FIGURE 8 requirements of the National Fire SPRINKLER PLACEMENT Protection Association for dry pipe UNDER SLOPED CEILINGS sprinkler systems, branch,cross,and FIGURE 5 IN LOADING DOCKS feed-main piping connected to Dry SPRINKLER FITTING Sprinklers and subject to freezing — UNHEATED AREA — temperatures must be pitched for 2-3/4"DIA. proper drainage. (69,9 mm) DSB-2 q CLEARANCE Exposure Length INSULATED RUN INTENDED HOLE FREEZER When using Dry Sprinklers in wet pipe OUTLET FOR FREEZER ADHESIVE systems to protect areas STRUCTURE PLUGGED STRUCTURES subject to freezing temperatures, use DSB-2\ i Table D to determine a sprinkler's 1 BOOT =r� s appropriate exposed barrel length_ \ Z� �! to prevent water from freezing in the ll I',II� connecting SPRINKLER g pipes due to conduction. FITTING 1 '►-. The exposed barrel length measure- (SEE DESIGN ment must be taken from the face of • CRITERIA i , the sprinkler fitting to the surface of the SECTION) � Z structure or insulation that is exposed TO DRY to the heated area.Refer to Figure 7 for an example. SYSTEM STRAP TIES AREA (ENDS ON DS-3 For protected area temperatures SUBJECT OPPOSING SHOWN between those given above, the SIDES OF WITH FLUSH minimum recommended length from TO BOOT) ESCUTCHEON the face of the fitting to the outside of FREEZING ,■ the protected area may be determined FIGURE 6 FIGURE 9 by interpolating between the indicated SPRINKLER FITTING MODEL DSB-2 DRY SPRINKLER values. — UNHEATED AREA — BOOT WITH SERIES DS-3 Clearance Space PENDENT SPRINKLER pace In accordance with Section 8.4.9.2 EXPOSURE of the 2010 edition of NFPA 13, when LENGTH For wet pipe system installations of connecting an area subject to freezing (SEE DESIGN 1-Inch NPT Series DS-3 Dry-Type and an area containing a wet pipe CRITERIA SECTION) Sprinklers connected to CPVC piping, sprinkler system,the clearance space use only the following TYCO CPVC around the sprinkler barrel of Dry-Type FACE OF fittings: Sprinklers must be sealed. Due to SPRINKLER temperature differences between two FITTING •1" x 1" NPT Female Adapter (P/N areas, the potential for the formation 80145) of condensation in the sprinkler and ill I •1" x 1" x 1" NPT Sprinkler Head subsequent ice build-up is increased.If Adapter Tee(P/N 80249). this condensation is not controlled, ice DSB-2 For dry pipe system installations, use build-up can occur that might damage INTENDED only the side outlet of maximum 2-1/2- the dry-type sprinkler and/or prevent•FOR FREEZER o inch reducing tee when locating Series proper operation in a fire situation. STRUCTURES • DS-3 Dry-Type Sprinklers directly Use of the Model DSB-2 Dry Sprinkler below the branch line.Otherwise, use Boot,described in technical data sheet HEATED � the configuration shown in Figure 6 to TFP591 and shown in Figure 9, can 11, assure complete water drainage from provide the recommended seal. above Series DS-3 Dry-Type Sprinklers • FIGURE 7 and the branch line. Failure to do so SPRINKLER FITTING may result in pipe freezing and water — HEATED AREA — damage. 57 CAMP PARSONS MATERIAL SUBMITTAL TFPSSO JOB#1406073 Page 6 of 8 • Do not install any bulb-type sprinkler if Care and the bulb is cracked or there is a loss of liquid from the bulb.With the sprinkler Maintenance held horizontally, a small air bubble should be present.The diameter of the TYCO Series DS-3 Dry Type Sprinklers air bubble is approximately 1/16 inch must be maintained and serviced 40 1 (1,6 mm)for the 135°F(57°C)rating to in accordance with the following 1/8 inch(3,2 mm)for the 360°F(182°C) instructions. rating. Obtain a leak-tight 1-Inch NPT sprinkler NOTICE CI joint by applying a minimum-to- Before closing a fire protection system DO NOT maximum torque of 20 to 30 ft. lbs. main control valve for maintenance (26,8 to 40,2 Nm). Higher levels of work on the fire protection system torque may distort the sprinkler Inlet that it controls, obtain permission to with consequent leakage or impairment shut down the affected fire protection of the sprinkler. systems from the proper authorities FIGURE 10 Do not attempt to compensate and notify all personnel who may be — DO NOT GRASP DEFLECTOR— for insufficient adjustment in an affected by this action. Escutcheon Plate by under or over- Absence of the outer piece of an tightening the Sprinkler. Re-adjust the escutcheon, which is used to cover a WRENCH FLAT position of the sprinkler fitting to suit. clearance hole, may delay the time to � ENGAGEMENT 1. Install horizontal sidewall sprinklers sprinkler operation in a fire situation. ..., AREA with the center line of waterway A Vent Hole is provided in the Bulb Seat ' parallel to the ceiling and perpen- (Figure 1)to indicate if the Dry Sprinkler WRENCH dicular to the back wall surface.The is remaining dry. Evidence of leakage FLATS word "TOP" on the deflector must from the Vent Hole indicates potential� face upwards toward the ceiling. leakage past the Inlet seal and the need i`�7 2. With a non-hardening pipe-thread to remove the sprinkler to determine ��G`A sealant such as TEFLON applied to the cause of leakage;for example, an the Inlet threads, hand-tighten the improper installation or an ice plug. sprinkler into the sprinkler fitting. Close the fire protection system control • APPLY Do not grasp the sprinkler by the valve and drain the system before WRENCH AS deflector(Figure 10). removing the sprinkler. SHOWN 3. Wrench-tighten the sprinkler using Exercise care to avoid damage before, either: during, and after installation. Never FIGURE 11 • a pipe wrench on the Inlet Band or paint, plate, coat, or otherwise alter W-TYPE 8 SPRINKLER WRENCH the Casing(Figure 1). the factory. efactoc sprinklers after they leave ry. • the W-Type 8 Sprinkler Wrench on Non-factory applied paint can Installation the Wrench Flat(Figure 11). adversely delay or prevent sprinkler Apply the Wrench Recess of the operation in the event of a fire. Series DS-3 Dry-Type Sprinklers must W-Type 8 Sprinkler Wrench to the Replace sprinklers that: be installed in accordance with the Wrench Flat. following instructions. •were damaged by dropping,striking, Note:If sprinkler removal becomes wrench twisting,wrench slippage,or NOTICE necessary, remove the sprinkler the like. using the same wrenching method Series DS-3 Dry-Type Sprinklers must noted above. Sprinkler removal •were modified or over-heated. only be installed in fittings that meet is easier when a non-hardening •have cracked bulbs or have lost liquid the requirements of the Design Criteria sealant was used and torque guide- from the bulbs.Refer to the Installation section. Refer to the Design Criteria lines were followed. After removal, Section in this data sheet. section for other important require- inspect the sprinkler for damage. ments regarding piping design and •are leaking or exhibiting visible signs sealing of the clearance space around 4. After applying a wall finish, slide on of corrosion. the Sprinkler Casing. With reference to the outer piece of the Escutcheon Figure 10, do not grasp the sprinkler until it comes in contact with the by the deflector. Failure to follow this mounting surface. instruction may impair performance of For Deep Escutcheons, slide the the device. outer skirt over the inner cup to make firm contact with the mounting surface. • 58 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFPSSO Page 7 of 8 Responsibility lies with owners for the Limited • inspection,testing,and maintenance of Ordering their fire protection system and devices Warranty Procedure in compliance with this document,as well as with the applicable standards of Products manufactured by Tyco Contact your local distributor for avail- the National Fire Protection Association Fire Protection Products (TFPP) are ability.When placing an order,indicate (for example, NFPA 25), in addition to warranted solely to the original Buyer the f g full product name, including the standards of any other Authorities for ten 10 Having Jurisdiction. The installing ( ) years against defects description and Part Number(P/N). contractor or sprinkler manufacturer in material and Overly installed when ( ) should be contacted relative to any paid for and properly installed and Dry Sprinklers questions. maintained under normal use and When ordering 11.2 K-Factor Series service. This warranty will expire DS-3 Horizontal Sidewall Dry-Type Automatic sprinkler systems are recom- ten (10) years from date of shipment Sprinklers, specify the following mended to be inspected, tested, and by TFPP. No warranty is given for information: maintained by a qualified Inspection products or components manufac- •Model/SIN TY5339 Service in accordance with local tured by companies not affiliated by requirements and/or national codes. ownership with TFPP or for products •Order Length and components which have been Dry-Type Sprinklers are furnished subject to misuse, improper instal- based upon Order Length as lation, corrosion, or which have not measured from the face of the been installed, maintained, modified wall to the face of the sprinkler or repaired in accordance with appli- fitting (Figure 2, 3, and 4).After the cable Standards of the National Fire measurement is taken, round it to Protection Association, and/or the the nearest 1/4 inch increment. standards of any other Authorities •Inlet Thread Connections Having Jurisdiction. Materials found 1-Inch NPT or 7-R1 by TFPP to be defective shall be either repaired or replaced, at TFPP's sole •Temperature Rating option. TFPP neither assumes, nor •Sprinkler Finish authorizes any person to assume for it, any other obligation in connection •Escutcheon Type with the sale of products or parts of •Part Number from Table E. products. TFPP shall not be respon- sible for sprinkler system design errors Sprinkler Wrench • or inaccurate or incomplete infor- Specify W-Type 8 Sprinkler Wrench, mation supplied by Buyer or Buyer's P/N 56-010-4-118. representatives. In no event shall TFPP be liable, in Sprinkler Boot contract, tort, strict liability or under Specify Model DSB-2 Dry Sprinkler any other legal theory, for incidental, Boot,Number 63-000-e Boo. This Pap indirect, special or consequential Ties,and includes/3 one Boot,two(quantity damages, including but not limited to Ties,hes 1/3 oz. ffAdhtfor (sanity labor charges, regardless of whether of Boot)ve is sufficient for installing TFPP was informed about the possi- bility one Boot). of such damages,and in no event shall TFPP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties.express or implied, including warranties of merchantability and fitness for a partic- ular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components,whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part,of any portion of this warranty will not affect the remainder. • 59 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 8 of 8 • P/N" 61 - XXX - X - XXX SPRINKLER ESCUTCHEON FINISH FINISH(1) MODEL/SIN 1 NATURAL BRASS BRASS PLATED 161 Flush Escutcheon TY5339 (1"NPT),155°F(68°C) 4 WHITE POLYESTER WHITE COATED 163 Flush Escutcheon TY5339 (1"NPT),Escutcheon (93°C) g CHROME PLATED CHROME PLATED 17t Deep Escutcheon TY5339 (1"NPT),155°F(68°C) 0 CHROME PLATED WHITE COATED 173 Deep Escutcheon TY5339 (1"NPT),200°F(93°C) 151 Without Escutcheon TY5339 (1"NPT),155°F(68°C) ORDER 153 Without Escutcheon TY5339 LENGTH(2) (1"NPT),200°F(93°C) 055 5.50" 082 8.25" Notes Use Prefix"I"for ISO 7-R1 Connection;for example,1-61-161-1-055. 1. Does not apply to assemblies without escutcheon. 180 18.00" 2. Dry-Type Sprinklers are furnished based upon"Order Length"as measured per Figures 2,3,and 4.After the measurement is taken,round it to the nearest 1/4 Inch 187 18.75" increment. 372 37.25" • 480 46.00" TABLE E SERIES DS-3 HORIZONTAL SIDEWALL, DRY-TYPE SPRINKLERS(ECOH) — PART NUMBER SELECTION — • Copyright®2011 Tyco Fire Protection Products.All rights reserved. 't(�C[� TEFLON is trademark of The DuPont Corporation. 60 CAMP PARSONS MATERIAL SUBMITTAL 'OR 4141Y9' • 11Ittu 'I 800-381-9312 Technical Services +1-401-781-8220 www. 00-3 ire.co 2 Series DS-3 Dry-Type Sprinklers 11.2K* Horizontal Sidewall, Extended Coverage, Standard Response General Owners are responsible for maintaining their fire protection system and devices in proper operating condition. The „- r Description installing contractor or sprinkler manu- facturer should be contacted with any TYCO Series DS-3 Dry-Type Sprinklers, questions. 11.2K Horizontal Sidewall, Standard s Response, Extended Coverage, Series DS-3 Dry-Type Sprinklers must Ordinary Hazard, are decorative glass only be installed in fittings that meet bulb automatic sprinklers. They are the requirements of the Design Criteria intended for use in applications where section. Installation of Series DS-3 the sprinklers and/or a portion of the Dry-Type Sprinklers in a recessed installation will void all sprinkler warren- connecting piping may be exposed to ties,as well as void the sprinkler's labo- Finishes freezing temperatures; for example, ratory approvals. Sprinkler: Natural Brass, Chrome horizontal piping extensions through a Plated,White Polyester wall protect an unheated area of a Model/Sprinkler Escutcheon:White Coated or Chrome building. p Plated, Brass Plated Series DS-3 Extended Coverage Ordinary Hazard Horizontal Sidewall, Identification Physical Characteristics Inlet Copper Dry-Type Sprinklers are designed for Number (SIN) Co • extended coverage use in ordinary Plug Copper hazard occupancies(ECOH)per NFPA TY5339 Yoke Stainless Steel 13. Casing Galvanized Series DS-3 Dry Type Sprinklers Technical Carbon Steel provide protection of coverage areas up to 16 ft.x 20 ft.(320 ft2)as compared Data Insert Bronze Bulb Seat Bronze to standard coverage horizontal Bulb Glass(3 mm) sidewall sprinklers having a maximum ro Appvals coverage area of 10 ft.x 10 ft. (100 ft2) UL C-UL Listed Compression Screw Bronze for ordinary hazard occupancies. Deflector Bronze Refer to Table A and the Design Criteria Frame Bronze NOTICE Section. Guide Tube Stainless Steel Series DS-3 Dry-Type Sprinklers Maximum Working Pressure Water Tube Stainless Steel described herein must be installed 175 psi(12,1 bar) Spring Stainless Steel and maintained in compliance with this document, as well as with the appli- Inlet Thread Connections Gasketed Spring cable standards of the National Fire .1-Inch NPT Plate Seal Beryllium Nickel Protection Association, in addition to (Standard) w/TEFLON the standards of any other Authorities Having Jurisdiction. Failure to do so •ISO 7-R1 Pin Stainless Steel may impair the performance of these (For information on ISO Inlet Thread Button Spring Stainless Steel devices. Connections, contact your Tyco Helper Spring Stainless Steel Sales Representative.) Escutcheon Carbon Steel Discharge Coefficient IMPORTANT Refer to Table B. Always refer to Technical Data Temperature Ratings Sheet TFP700 for the "INSTALLER Te prat and Ratings 93°C WARNING"that provides cautions (68°C) ((93°C) with respect to handling and instal- lation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its compo- • nents and cause the sprinkler to fail to operate in a tire situation or cause it to operate prematurely. ^Refer to Table 8 for info on discharge coefficients. Page 1 of 8 SEPTEM@IER 2011 TFP550 • CAMP PARSONS MATERIAL SUBMITTAL TFP55O JOB#1406073 Page 2 of 8 • PLUG WITH YOKE PLUG CASING INSERT FRAME BULB DEFLECTOR GASKETED ' SPRING SPRING SEAL PLATE / I ( �'=■ ii ! ---\\_ I INLET WATER GUIDE BULB COMPRESSION INLET 1'NPT SPRING BAND TUBE TUBE SEAT SCREW FIGURE 1 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER TY5339(ECOH) —ASSEMBLY— Temperature Bulb SPRINKLER FINISH K-Factor Rating Color Code Natural Chrome I White LENGTH GPM/ps�r2 Brass Plated Polyester Inches(mm) (LPM/baru2) 155°F(68°C) Red Listed by Underwriters Laboratories,Inc. (maximum order length of 48 inches) 2-1/2 to 14-3/4 11.2 (63 mm to 375 mm) (161,3) 200°F(93°C) Green Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 inches) 15 to 18-3/4 10,9 (381 mm to 476 mm) (157,0) TABLE A 19 to 23 10.8 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS (483 mm to 584 mm) (155,5) EXTENDED COVERAGE,ORDINARY HAZARD(TY5339) 23-1/4 to 26-3/4 10.7 • — LABORATORY LISTINGS AND APPROVALS— (591 mm to 679 mm) (154,1) 27-1/4 to 31-1/4 10.6 Operation (692 mm to 794 mm) (152,6) 31-1/2 to 35-1/4 10.5 When TYCO Series DS-3 Dry-Type (800 mm to 895 mm) (151,2) Sprinklers are in service, water is 35-1/2 to 39-1/2 10.4 prevented from entering the assembly (902 mm to 1003 mm) (149,8) by the Plug with Gasketed Spring 39-3/4 to 43-1/2 10.3 Seal Plate(Figure 1)in the Inlet of the 0010 mm to 1105 mm) (148,3) Sprinkler. The glass bulb contains a fluid that 43-3/4 to 48 10.2 ands when exposed (111 mm to 1219 mm) (146,9) expands posed to heat.When the rated temperature is reached,the Notes fluid expands sufficiently to shatter K-Factor Length is determined as follows: the glass bulb, and the Bulb Seat is released. • Flush:Order Length from Figure 2 plus The compressed Spring is then able to inch rder eng to expand and push the Water Tube as ▪ Deep:Order Length from Figure 4 plus well as the Guide Tube outward.This 3-1/4 inch(82,6 mm) action simultaneously pulls inward on • Without Escutcheon:Order Length from Figures minus 2-1 the Yoke, withdrawing the Plug With 2-1/4 inches(57,2 mm) Gasketed Spring Seal Plate from the Inlet allowing the sprinkler to activate TABLE B and flow water. —DISCHARGE COEFFICIENTS— • 63 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFPSSG Page 3 of 8 • Coverage Top Of Minimum Areal W x L Minimum Flow2 Min Pressure2 Deflector-to-Ceiling Temperature Spacing° Application Ft.x Ft. GPM(LPM) PSI(bar) Distance3• Rating°F(°C► Ft.(m)? (m x m) Inches(mm) 16x16 38(144) 11.5 Series DS-3(TY5339) (4,9 x 4,4) (00,7979 ) Horizontal Sidewall 16 x 18 43(163) 14.7 Dry-Type Sprinkler(ECOH) (4,9 x 5,5) (1,01) OH Group 1(0.15 gpm/sq.ft) Standard Response 16 x 20 46(162) 18.4 6 to 12 8 (4,9 x 6,1) (1,27) (150 to 300) 155,93) ( 4) 16 x 16 51 (193) 20.7 Series DS-3(TY5339) (4,9 x 4,4) (1,43) Horizontal Sidewall 16 x 18 58(220) 26.8 Dry-Type Sprinkler(ECOH) (49 x 5,5) (1,65) OH Group 2(0.20 gpm/sq.ft) , Standard Response 16 x 20 64(242) 32.7 (4,9 x 6,1) (2,25)Notes 1. Rockwall(where sprinkler is located)by sidewall(length of throw). 2. Requirement is based on minimum flow in GPM from each sprinkler.The indicated residual pressures are based on the nominal K-Factor of 11.2. 3. The centerline of the sprinkler waterway is located below the deflector as shown in Figures 2,3,and 4. 4. Minimum spacing is for lateral distance between sprinklers located along a single wall.Otherwise adjacent sprinklers(that is,sidewall sprinklers on an adjacent wall, on an opposite wall,or pendent sprinklers)must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized. TABLE C SERIES DS-3 UL AND C-UL COVERAGE ISTING COVERAGE AND FLOW RATE DRY-TYPE SPRINKLERS • Temperatures for Heated Area Ambient Temperature 50°F(10°C) 60°F(16°C) Exposed to Discharge End 40°F(4°C) 0 0 4(100) 8(200) 12(305) 14(355) 14(355) 16(405) 18(455) 20(510) of Sprinkler Minimum Exposed Barrel Length, Inches(mm)2 0 0 0 1 (25) 3(76) 4(100) 6(150) 8(200) 8(200) 10(255) 40°F(4°C) 0 30°F(-1°C) 0 20°F(-7°C) 0 0 0 1 (25) 3(75) 4(100) 4(100) 6(150) 6(150) 10°F(-12°C) 0°F(-18°C) -10°F(-23°C) -20°F(-29°C) -30°F(-34°C) -40°F(-40°C) -50°F(-46°C) -60°F(-51°C) 20(510) 10(255) Notes 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE D EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS • — MINIMUM RECOMMENDED LENGTHS - 64 CAMP PARSONS MATERIAL SUBMITTAL TFP55O JOB#1406073 Page 4 of 8 • ORDER LENGTHS: FACE OF Design 3"to 45-1/4"(76,2 10 1149,4 mm) MOUNTING Criteria IN 1/4"(6,4 mm)INCREMENTS — SURFACE 2'±1/8" TYCO Series DS-3, Standard FACE OF (50,8±3,2 mm) Response, Extended Coverage SPRINKLER FITTING Ordinary Hazard, Horizontal Sidewall, 1"NPT, 2-3/4"DIA. p 9/16'(14,3 mm) Y NOMINAL MAKE-IN (69,9 mm) P� Dry Type Sprinklers (ECOH) are for 9/16'(14,3 mm) } use in ordinary hazard occupancies with non-combustible unobstructed IIB I ' 3-11/16"DIA. construction and with a ceiling slope not exceedin 2 inches er foot 9 2°), (93,7 mm) 9 p ( . using the design criteria provided + in Table C, as well as any additional SPRINKLER FITTING Nil (REFER TO DESIGN requirements specified in NFPA 13 for CRITERIA SECTION) CENTERLINE Extended Coverage Sidewall Spray OF WATERWAY Sprinklers. A 36-inch (914 mm) clearance must FIGURE 2 be maintained between the top of the SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER sprinkler deflector and any miscella- WITH FLUSH ESCUTCHEON(TY5339) neous storage. Series DS-3 Dry-Type Sprinklers may be installed on sloped ceilings in loading docks with a maximum roof ORDER LENGTHS: FACE OF slope of 4 inches per foot (18.4°) as 1"to 44"(25,410 1117,6 mm) MOUNTING shown in Figure 8 and using the design IN 1/4"(6,4 mm)INCREMENTS SURFACE criteria provided in Table C. 4-1/8"±3/8° FACE OF (104,8±9,5 mm) Sprinkler Fittings SPRINKLER FITTING p_y4"DIA. Install 1-Inch NPT Series DS-3 1"NPT, 9/16"(14,3 mm) NOMINAL MAKE-IN (69,9 mm) \ Dry Type Sprinklers in the 1-Inch NPT sns"(14,3 mm) \ I outlet or run of the following fittings: • rj •malleable or ductile iron threaded �11111111110 ��� tee fittings that meet the dimen- �� f deg g mm) sional requirements of ANSI B16.3 `� (Class 150) SPRINKLER FITTING _ ! ••cast iron threaded tee fittings that (REFER E DESIGN CENTERLINE meet the dimensional requirements CRITERIA SECTION) OF WATERWAY of ANSI 816.4(Class 125). Do not install Series DS-3 Dry-Type Sprinklers into elbow fittings.The Inlet FIGURE 3 of the sprinkler can contact the interior SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER of the elbow. WITH DEEP ESCUTCHEON(TY5339) The unused outlet of the threaded tee is plugged as shown in Figure 6. Series DS-3 Dry-Type Sprinklers can ORDER LENGTHS: also be installed in the 1-Inch NPT 5-1/4"to 48"(133,4 to 1219,2 mm)— _ outlet of a GRINNELL Figure 730 IN 1/4"(6,4 mm)INCREMENTS Mechanical Tee. However, the use of MINIMUM the Figure 730 Tee for this arrangement- FACE OF SPRINKLER FITTING 2-1/4"(57,2 mm) is limited to wet pipe systems. DEFLECTOR TO 1'NPT, MOUNTING The configuration shown in Figure 7 is NOMINAL MAKE-IN SURFACE only applicable for wet pipe systems 9/16"(14,3 mm) where the sprinkler fitting and water- filled pipe above the sprinkler fitting are not subject to freezing and where the 1111 length of the Dry-Type Sprinkler has the 9/16" Figu10.RefertortheeExposurel in e Length SPRINKLER FITTING (14,3 mm) section. (REFER TO DESIGN CENTERLINE CRITERIA SECTION) OF WATERWAY FIGURE 4 • SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER WITHOUT ESCUTCHEON(TY5339) 65 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 5 of 8 • NOTICE ,ii TO DRY Do not install Series DS-3 Dry-Type SYSTEM `�__ Sprinkler into any other type fitting MAXIMUM without first consulting the Technical THROW Services Department.Failure to use the O a,,, -----1 appropriate fitting may result in one of the following: •Failure of the sprinkler to operate prop- DSB-2 kilit 5 -I' ' ..,,,,i erly due to formation of ice over the INTENDED 6"(152,4 mm) <j Inlet Plug or binding of the Inlet Plug. FOR FREEZER �'' T111.2;4(030_4,6 mm) \ •Insufficient engagement of the Inlet STRUCTURES , y O TOP 4/12 pipe threads with consequent leakage. s OF SPRINKLER SLOPE AREA DEFLECTOR MAXIMUM Drainage SUBJECT VIII .:'' DISTANCE In accordance with the minimum TO requirements of the National Fire FREEZING FIGURE 8 Protection Association for dry pipe I SPRINKLER PLACEMENT sprinkler systems, branch,cross,and UNDER SLOPED CEILINGS feed-main piping connected to Dry FIGURE 5 IN LOADING DOCKS Sprinklers and subject to freezing SPRINKLER FITTING temperatures must be pitched for — UNHEATED AREA — proper drainage. 2-3/4"DIA. (69,9 mm) Exposure Length DSB-2 C CLEARANCE INSULATED When using Dry Sprinklers in wet pipe RUN INTENDED 1 HOLE FREEZER sprinkler systems to protect areas OUTLET FOR FREEZER ip ADHESIVE STRUCTURE subject to freezing temperatures, use PLUGGED STRUCTURES @ Table D to determine a sprinkler's _ DSB-z i to appropriate exposed barrel length Ef BOOT to prevent water from freezing in the connecting pipes due to conduction. rt SPRINKLER The exposed barrel length measure- j FITTING �� I�1 meet must be taken from the face of • (SEE DESIGN the sprinkler fitting to the surface of the O CRITERIA _ ) structure or insulation that is exposed SECTION) / to the heated area.Refer to Figure 7 for TO DRY an example. SYSTEM STRAP TIES DS-3 For protected area temperatures LW (ENDS ON SHOWN between those given above, the AREA OPPOSING WITH FLUSH minimum recommended length from SUBJECT SIDES OF ESCUTCHEON the face of the fitting to the outside of TO BOOT) the protected area may be determined FREEZING FIGURE 9 by interpolating between the indicated FIGURE 6 MODEL DSB-2 DRY SPRINKLER values. SPRINKLER FITTING BOOT WITH SERIES DS-3 Clearance Space — UNHEATED AREA — DRY-TYPE PENDENT SPRINKLER In accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13,when EXPOSURE connecting an area subject to freezing LENGTH For wet pipe system installations of and an area containing a wet pipe ~(SEE DESIGN 1-Inch NPT Series DS 3 Dry Type sprinkler system,the clearance space CRITERIA SECTION) Sprinklers connected to CPVC piping, around the sprinkler barrel of Dry-Type use only the following TYCO CPVC Sprinklers must be sealed. Due to FACE OF fittings: temperature differences between two SPRINKLER •1" x 1" NPT Female Adapter (P/N areas, the potential for the formation FITTING 80145) of condensation in the sprinkler and I� •1" x 1" x 1" NPT Sprinkler Head subsequent ice build-up is increased.If it Adapter Tee(P/N 80249). this condensation is not controlled,ice build-up can occur that might damage DSB-z/ MIF For dry pipe system installations, use the dry-type sprinkler and/or prevent INTENDED only the side outlet of maximum 2-1/2- proper operation in a fire situation. FOR FREEZER inch reducing tee when locating Series Use of the Model DSB-2 Dry Sprinkler STRUCTURES DS-3 Dry Type Sprinklers directly Boot,described Model technical data sheet below the branch line.Otherwise, use Boot,described and shown in Figure 9, can HEATED the configuration shown in Figure 6 to provide the recommended seal. AREA assure com lete water drains a from above Series DS-3 Dry-Type Sprinklers • FIGURE 7 and the branch line. Failure to do so SPRINKLER FITTING may result in pipe freezing and water —HEATED AREA — damage. 66 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 6 of 8 Do not install any bulb-type sprinkler if Care and • the bulb is cracked or there is a loss of liquid from the bulb.With the sprinkler Maintenance ,IP' held horizontally, a small air bubble C should be present.The diameter of the TYCO Series DS-3 Dry-Type Sprinklers v1„, air bubble is approximately 1/16 inch (1,6 mm)for the 135°F(57°C)rating to must or ancet with and following �� 1/8 inch(3,2 mm)for the 360°F(182°C) in accordance with the following CI rating. instructions. Obtain a leak-tight 1-Inch NPT sprinkler NOTICE joint by applying a minimum-to- DO NOT maximum torque of 20 to 30 ft. lbs. Before closing a fire protection system (26,8 to 40,2 Nm). Higher levels of main control valve for maintenance torque may distort the sprinkler Inlet work on the fire protection system with consequent leakage or impairment that it controls, obtain permission to of the sprinkler. shut down the affected fire protection FIGURE 10 Do not attempt to compensate systems d notify all personnel ewho authorities FIGURE —DO NOT GRASP DEFLECTOR — for insufficient adjustment in an affected by this action. Escutcheon Plate by under or over- Absence of the outer piece of an WRENCH FLAT tightening the Sprinkler. Re-adjust the p position of the sprinkler fitting to suit. escutcheon, which is used to cover a rj-!K. ENGAGEMENT clearance hole, may delay the time to / � _ AREA 1. Install horizontal sidewall sprinklers sprinkler operation in a fire situation. with the center line of waterway A Vent Hole is provided in the Bulb Seat WRENCH I parallel to the ceiling and perpen- FLq �� dicular to the back wall surface.The (Figure 1)to indicate if the Dry Sprinkler word °TOP" on the deflector must is remaining dry. Evidence of leakage face upwards toward the ceiling. from the Vent Hole indicates potential leakage past the Inlet seal and the need �" % 2. With anon-hardening pipe-thread to remove the sprinkler to determine sealant such as TEFLON applied to the cause of leakage;for example,an the Inlet threads, hand-tighten the improper installation or an ice plug. APPLY sprinkler into the sprinkler fitting. Close the fire protection system control WRENCH AS ure 10) Do not grasp the sprinkler by the valve and drain the system before • SHOWN deflector(Fig . removing the sprinkler. 3. Wrench-tighten the sprinkler using Exercise care to avoid damage before, either: during, and after installation. Never FIGURE 11 • a pipe paint, plate, coat, or otherwise alter W-TYPE 8 SPRINKLER WRENCH P Pe wrench on the Inlet Band or automatic sprinklers the Casing(Figure 1). p 'nklers after they leave the factory. • the W-Type 8 Sprinkler Wrench on Installation the Wrench Flat(Figure 11). Non-factory applied paint can adversely delay or prevent sprinkler Series DS-3 Dry-Type Sprinklers must Apply the Wrench Recess of the operation in the event of a fire. be installed in accordance with the W-Type 8 Sprinkler Wrench to the following instructions. Wrench Flat. Replace sprinklers that: Note:If sprinkler removal becomes were damaged by dropping,striking, NOTICE necessary, remove the sprinkler wrench twisting,wrench slippage,or using the same wrenching method the like. Series DS-3 Dry-Type Sprinklers must noted above. Sprinkler removal •were modified or over-heated.en a only be installed in fittings gat meet sealant was hsed and torque guide •have cracked bulbs or have lost liquid the requirements of the Design Criteria section. Refer to the Design Criteria lines were followed. After removal, Section the bulbs.data htee Installation section for other important require- inspect the sprinkler for damage. Section in this data sheet. ments regarding piping design and • are orrosi or exhibiting visible signs sealing of the clearance space around 4. After applying a wall finish,slide on o g g the Sprinkler Casing. With reference to the outer piece of the Escutcheon of corrosion. Figure 10, do not grasp the sprinkler until it comes in contact with the by the deflector. Failure to follow this mounting surface. instruction may impair performance of For Deep Escutcheons, slide the the device. outer skirt over the inner cup to make firm contact with the mounting surface. • 67 • CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 7 of 8 • Responsibility lies with owners for the Limited Ordering inspection,testing,and maintenance of their fire protection system and devices Warranty Procedure in compliance with this document, as well as with the applicable standards of Products manufactured by Tyco Contact your local distributor for avail- the National Fire Protection Association Fire Protection Products (TFPP) are ability.When placing an order,indicate (for example, NFPA 25), in addition to warranted solely to the original Buyer the full product name, including the standards of any other Authorities for ten (10) years against defects description and Part Number(P/N). Having Jurisdiction. The installing in material and workmanship when contractor or sprinkler manufacturer paid for and properly installed and Dry Sprinklers should be contacted relative to any maintained under normal use and When ordering 11.2 K-Factor Series questions. service. This warranty will expire DS-3 Horizontal Sidewall Dry Type Automatic sprinkler systems are recom- ten (10) years from date of shipment Sprinklers, specify the following mended to be inspected, tested, and by TFPP. No warranty is given for information: maintained by a qualified Inspection products or components manufac- •Model/SIN TY5339 Service in accordance with local tured by companies not affiliated by • Length requirements and/or national codes. ownership with TFPP or for products Dry-Type n Sprinklers are furnished and components which have been upon Order Length as subject to misuse, improper instal- measured from the face th of the lation, corrosion, or which have not measured u the face of the sprinkler been installed, maintained, modified wall (Figure face 3, and the sprinkler the or repaired in accordance with appli- fitting ( 9 cable Standards of the National Fire measurement is taken, round it to Protection Association, and/or the the nearest 1/4 inch increment. standards of any other Authorities •Inlet Thread Connections Having Jurisdiction. Materials found 1-Inch NPT or 7-R1 by TFPP to be defective shall be either •Temperature Rating repaired or replaced, at TFPP's sole P g option. TFPP neither assumes, nor •Sprinkler Finish authorizes any person to assume for .Escutcheon Type it, any other obligation in connection with the sale of products or parts of •Part Number from Table E. • products. TFPP shall not be respon- sible for sprinkler system design errors Sprinkler Wrench or inaccurate or incomplete infor- Specify W-Type 8 Sprinkler Wrench, mation supplied by Buyer or Buyer's P/N 56-010-4-118. representatives. Sprinkler Boot In no event shall TFPP be liable, in Specify Model DSB-2 Dry Sprinkler contract, tort, strict liability or under Boot, P/N 63-000-0-002. This Part any other legal theory, for incidental, Number includes one Boot,two Strap indirect, special or consequential Ties,and 1/3 oz. of Adhesive(quantity damages, including but not limited to of adhesive is sufficient for installing labor charges, regardless of whether one Boot). TFPP was informed about the possi- bility of such damages,and in no event shall TFPP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,express or implied. including warranties of merchantability and fitness for a partic- ular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components,whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part,of any portion of this warranty will not affect the remainder. • 68 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 8 of 8 • P/N* 61 -. XXX - X - XXX SPRINKLER ESCUTCHEON MODEL/SIN FINISH FINISH(1) Flush Escutcheon 1 NATURAL BRASS BRASS PLATED 161 TY5339 (1°NPT),155°F(68°C) Flush Escutcheon 4 WHITE POLYESTER WHITE COATED 163 (1"NPT),200°F(93°C) TY5339 171 Deep Escutcheon 9 CHROME PLATED CHROME PLATED (1"NPT),155°F(68°C) TY5339 Deep Escutcheon 0 CHROME PLATED WHITE COATED 173 (1"NPT),200°F(93°C) TY5339 151 Without Escutcheon TY5339 (1"NPT),155°F(68°C) 153 Without Escutcheon NPT),200°F(93°C) TY5339 ORDER - LENGTH(2) 055 5.50" Notes • Use Prefix"I"for ISO 7-R1 Connection;for example,1-61-161-1-055. 062 8.25" 1. Does not apply to assemblies without escutcheon. 2. Dry-Type Sprinklers are furnished based upon"Order Length"as measured per 180 18.00" Figures 2,3,and 4.After the measurement is taken,round it to the nearest 1/4 inch increment. 187 18.75" 372 37.25" • 480 48.00" TABLE E SERIES DS-3 HORIZONTAL SIDEWALL, DRY-TYPE SPRINKLERS(ECOH) — PART NUMBER SELECTION— . Copyright©2011 Tyco Fire Protection Products.All rights reserved. � �®TEFLON is trademark of The DuPont Corporation. 69 CAMP PARSONS MATERIAL SUBMITTAL ,,THE INCH" M1 (i JOB#1406073 �,, QUICK RE SPONSE G ....,. AUTOMATIC SPRINKLERS V" MODEL GL5606 • FIRE SPRINKLER CORPORATION ONE INCH ADJUSTABLE DESCRIPTION AND OPERATION CONCEALED PENDENT The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile, aesthetically pleasing design. It provides sprinkler operation approximately six times faster than ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specified when allowed by the applicable standards. It offers the additional feature of greatly increased safety to life and should be used advisedly and under the direction of approving authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover plate assembly. All that is seen at the ceiling is a 3 5/16"diameter ceiling plate or an optional 23/"diameter ceiling plate color finished to match the specifier's exact requirements. The GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its 3mm frangible glass ampule which is located above the ceiling and concealed from view by the ceiling plate. The provided protective cap needs to be removed in order to install the sprinkler with the proper wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be installed. The "push on - screw off' designed cover plate is easily installed and with a nominal 1" inch of adjustment makes it easier to get a proper fit at the ceiling. Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the 3mm glass bulb to burst allowing the deflector to drop down and distribute water in an approved pattern to extinguish or control the fire. TECHNICAL DATA • - *See reverse side for Approvals and Specifications. •Temperature Ratings - . 135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate 155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate 155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate 3 5/16"diameter plate 175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate 200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate f •Water Working Pressure Rating - 175 psi (12 Bars) •Factory tested hydrostatically to 500 psi (34 Bars) •Maximum low temperature glass bulb rating is -67°F (-55°C) •Frame - bronze • Deflector- brass • Screw- brass •Bulb seat - brass • Spring - nickel alloy • Seal - teflon 2 3/4"diameter plate *Bulb - glass with alcohol based solution, 3mm size QUICK RESPONSE *Drop Pin - stainless steel WHITE ADJUSTABLE *Cover Plate brass CONCEALED PENDENT *Upper Escutcheon Assembly - plated steel NOTE: Globe's wrench P/N 332765 must be used to install this sprinkler. 'SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE BULB N.F.P.A. MAXIMUM CEILING SPRINKLER TEMPERATURES COLOR TEMPERATURE ORDINARY 1155 /1 ',1 57°C/68°C '4 ORANGE/RED 100 F 38°C111 i l INTERMEDIATE 't r (� hlllH _ YELLOW/GREEN 1 CIPF 6-6°C 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 (989) 846-4583 • FAX 989-846-9231 MAY 2012 A-3871 BULLETIN GL5606 REV#6 h. CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 QUICK RESPONSE • AUTOMATIC SPRINKLERS MODEL GL5606 ONE INCH ADJUSTABLE CONCEALED PENDENT SPECIFICATIONS NOMINAL"K" FACTOR THREAD SIZE LENGTH FINISHES Bright Chrome White Painted 5.6 (80 metric) 1/2"NPT 2 1/2" (6.4 cm) Bright Brass' Satin Chrome' Other Painted Finishes' NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES N AVAILABLE CONTACT GLOBE FOR ORDERINGSPECIFICATIONS. THAN WHITE, OTHER APPROVALS **135°F (57°C) 155°F (68°C) **155°F (68°C) 175°F (79°C) 200°F (93°C) NYC-DOB STYLE SIN K with plate with plate with plate with plate with plate cULus *FM MEA MODEL FACTOR 135°F (57°C) 135°F (57°C) 155°F (68°C) 155°F (68°C) 155°F (68°C) 101-92-E Adjustable Concealed GL5606 5.6 X X X X X X X X Pendent TM APPROVED AS STANDARD RESPONSE "NO FM APPROVALS CROSS SECTIONS 2 2 1/4"DIA MIN. ROLE IN LIN. ROLE IN CEILING HOLE IN CEILNG DIG. 11/8" • 7/8 D A 1'X1/1' l'xl/2'• RFDUCE0. irri RRMILEN kr ii a, I!1IIi� 131•'M8% CLF �■I �,'�1-, I 11/8"I IAN. DEREClOR tilt' il ea 1 I 7/8"MIN. DEREQIXt . DROP PIN DROP PIN StiP00.T SHELL _ \ SUPP TSHELL MI 2 3/4" 1/• 35/1B 1/e' CEILING LOVER PLATE CEILING COYER PLATE OPTIONAL COVER WHITE 135°F WHITE 155°F CHROME 135°F CHROME 155°F PLATE SIZE PART# PART# PART# PART# 2 3/4" 332729 332726 332731 332724 3 5/16" 332706 332711 332704 332709 ORDERING INFORMATION GLOBE® PRODUCT WARRANTY SPECIFY Globe agrees to repair or replace any of its own manufactured •Quantity • Model Number • Style products found to be defective in material or workmanship for •Orifice • Thread Sizes • Temperature a period of one year from date of shipment. •Finishes desired For specific details of our warranty, please refer to Price List •Quantity-Adjustable Concealed Wrenches-P/N 332765 Terms and Conditions of Sale (Our Price List). • CIL 4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658 989-846-4583 FAX 989-846-9231 FIRE SPRINKLER CORPORATION 1-800-248-0278 www.globesprinkler.com MAY 2012 PRIN-Fk U.S.A. BULLETIN GL5606 REV#6 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 it.a. IC ID 2 miaow `p,' AUTOMATIC SPRINKLERS GL SERIES FIE SPRINKLER CORPORATION DRY TYPE DESCRIPTION AND OPERATION The Globe Quick Response GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples. The Globe Quick Response GL Series Dry Type Pendent ii, Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation ap- proximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the 11 `: ''e, spring assembly to pivot alongside the inner tube. At this time, q,. ; water flows through the sprinkler and is distributed by the deflector „, in an approved discharge pattern. It can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response j, 1 1' Sprinklers should be used advisedly and under the direction of ir AV approving authorities having jurisdiction. The heart of Globe's Model GL Series sprinkler proven actu- SURFACE SLEEVE ating assembly is a hermetically sealed frangible glass ampule MOUNT &SKIRT that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the ID internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass ail causing the glass to shatter. This results in water discharge which is distributed in an approved pattern. TECHNICAL DATA ,. ,y+ • See reverse side for Approvals and Specifications. • Temperature Ratings - 135°F (57°C). 155°F (68°C), 175°F ill PI'g.F'• (79°C), 200°F (93°C), 286°F (141°C) ,� • Water Working Pressure Rating - 175 psi (12 Bars) - • Factory tested hydrostatically to 500 psi (34 Bars) `, vi • Maximum low temperature glass bulb rating is -67°F (-55°C) - If • Frame - bronze• Deflector - brass • Screw - brass EXTENDED RECESSED • Bulb seat - brass • Spring - teflon coated nickel alloy • Retainer- brass • Pin - stainless steel *Torsion spring - stainless steel • Bulb - glass with alcohol based solution, 3mm • Orifice insert - brass • 3/4" NPT or 1" NPT • Outer tube - galvanized steel pipe • Inner tube stainless steel • SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CLASSIFICATION BULB COLOR TEMPERATURES CEILING TEMPERATURE ORDINARY X35°F/1S5°F 57"'C/6&C ORANGE/RED 100 F 38°G ° - YELLOW/GREEN 1 ! 86CC INTERMEDIATE �-,17-0°F4--04V-1,-,--4.-4:- '� '�� , ° • HIGH 1 286°F 11-=, €p BLUE ;i 107° --;'.7 ■4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 * FAX 989-846-9231 JULY 2010 A-A5 BULLETIN GL5635, REV.#13 CAMP JOB PARSONS#1406073 MATERIAL SUBMITTAL QUICK RESPONSE AUTOMATIC SPRINKLERS GL SERIES DRY TYPE SPECIFICATIONS NOMINAL"K" FACTOR THREAD SIZE LENGTH FINISHES 5.6 (80 metric) cULus Variable Factory Bronze ( ) 3!4"or1"NPT to 48" Satin Chrome' Bright Chrome FM Variable White Polyester2 8.1 (116 metric) 1"NPT Black Polyester'? to 36" Lead Coated'3 NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. 'cULus LISTED CORROSION RESISTANT: APPROVALS POLYESTER MUST BE SPECIFIED ON ORDER. LEAD COATED IS UL APPROVED ONLY. STYLE SIN MODEL KFACTOR THREAD SIZE 135°F 155°F 175°F 200°F 286°F 57°C 68°C 76°C 93°C 141°C 286°F "FM cllLus - -E GL5635 5.6 1"NPT X X X X X X 101-92-E PENDENT X X X GL5838 5.6 3/4"NPT X X X X X - X X GL8135 8.1 1"NPT X X X X X - X X RECESSED GL5635 5.6 1"NPT X X X X X X X X P GL5638 5.6 3/4"NPT X X X X X - X X GL8135 8.1 1"NPT X X X X X - X X NOTE: LISTED FOR ALL HAZARDS 'PENDENT STYLE-FM APPROVED 155°F,200°F,AND 286°F IMPORTANT INSTALLATION DATA 'RECESSED PENDENT STYLE-FM APPROVED 155°F AND 200°F Globe GL Series Dry Pendent sprinklers should be installed CROSS SECTIONS in accordance with the requirements set forth in NFPA 13. • These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible,the proper •"',""�'y"`r} MY 1114 a.,•n om, !I sprinkler head wrench may be used with extreme care for• "°" i - lengths up to a 6 j r I- —N 9 P approximately 18". Excessive force may distort the frame thus destroying the unit. When installed in a wet system extending Into a freezing " " I. area see chart on Dry Caution Sheet for minimum exposed z�'��'���//, '''"""'"" barrel length to prevent ice plugs. Please refer to our Dry 7 � ° Mir I .;44....."" Caution sheet for further important installation data. I W/Z ORDERING INFORMATION 11I! —n O°`"o" '∎1,' SPECIFY EXTENDEDPENDENT PENDENT •Quantity • Model Number •Style • Orifice •Temperature • Finishes desired "'°,". ,mom! ir•"^ ,. •Quantity-Wrenches- P/N 333010 I • 1 Il — i i- �^i`^ .l —r •Quantity - Recessed Wrenches- P/N 337014 •Quantity-Protective Caps-P/N 327109-cap(Friction Fit u;a„ Recessed) " •Escutcheons desired aW. .:7' AMP' / •"A" Dimension - Distance from face of fitting to the finished /A _.. �..-. F, . I ceiling line regardless of escutcheon used. _,_°" _'a;�' ` :ao° ' �"` ° ° GLOBE PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured RECESSED PENDENT SLEEVE&SKIRTPENDENT products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty,please refer to Price List Terms and Conditions of Sale (Our Price List). � >L BE 4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658 . 989-846-4583 FAX 989-846-9231 FIRE SPRINKLER A 1-800-248-0278 www.globesprinkler.com JULY2010 PRINT8U.S.A. BULLETIN GL5635,REV.#13 CAMP PARSONS MATERIAL SUBMITTAL t. JOB#1406073 QUICK RE SPONSE GL Ar . ; k AUTOMATIC SPRINKLERS • v try „. BE GL SERIES F RE �PIK . �OPRAT DRY TYPE HORIZONTAL SIDEWALL RECESSED HORIZONTAL SIDEWALL DESCRIPTION AND OPERATION The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary -11 - 71, ' horizontal pipe nipples. . II The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler -' '- utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times fasterthan ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot QUICK NON RESPONSE alongside the inner tube. At this time, water flows through the sprinkler and is DRY NON-ADJUSTABLE distributed by the deflector, in an approved discharge pattern. It can be installed HORIZONTAL SIDEWALL wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction. The heart of Globe's GL Series sprinkler proven actuating assembly is a - hermetically sealed frangible glass ampule that contains a precisely measured a amount of fluid. When heat is absorbed, the liquid within the bulb expands i Mai e.increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to • shatter. This results in water discharge which is distributed in an approved pattern. QUICK RESPONSE TECHNICAL DATA DRY SLEEVE 8 SKIRT HORIZONTAL SIDEWALL • See reverse side for Approvals and Specifications. * Temperature Ratings- 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C). :'1'3; i a Water Working Pressure Rating - 175 psi (12 Bars). ;f • Factory tested hydrostatically to 500 psi (34 Bars). • Maximum low temperature glass bulb rating is-67°F (-55°C). 1 • Frame - bronze • Deflector- brass . Screw- brass + Bulb seat- brass • Spring - teflon coated nickel alloy • Retainer- brass • Pin - stainless steel * Torsion s rin QtitGK RESPONSE p g - stainless steel DRY RECESSED • Bulb - glass with alcohol based solution, 3mm ® Orifice insert- brass HORIZONTAL SIDEWALL « 3/4" NPT or 1" NPT ® Outer tube - galvanized steel pipe O Inner tube - stainless steel • SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE SPRINKLER N.F.P.A. MAXIMUM TEMPERATURES BULB COLOR CEILING TEMPERATURE ORDINARY , 135"Ff155°F 57"C/68°C ORANGE/RED 100°F 38pC INTERMEDIATE I175°F/20O°F 79°C/93°C, YELLOW/GREEN 150°F 66°C HIGH 286°F 19°t; BLUE 225°F 107°C • 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 . FAX 989-846-9231 JULY 2010 A-58 BULLETIN GL5641, REV. #14 CAMP PARSONS MATERIAL SUBMITTAL QUICK RESPONSE JOB#1406073 AUTOMATIC SPRINKLERS 0 GL SERIES DRY TYPE SPECIFICATIONS NOMINAL"K' FACTOR THREAD SIZE LENGTH FINISHES cULus Factory Bronze 5.6 (80 metric) 314" or 1" NPT Variable to Satin Chromes 48" Bright Chrome FM White Polyester 8.1 (116 metric) 1" NPT Variable to Black Polyester 36 Lead Coated2 NOTE: Metric Conversions are approximate. 'Finishes available on special order. cULus listed corrosion resistant: Polyester must be specified on order, 'Lead Coated is UL approved only. APPROVALS 135°F 155T 175T 200°F 286°F •FM cULus STYLE SIN CODE K FACTOR THREAD SIZE 57°C 68°C 79°C 93°C 141°C HORIZONTAL GL5641 5.6a 1"NPT X X X X X X X GL5642 5.6a 3/4"NPT X X X X X X SIDEWALL 1"NPT X X X X X - X GL8141 8.1° RECESSED GL5641 5.6a 1"NPT X X X X X X X HORIZONTAL GL5642 5.6a 3/4" NPT X X X X X - X SIDEWALL GL8141 8.1° 1"NPT X X X X X - X NOTE:'Listed for light hazard ordinary only with deflectordefe defector below 2the ceiling. IMPORTANT INSTALLATION DATA Listed for light and ordinary hazard with deflector from 4"-12"below the ceiling. 'Recessed Horizontal Sidewall-FM Approved 155°F and 200°F only. • 'Horizontal Sidewall-FM Approved 155°F,200°F,and 286°F only. Globe GL Series Dry Horizontal Sidewall sprinklers should be installed in accordance with the requirements set forth in CROSS SECTIONS NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube.When this is not possible,the „ proper sprinkler head wrench may be used with extreme care ;,;::"„, for lengths up to approximately 18".Excessive force may distort ,;;,T— the frame thus destroying the unit. 01 r'tga. I When installed in a wet system extending into a freezing --- s__-_ LJ area see cha rt on Dry Caution Sheet for minimum exposed 11 tiL. � ‘�,,�•°, barrel length to prevent ice plugs. Please refer to our Dry - _� �•!� a II , Caution sheet for further important installation data. ■ T ,r g ° ° ' ORDERING INFORMATION• .5''°' L.. -u:..z'_J -..•, 71r", rw. SPECIFY EXTENDED RECESSED •Quantity • Model Number • Style HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL •Orifice •Temperature •Finishes desired •Quantity-Wrenches-P/N 333010 ,}n,.�,,,,,, •Quantity-Recessed Wrenches-P/N 337014 "IV— ,�_ y. •Quantity-Protective Caps-P/N 327109-CAP(Friction Fit L 1 ° ° / ` ,� „ — W Recessed) •Escutcheonsdesired / m 1 r our I ° '°` •'A"Dimension-Distance from face of fitting to the finished '�' ; ceiling regardless of escutcheon used. S , � _ ,� - � 4° GLOBES PRODUCT WARRANTY a,,, :' '° ;n-- Globe agrees to repair or replace any of its own manufactured B6NON-ADJUSTABLE SLEEVE&SKIRT products found to be defective in material or workmanship for a HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale(Our Price List). 4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658 FIRE SPRINKLER . P 10R:-:Ai1 QN 989-846-4583 FAX989-846-9231 1-800-248-0278 www.globesprinkler.com JULY 2010 PRINT=? U.S.A. BULLETIN GL5641, REV.#14 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • SECTION 2. 3 VALVES AND ACCESSORIES • • 79 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • Fire Department Connection, .7-- ry #y t �` 4 Straight Pattern r:, I i 1,1' i xr. Description Installation Specs The Straight Pattern Fire Installation of the Fire De- Size: Department Connection is partment Connection is 4" IPS Outlet Underwriters' Laboratories achieved with readily avail- (2) 2 1/2" NST listed and Factory Mutual able jobsite tools. Prior to Swivel Inlets itat Approved. Manufactured installation make sure the Tyoe: from solid brass components proper identification sign has Straight Pattern Pit' Approved. increase service life.The been installed on the nipple. single clapper design fea- Coat male threads of 4" IPS Material: tures brass clapper and nipple liberally with a suit- Brass brass seats within a cast able pipe thread sealant brass body. The 2 1/2" such as Pipefit0.Tighten Swivels: swivels are pin lug design FDC one full turn past hand 2 1/2" NST PL for ease of use and tight. Make sure FDC is BCT campatablilty with local fire aligned according to require- ONT service districts.Swivel ments. QST gaskets are included. Break- PHX able caps in either metal or DO NOT OVER TIGHTEN. TEM plastic should be installed to OVERTIGHTENING MAY CLV protect swivels and prevent CAUSE SEVERE debris from being accidently STRETCHING AND POS- Approvals: introduced into the water way. SIBLE CRACKING OF THE OF THE FDC BODY. UL Listed FM Approved For questions: 1 800 344-1822 1 800 344-3775 fax http://www.fppi.com • FPP1 info @fppi.com ©1995-2000 Fire Protection Products, Inc. 80 CAMP PARSONS MATERIAL SUBMITTAL ■ I ,, (� ry Standpipe Equipment C` l.7 MI F P P I Fire Department Connections & Accessories • Storz Type Fire Department Connection Provides a"quick connection"of large diameter hose by Fire Service Professionals to fire sprinkler or standpipe systems. Conforms with NFPA1963 requirements. Forged aluminum. Storz Fire Dept. Connections w/Caps Box Qty. 09-205-00 4" Storz x 4" FNPT w/Cap (UL) 2 09-207-00 5" Storz x 4"FNPT w/Cap (UL) 2 09-215-00 4" Storz x 4" FNPT, 30°w/Cap(UL) 1 09-217-00 5" Storz x 4"FNPT, 30°w/Cap (UL) 1 Storz Kits Fire Dept.Connections w/Caps Box Qty. &Sprinkler Wall Plates 09-230-00 4" Storz x 4"FNPT w/Cap & Wall Plate (UL) 1 0 09-234-00 5" Storz x 4" FNPT w/Cap&Wall Plate (UL) 1 09-236-00 4" Storz x 4"FNPT, 30°w/Cap &Wall Plate (UL) 1 09-238-00 5" Storz x 4"FNPT, 30°w/Cap&Wall Plate (UL) 1 0 • C3 Storz Individual Storz Components Box Qty. a 09-200-00 4" Storz x 4" FNPT(UL) 4 0- t 4- 09-202-00 5" Storz x 4" FNPT(UL) 4 4 § 09-210-00 4" Storz x 4"FNPT w/30° Elbow (UL) I 3 • 09-212-00 5"Storz x 4"FNPT w/30°Elbow(UL) 1 • 09-220-00 4" Storz Cap&Chain 4 N N 09-222-00 5"Storz Cap&CHain 4 , E 4 N. M o -Ir o0 r FDC Wall Plates Part No. Description Box Qty. C o 09-507-00 FDC W/P 4" IPS Auto Spr" Plastic 25 09-508-00 FDC W/P 4"IPS "Auto Spr" AL 12 gr, ''j 1 5 i= 09-509-00 FDC Sign 4"x 8" "Fire Dept Conn" AL 100 a? it 5 09-510-00 FDC W/P 4" IPS "Auto Spr" RB 5 r� -- a C 09-510-10 FDC W/P 4" IPS "Auto Spr" PC 5 ' _ •09-514-00 FDC W/P 4" IPS "Standpipe" AL 12 TS CL G 09-516-00 FDC W/P 4" IPS "Standpipe-Auto" AL 12 is+ 09-520-00 FDC W/P 21/2"IPS "Auto Spr" RB 10 I y 09-522-00 FDC W/P 21/2" IPS "Auto Spr" AL 20 AL=Aluminum RB=Rough Brass • PC=Polished Chrome 82 33 WILKINS. Model 350A a zt ilxcompany Double Check Valve Assembly . . " .[ :E 3 T � E , . APPLICATION Pi '""' Designed for installation on potable water lines to protect against w ► both backsiphonage and backpressure of polluted water into the I °. : " i° ° - potable water supply.The Model 350A shall provide protection ff • • where a potential health hazard does not exist. Ideal for use where lead-free*valves are required. (with OSY gates) (with BGVIC valves) 0.-f.2 STANDARDS COMPLIANCE(Horizontal&Vertical) FEATURES • ASSE®Listed 1015 Sizes: 02 1/2"* Jr' U4" ❑6" 08" 010" • AWWA Compliant C510(with gates only) Maximum working water pressure 175 PSI • IAPMO®Listed Maximum working water temperature 140°F • GSA®Certified Hydrostatic test pressure 350 PSI • UL®Classified End connections • C-UL®Classified (Grooved for steel pipe) AWWA C606 • FM®Approved (Flanged) ANSI B16.1 • NYC MEA 220-04-M Vol 2(2 1/2"-8") Class 125 • Approved by the Foundation for Cross Connection Control *2 1/2"&3"sizes use 4"body&reducer couplings and Hydraulic Research at the University of Southern OPTIONS(Suffixes can be combined) California ❑ - with flanged end NRS gate valves(standard) • NSF®Listed-Standard 61,Annex G* ❑ FSC - with epoxy coated wye type strainer(flanged only) *(0.25%MAX.WEIGHTED AVERAGE LEAD CONTENT) ❑ G - with grooved end NRS gate valves MATERIALS ❑ GF - with grooved inlet gate connection and flanged Main valve body Ductile Iron ASTM A 536 Grade 4 outlet gate connection Access covers Ductile Iron ASTM A 536 Grade 4 ❑ FG - with flanged inlet gate connection and grooved Coatings FDAApproved electrostatic epoxy outlet gate connection finish ❑ L - less shut-off valves(grooved body connections) Internals Stainless steel, 300 Series ❑ OSY - with flanged end OS&Y gate valves NORYLTM NSF Listed • OOSYG- with grooved end OS&Y gate valves Fasteners&springs Stainless Steel,300 Series ❑ PI - with Post Indicator Gate Valves(3"-12") Seal ring EPDM(FDA approved) ❑BGVIC- with grooved end butterfly valves 0-ring Buna Nitrile(FDA approved) ACCESSORIES ® ❑ Repair kit(rubber only) MODEL 350A L - =-- ❑ Thermal expansion tank(Model XT) with OSY& Ell ❑ OS&Y Gate valve tamper switch(OSY-40) FSC option ❑ Test Cock Lock(Model TCL24) E- lj • T tr 'll 000 DIMENSIONS&WEIGHTS(do not include pkg.) • }� �'la °°._ F WEIGHT .y 8 WITH WITH MODEL WITH OS&Y A 0 • SIZE WITHOUT WITH NRS GATES WGATESS GATES BUTTERFLY - G - �y GATES GATES (GXF) (GXF) (GXG) (GXG) (GXG) • in. mm lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg -&D MI- rl 2112 65 90 41 184 83.5 192 87 176 80 184 83.5 108.8 49.4 MODEL 1,__ _ �') ..a E 3 80 89 40,5 204 92.5 210 95.3 194 88 200 90.8 109.4 50 350A with 10-‘1 4 100 76 34.5 220 100 230 104 194 88 204 93 108 49 BGVIC option I II� UIr) -• F 6 150 126 57.2 346 157 362 164 316 143 332 151 178 81 - 8 200 286 130 738 335 762 335 738 335 738 335 394 179 8 _- --y 'III 10 250 339 153.8 966 438.2 1024 464.5 844 382.8 902 409.1 511 232 1-----A 01 0 DIMENSION(approximate) MODEL a E E E E WITH SIZE A A WITH LESS C D OS&Y OS&Y NRS GATE BUTTERFLY F G Attention: BUTTERFLY GATE OPEN CLOSED VALVES VALVES Model 350A in. mm in. mm in. mm in. mm in mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm (grooved body) 21/2 65 351/8 892 321/8 816 201/8 511 4 1/2 114 71/4 184 163/8 416 137/8 352 11 3/8 289 8 203 6 152 451/4 1150 &Model 350 3 80 361/8 918 33 838 201/8 511 41/2 114 71/4 184 187/8 479 155/8 397 123/8 314 8 203 6 152 467/8 1191 (flange body) 4 100 381/4 972 331/4 845 197/8 505 41/2 114 8 203 22314 578 181/4 464 143/4 375 91/8 232 6 152 533/8 1356 have different • 6 150 471/4 1200 401/4 1022 257/8 657 51/2 140 10 254 301/8 755 233/4 603 19 483 101/8 257 7 178 653/8 1661 lay lengths. 8 200 62 1575 55 1397 38 1/2 978 10 254 11 279 37 3/4 959 29 1/4 743 22 1/2 572 1115/16 303 81/2 216 86 3/8 2194 10 250 64 5/8 1642 58 1/2 1485 38 1/2 978 10 254 12 305 45 3/4 1162 35 3/8 899 26 1/2 673 13 5/16 338 81/2 216 94 3/8 2398 DOCUMENT#: REVISION: (Patent No. 5,913,331) BF-350A 1/11 Page 1 of 2 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 FLOW CHARACTERISTICS iii, MODEL 350A 2 1/2",3"&4"(STANDARD&METRIC) 0.0 FLOW RATES(Us)12.6 25.2 37.9 50.5 &15 (7)a 1 104s.Y n _ 010 2112"(65mm) 4°(100mm)- m w " 80mm 69 O cc LU 5 35 cc LU n D a a - a 0 200 0 4 600 800 FLOW RATES ES(GPM) MODEL 350A 6",8"&10"(STANDARD&METRIC) FLOW RATES(Ils) 0.0 63.1 126.2 �?15 189.3 252.4 ra a -1/ 104 tq :0"(250mm)- O 1D r r"ry60mmm w En J rr 69 0 j 5 r,������— w H ! w� s 35 rn a 0 w 1 0 0 a 1000 2000 3000 4000 FLOW RATES(GPM) 6 Rated Flow(eElablIshed by approval agencies) TYPICAL INSTALLATION Local codes shall govern installation requirements. Unless other- Capacity thru Schedule 40 Pipe(GPM) wise specified, the assembly shall be mounted at a minimum of Pipe size 5 ft/sec 7.5 fUsec 10 ft/sec 15 ft/sec • 12"(305mm) and a maximum of 30" (762mm)above adequate 2 112" 75 112 149 224 drains with sufficient side clearance for testing and maintenance. 3" 115 173 230 346 The installation shall be made so that no part of the unit can be 4" 198 298 397 595 submerged. 6" 450 675 900 1351 y 8" 780 1169 1559 2339 10" 1229 1843 2458 3687 I se, ,J 12" 1763 2644 3525 5288 r L':-. _ All - 71 'L5, C - PROTECTIVE _ 'f� i= . �, g , ENCLOSURE II � Iii ,_� T I.11kLr ll�IA !AM -r-P�• __' 'II I.I 1 1 ! IL\v\�.._.{'i) / 1 � C,, 12'MIN _ —' III' • �y//may//�{ TF 1 I 4-411 MI sm MAX T- Y4 .. 1T MIN. i -_. IILI I. 3a�0.K n °. . • —....DIRECTION OF FLOW's.„. .... .I .I.`..) • - ni ' DIRECTION OF FLOW INDOOR INSTALLATION INDOOR INSTALLATION OUTDOOR INSTALLATION MODEL 350ABGVIC (VERT.)MODEL 350A MODEL 350AFS SPECIFICATIONS The Double Check Backflow Prevention Assembly shall be ASSE® Listed 1015,and supplied with full port gate valves.The main body and access cover shall be epoxy coated ductile iron(ASTM A 536 Grade 4),the seat ring and check valve shall be NORYLTm, the stem shall be stainless steel(ASTM A 276)and the seat disc elastomers shall be EPDM.The checks shall be accessible for maintenance without removing the device from the line. The Double Check Backflow Prevention Assembly shall be a WILKINS Model 350A. • WILKINS a Zum company,1747 Commerce Way,Paso Robles,CA 93446 Phone:806/238-7100 Fax:805/238-5766 IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax Product Support Help Line:1-877-BACKFLOW(1-877-222-6356) • Website: http://www.zurn.com Page 2 of 2 85 CAMP PARSONS MATERIAL SUBMITTAL WO Technical Services I w + 0 -38 -4 y0071-98 - 81-821 wwtc -firec3o2m 0 2 • . . Series DS-3 Dry-Type Sprinklers 11.2K* Horizontal Sidewall, Extended Coverage, Standard Response General Owners are responsible formaintaining their fire protection system and devices Description in proper operating condition. The installing contractor orsprinkler manu- " TYCO Series DS-3 Dry-Type Sprinklers, facturer should be contacted with any 11.2K Horizontal Sidewall, Standard questions. --^ Response, Extended Coverage, Series DS-3 Dry-Type Sprinklers must z Ordinary Hazard, are decorative glass only be installed in fittings that meet bulb automatic sprinklers. They are the requirements of the Design Criteria intended for use in applications where section. Installation of Series DS-3 • the sprinklers and/or a portion of the Dry-Type Sprinklers in a recessed connecting piping may be exposed to installation will void all sprinkler warran- freezing temperatures; for example, ties,as well as void the sprinkler's labo- Finishes horizontal piping extensions through a ratoryapprovals. Sprinkler: Natural Brass, Chrome wall to protect an unheated area of a ■� Plated,White Polyester building. Model/Sprinkler Escutcheon: White Coated or Chrome Series DS-3 Extended Coverage Plated, Brass Plated Ordinary Hazard Horizontal Sidewall, Identification physjcal Characteristics Dry-Type Sprinklers are designed for Number (SIN) Inlet extended coverage use in ordinary Copper hazard occupancies(ECOH)per NFPA Plug Copper • 13. TY5339 Yoke Stainless Steel Series DS-3 Dry-Type Sprinklers Technical Casing Galvanized provide protection of coverage areas up Carbon Steel to 16 ft.x 20 ft. (320 ft2)as compared Insert Bronze to standard coverage horizontal Data Bulb Seat Bronze sdewall sprinklers having a maximum Bulb coverage area of 10 ft.x 10 ft.(100 ft2) Approvals Glass(3 mm) for ordinary hazard occupancies. UL and C-UL Listed Compression Screw Bronze Refer to Table A and the Design Criteria Deflector Bronze NOTICE Section. Frame Bronze Series DS-3 Dry-Type Sprinklers Guide Tube Stainless Steel described herein must be installed Maximum Working Pressure Water Tube Stainless Steel and maintained in compliance with this 175 Psi(12,1 bar) document, as well as with the appli- Spring Stainless Steel cable standards of the National Fire Inlet Thread Connections Gasketea Spring Protection Association, in addition to 1-Inch NPT Plate Seal Beryllium Nickel the standards of any other Authorities (Standard) w/TEFLON Having Jurisdiction. Failure to do so •ISO 7-R7 Pin Stainless Steel may impair the performance of these (For information on ISO Inlet Thread Button Spring Stainless Steel devices. Connections, contact your Tyco Helper Spring Stainless Steel Sales Representative) Escutcheon Carbon Steel Discharge Coefficient IMPORTANT Refer to Table B. Always refer to Technical Data Sheet TFP700 for the `INSTALLER Temperature Ratings WARNING"that provides cautions 155°F(68°C)and 200°F(93°C) with respect to handling and instal- lation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail • to operate in a fire situation or cause it to operate prematurely. Refer to Table B for info on discharge coefficients. Page 1 of 8 SEPTEMMER 2011 TFP3S0 ■ CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 H Page 2 of 8 PLUG WITH YOKE PLUG CASING INSERT FRAME BULB DEFLECTOR GASKETED SPRING \ / SPRING SEAL PLATE 64 ° d. '°'� "'°� .y.�> .07i d _ _ C i jz::iiizti:zii: ��iW wej, , INLET WATER GUIDE BULB COMPRESSION INLET 1"NPT SPRING BAND TUBE TUBE SEAT SCREW FIGURE 1 SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER TY5339(ECOH) —ASSEMBLY— SPRINKLER FINISH K-Factor K-Factor Temperature Bulb LENGTH GP /ps /2 Rating t Color Code Natural Chrome White M is Inches(mm) (LPM/bartre) Brass I Plated Polyester 155°F(68°C) Red Listed by Underwriters Laboratories,Inc. 2-1/2 to 14-3/4 11.2 (maximum order length of 48 inches) (63 mm to 375 mm) (161,3) 200°F(93°C) Green Listed by Underwriters Laboratories for use in Canada 15 to 18-3/4 10.9 (maximum order length of 48 inches) (381 mm to 476 mm) (157,0) 19 to 23 10.8 TABLE A (483 mm to 584 mm) (155,5) SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS 23-114 to 26-3/4 10.7 11111 EXTENDED COVERAGE,ORDINARY HAZARD(TY5339) (591 mm to 679 mm) (154,1) — LABORATORY LISTINGS AND APPROVALS — 27-1/4 to 31-1/4 10.6 (692 mm to 794 mm) (152,6) Oneration 31-1/2 to 35-1/4 10.5 M (800 mm to 895 mm) (151,2) When TYCO Series DS-3 Dry-Type 35-1/2 to 39-1/2 10.4 Sprinklers are in service, water is (902 mm to 1003 mm) (149,8) prevented from entering the assembly 10 / 39-3/4 to 43-1/2 .3 by the Plug with Gasketed Spring (10 33 mm to 43-1 2 (14.3) Seal Plate(Figure 1)in the Inlet of the Sprinkler. 43-3/4 to 48 10.2 (111 mm to 1219 mm) (146,9) The glass bulb contains a fluid that expands when exposed to heat.When Notes the rated temperature is reached,the fluid expands sufficiently to shatter K-Factor Length is determined as follows: the glass bulb, and the Bulb Seat is • Flush:Order Length from Figure 2 plus released. 1/2 inch(12,7 mm) The compressed Spring is then able • Deep:Order Length from Figure 4 plus to expand and push the Water Tube as 3-1/4 inch(82,6 mm) well as the Guide Tube outward.This • Without Escutcheon:Order Length from action simultaneously pulls inward on Figure 5 minus 2-1/4 inches(57,2 mm) the Yoke, withdrawing the Plug with Gasketed Spring Seal Plate from the TABLE B Inlet allowing the sprinkler to activate — DISCHARGE COEFFICIENTS — and flow water. • 88 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 3 of 8 • Coverage Top Of Application Areal W x L Minimum Flown Min Pressure2 Deflector-to-Ceiling Temperature Minimum Ft.x Ft. GPM(LPM) PSI(bar) Distance3. Ratin F C Spacings cm.m) Inches(mm) g° (° ) Ft.(m) 16 x 16 38 1 11.5 44 ( ) Series DS-3(TY5339) (4,9 x 4,4) (0,79) Horizontal Sidewall Dry-Type Sprinkler(ECOH) 16 x 18 43 163 14.7 OH Group 1 (0.15 gpm/sq.ft) (4,9 x 5,5) ( ) (1 Ot) Standard Response 16 x 20 18.4 (4,9 x 6,1) 48(182) (1,27) 6 to 12 16 x 16 51 (193) 20.7 (150 to 300) 155,200 (2,4) Series DS-3(TY5339) (4,9 x 4,4) (1,43) Horizontal Sidewall 16 x 18 Dry-Type (220 26.8 OH Group 2(0.20 Sprinkler gpm/sq.ftJ(ECOHJ 58(4,9 x 5,5) ) (1,85) Standard Response 16 x 20 (4,9 x 6,1) 64(242) 32.7 (2,25) Notes 1. Backwall(where sprinkler is located)by sidewall(length of throw). 2. Requirement is based on minimum flow in GPM from each sprinkler.The indicated residual pressures are based on the nominal K-Factor of 11.2. 3. The centerline of the sprinkler waterway is located below the deflector as shown in Figures 2,3,and 4. 4. Minimum spacing is for lateral distance between sprinklers located along a single wall.Otherwise adjacent sprinklers(that is,sidewall sprinklers on an adjacent wall,on an opposite wall,or pendent sprinklers)must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized. TABLE C SERIES DS-3 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS — UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA — • Ambient Temperature Temperatures for Heated Areal Exposed to Discharge End 40°F(4°C) I 50°F(10°C) I 60°F(16°C) of Sprinkler Minimum Exposed Barrel Length, Inches(mm)2 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE D EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS — MINIMUM RECOMMENDED LENGTHS - 89 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB*1406073 Page 4 of 8 0 Design ORDER LENGTHS: FACE OF Criteria 3"to 45-1/4"(76,2 to 1149,4 mm) MOUNTING IN 1/4"(6,4 mm)INCREMENTS SURFACE 2"t 1/8' TYCO Series DS-3, Standard FACE OF (50,8 t 3,2 mm) Response, Extended Coverage SPRINKLER FITTING Ordinary Hazard, Horizontal Sidewall, 2-3/4"DIA. 9/16"(14,3 mm) Dry Type Sprinklers (ECOH) are for 1"NPT, (69.9 mm) � 1 use in ordinary hazard occupancies 9/16"(14,3 mm) NOMINAL MAKE-IN \\\ iI with non-combustible unobstructed construction and with a ceiling slope 'III'��jlll 3-11/16"DIA. not exceeding 2 inches per foot(9.2°), pIIIIIwIiI� MI, \ f (93,7 mm) using the design criteria provided RIM in Table C, as well as any additional �. I 1 requirements specified in NFPA 13 for SPRINKLER FITTING -- Extended Coverage Sidewall Spray (REFER TO DESIGN CENTERLINE Sprinklers. CRITERIA SECTION) OF WATERWAY A 36-inch (914 mm) clearance must FIGURE 2 be maintained between the top of the SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER sprinkler deflector and any miscella- WITH FLUSH ESCUTCHEON(7Y5339) neous storage. Series DS-3 Dry-Type Sprinklers may be installed on sloped ceilings in loading docks with a maximum roof slope of 4 inches per foot (18.4°) as ORDER LENGTHS:1117, FACE IN shown in Figure 8 and using the design 1"to 46,(25m to INCREMENTS mm) ' SURFACE criteria provided in Table C. IN 1/4"(6,4 mm)INCREMENTS SURFACE 4-1/8•±3/8" ` - (104,8 t 9,5 mm) Sprinkler Fittings FACE OF Install 1-Inch NPT Series DS-3 SPRINKLER FITTING 2-3/4•DIA. 9/16"(14,3 mm) Dry-Type Sprinklers in the 1-Inch NPT 1"NPT, (69,9 mm) I outlet or run of the following fittings: • NOMINAL MAKE-IN +I 9MIN NOMINAL MAKE-IN KE- •malleable or ductile iron threaded II' I' 3-1/2"DIA. tee fittings that meet the dimen- uI'II ��1 sional requirements of ANSI B16.3 Illmu (88,9 mm) Class 150) •cast iron threaded tee fittings that SPRINKLER FITTING q. ----- meet the dimensional requirements (REFER TO DESIGN CENTERLINE of ANSI B16.4(Class 125). CRITERIA SECTION) OF WATERWAY Do not install Series D5-3 Dry Type Sprinklers into elbow fittings.The Inlet of the sprinkler can contact the interior FIGURE 3 of the elbow. SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER The unused outlet of the threaded tee is WITH DEEP ESCUTCHEON(f Y5339) plugged as shown in Figure 6. Series DS-3 Dry-Type Sprinklers can also be installed in the 1-Inch NPT ORDER LENGTHS: outlet of a GRINNELL Figure 730 - 5-1/4"to 48"(133,4 to 1219,2 mm) Mechanical Tee. However, the use of IN 1/4"(6,4 mm)INCREMENTS MINIMUM the Figure 730 Tee for this arrangement 2-1/4"(57,2 mm) is limited to wet pipe systems. FACE OF SPRINKLER FITTING - DEFLECTOR TO MOUNTING The configuration shown in Figure 7 is 1"NPT, SURFACE only applicable for wet pipe systems NOMINAL MAKE-IN where fitting ri and water- 9/16"(14,3 mm) filled pipe the above the sprinkler sprinkler fitting are not subject to freezing and where the '�IIIIplll/ ��.. len th of the Dry-Type Sprinkler has the �NIII' �' / } minimum expour length depicted in 9/18° Figure 10.Refer to the Exposure Length (14,3 mm) section. SPRINKLER FITTING (REFER TO DESIGN CENTERLINE CRITERIA SECTION) OF WATERWAY • FIGURE 4 SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER WITHOUT ESCUTCHEON(TY5339) 90 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP550 Page 5 of 8 NOT/CE • TO DRY Do not install Series DS-3 Dry-Type SYSTEM "\ YSTEM Y' ye p Sprinkler into any other type fitting MAXIMUM without first consulting the Technical THROW Services Department.Failure to use the •A �� appropriate fitting may result in one of the following: , . :.„, •Failure of the sprinkler to operate ro DSB-2 -_ P P P P INTENDED =' erly due to formation of ice over the FOR FREEZER 6'(152,4 mm) j--- Inlet Plug or binding of the Inlet Plug. STRUCTURES _,i4: TO 12”(304,8 mm) •Insufficient en a ement of the Inlet CEILING TO TOP 4/12 g 9 OF SPRINKLER SLOPE pipe-threads with consequent leakage. AREA DEFLECTOR MAXIMUM ,'i SUBJECT DISTANCE Drainage TO In accordance with the minimum FREEZING FIGURE 8 requirements of the National Fire Ilir SPRINKLER PLACEMENT Protection Association for dry pipe UNDER SLOPED CEILINGS sprinkler systems, branch, cross, and FIGURE 5 IN LOADING DOCKS feed-main piping connected to Dry SPRINKLER FITTING Sprinklers and subject to freezing — UNHEATED AREA — temperatures must be pitched for 2-3/4"DIA. proper drainage. (69,9 mm) Exposure Length DSB-2 "r CLEARANCE INSULATED When using e Dr Sprinklers in wet pipe RUN INTENDED HOLE FREEZER sprinkler systems p OUTLET FOR FREEZER ADHESIVE STRUCTURE freezing to protect areas PLUGGED STRUCTURES subject to freezing temperatures, use DSB-2 Table D to determine a sprinkler's HLERIlin BOOT 1r appropriate exposed barrel length _ to prevent water from freezing in the �= connecting pipes due to conduction. I j FITTING ',III,- The exposed barrel length measure- ment DESIGN ment must be taken from the face of • CRITERIA ap the sprinkler fitting to the surface of the SECTION) , ! i / structure or insulation that is exposed TO DRY to the heated area.Refer to Figure 7 for an example. SYSTEM STRAP TIES AREA (ENDS ON DS-3 For protected area temperatures OPPOSING SHOWN between those given above, the SUBJECT SIDES OF WITH FLUSH minimum recommended length from TO BOOT) ESCUTCHEON the face of the fitting to the outside of FREEZING .1 the protected area may be determined FIGURE 6 FIGURE 9 by interpolating between the indicated SPRINKLER FITTING MODEL DSB-2 DRY SPRINKLER values. — UNHEATED AREA — BOOT WITH SERIES DS-3 Clearance Space DRY-TYPE PENDENT SPRINKLER In accordance with Section 8.4.9.2 EXPOSURE r of the 2010 edition of NFPA 13, when LENGTH For wet pipe system installations of connecting an area subject to freezing ~(SEE DESIGN 1-Inch NPT Series DS-3 Dry-Type and an area containing a wet pipe CRITERIA SECTION) pri Sprinklers connected to CPVC piping, sprinkler system,the clearance space use only the following TYCO CPVC around the sprinkler barrel of Dry-Type FACE OF fittings: Sprinklers must be sealed. Due to SPRINKLER temperature differences between two FITTING •1" x 1" NPT Female Adapter (P/N areas, the potential for the formation 80145) of condensation in the sprinkler and I •1" x 1" x 1" NPT Sprinkler Head subsequent ice build-up is increased. If LLL Adapter Tee(P/N 80249). this condensation is not controlled, ice DSB-z For dry pipe system installations, use build-up can occur that might damage INTENDED Al only the side outlet of maximum 2-1/2- proper er opera sprinkler and/or ua prevent FOR FREEZER proper operation in a fire situation. STRUCTURES inch reducing tee when locating Series DS-3 Dry-Type Sprinklers directly Use of the Model DSB-2 Dry Sprinkler below the branch line.On use Boot,described in technical data sheet HEATED the configuration Shown inh Figure,6 to TFP591 and shown in Figure 9, can AREA assure complete water drainage from provide the recommended seal. above Series DS-3 Dry-Type Sprinklers 5 FIGURE 7 and the branch line. Failure to do so SPRINKLER FITTING may result in pipe freezing and water — HEATED AREA — damage. 91 ■ CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 6 of 8 • Do not install any bulb-type sprinkler if Care and the bulb is cracked or there is a loss of liquid from the bulb.With the sprinkler Maintenance held horizontally, a small air bubble should be present.The diameter of the TYCO Series DS-3 Dry Type Sprinklers 4�1 ` air bubble is approximately 1/16 inch must be maintained and serviced • (1,6 mm)for the 135°F(57°C)rating to in accordance with the following 1/8 inch(3,2 mm)for the 360°F(182°C) instructions. �` rating. Obtain a leak-tight 1-Inch NPT sprinkler NOTICE rl joint by applying a minimum-to- Before closing a fire protection system DO NOT maximum torque of 20 to 30 ft. lbs. main control valve for maintenance (26,8 to 40,2 Nm). Higher levels of work on the fire protection system torque may distort the sprinkler Inlet that it controls, obtain permission to with consequent leakage or impairment shut down the affected fire protection of the sprinkler. systems from the proper authorities FIGURE 10 Do not attempt to compensate and notify all personnel who may be — DO NOT GRASP DEFLECTOR — for insufficient adjustment in an affected by this action. Escutcheon Plate by under or over- Absence of the outer piece of an tightening the Sprinkler.Re-adjust the escutcheon, which is used to cover a WRENCH FLAT position of the sprinkler fitting to suit. clearance hole,may delay the time to ENGAGEMENT 1. Install horizontal sidewall sprinklers sprinkler operation in a fire situation. � � _ / AREA a with the center line of waterway A,Vent Hole is provided in the Bulb Seat �• parallel to the ceiling and perpen- (Figure 1)to indicate if the Dry Sprinkler WRENCH � dicular to the back wall surface.The is remaining dry. Evidence of leakage FLATS word "TOP" on the deflector must from the Vent Hole indicates potential face upwards toward the ceiling. leakage past the Inlet seal and the need a . 2. With a non-hardening pipe-thread to remove the sprinkler to determine sealant such as TEFLON applied to the cause of leakage;for example, an the Inlet threads, hand-tighten the improper installation or an ice plug. sprinkler into the sprinkler fitting. Close the fire protection system control • APPLY Do not grasp the sprinkler by the valve and drain the system before WRENCH AS deflector(Figure 10). removing the sprinkler. SHOWN 3. Wrench-tighten the sprinkler using Exercise care to avoid damage before, either: during, and after installation. Never FIGURE 11 a pipe wrench on the Inlet Band or paint, plate, coat, or otherwise alter W-TYPE 8 SPRINKLER WRENCH the Casin (Fi ure 1). automatic sprinklers after they leave 9 9 the factory. • the W-Type 8 Sprinkler Wrench on Non-factory applied paint can installation the Wrench Flat(Figure 11). adversely delay or prevent sprinkler Apply the Wrench Recess of the operation in the event of a fire. Series DS-3 Dry-Type Sprinklers must W-Type 8 Sprinkler Wrench to the Replace sprinklers that: be installed in accordance with the Wrench Flat. •were damaged by dropping,striking, following instructions. Note:If sprinkler removal becomes wrench twisting,wrench slippage,or necessary, remove the sprinkler the like. NOTICE using the same wrenching method Series DS-3 Dry-Type Sprinklers must noted above. Sprinkler removal •were modified or over-heated. only be installed in fittings that meet is easier when a non-hardening . have cracked bulbs or have lost liquid the requirements of the Design Criteria sealant was used and torque guide- from the bulbs.Refer to the Installation section. Refer to the Design Criteria lines were followed. After removal, Section in this data sheet. section for other important require- inspect the sprinkler for damage. .are leaking or exhibiting visible signs menu regarding piping design and • 4. After applying a wall finish, slide on of corrosion. sealing of the clearance space around the outer piece of the Escutcheon the Sprinkler Casing. With reference to until it comes in contact with the Figure 10, do not grasp the sprinkler mounting surface. by the deflector. Failure to follow this instruction may impair performance of For Deep Escutcheons, slide the the device. outer skirt over the inner cup to make firm contact with the mounting surface. III 92 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 TFP830 Page 7 of 8 Responsibility lies with owners for the Limited • inspection,testing,and maintenance of Ordering their fire protection system and devices Warrant in compliance with this document, as y Procedure well as with the applicable standards of Products manufactured by Tyco Contact your local distributor for avail- the National Fire Protection Association Fire Protection Products (TFPP) are ability. placing When lacin an order, indicate (for example, NFPA 25), in addition to warranted solely to the original Buyer the f full r duct name, including the standards of any other Authorities for ten 10 Having Jurisdiction. The installing ( ) years against defects description and Part Number(P/N). contractor or sprinkler manufacturer material and pery installed when should be contacted relative to an paid for and properly nstalled and Dry Sprinklers questions. y maintained under normal use and When ordering 11.2 K-Factor Series service. This warranty will expire DS-3 Horizontal Sidewall Dry-Type Automatic sprinkler systems are recom- ten (10) years from date of shipment Sprinklers, specify the following mended to be inspected, tested, and by TFPP. No warranty is given for information: maintained by a qualified Inspection products or components manufac- Service in accordance with local tured by companies not affiliated by Model/SIN TY5339 requirements and/or national codes. ownership with TFPP or for products •Order Length and components which have been Dry Type Sprinklers are furnished subject to misuse, improper instal- based upon Order Length as lation, corrosion, or which have not measured from the face of the been installed, maintained, modified wall to the face of the sprinkler or repaired in accordance with appli- fitting (Figure 2, 3, and 4).After the cable Standards of the National Fire measurement is taken, round it to Protection Association, and/or the the nearest 1/4 inch increment. standards of any other Authorities •Inlet Thread Connections Having Jurisdiction. Materials found 1-Inch NPT or 7-R1 by TFPP to be defective shall be either repaired or replaced, at TFPP's sole •Temperature Rating option. TFPP neither assumes, nor •Sprinkler Finish authorizes any person to assume for it, any other obligation in connection •Escutcheon Type with the sale of products or parts of •Part Number from Table E. products. TFPP shall not be respon- • sible for sprinkler system design errors Sprinkler Wrench or inaccurate or incomplete infor- Specify W-Type 8 Sprinkler Wrench, mation supplied by Buyer or Buyer's P/N 56-010-4-118. representatives. In no event shall TFPP be liable, in Sprinkler Boot In contract,o ev tort, strict liability or liable, in Specify Model DSB-2 Dry Sprinkler any c tort, theory,li for incidental,under Boot, P/N 63-000-0-002. This Part indirect,y th special or consequential Number includes one Boot,two Strap damages, including but not limited to Ties,and 1/3 oz. ffAdntfor ns(quantity labor charges, regardless of whether of Boot)ve is sufficient for installing TFPP was informed about the possi- bility one Boot). of such damages,and in no event shall TFPP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,express or implied, including warranties of merchantability and fitness for a partic- ular purpose This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components,whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part,of any portion of this warranty will not affect the remainder. 93 CAMP PARSONS MATERIAL SUBMITTAL TFP550 JOB#1406073 Page 8 of 8 • P/N* 61 - XXX - X - XXX SPRINKLER ESCUTCHEON FINISH FINISH(1) MODEL/SIN 1 NATURAL BRASS BRASS PLATED 161 Flush Escutcheon TY5339 (1"NPT),155°F(68°C) 4 WHITE POLYESTER WHITE COATED 183 Flush Escutcheon TY5339 (1"NPT),200°F(93°C) 9 CHROME PLATED CHROME PLATED 171 Deep Escutcheon TY5339 (1"NPT),155°F(68°C) 0 CHROME PLATED WHITE COATED 173 Deep Escutcheon TY5339 (1"NPT),200°F(93°C) 151 Without Escutcheon TY5339 (1"NPT),155°F(68°C) Without Escutcheon ORDER 153 TY5339 LENGTH(2) (1"NPT),200°F(93°C) 055 5.50" Notes 082 8.25" ' Use Prefix"I"for ISO 7-R1 Connection;for example,I-61-161-1-055. 1. Does not apply to assemblies without escutcheon. 180 18.00" 2. Dry-Type Sprinklers are furnished based upon"Order Length"as measured per Figures 2,3,and 4.After the measurement is taken,round it to the nearest 1/4 inch 187 18.75" increment. 372 37.25" 480 48.00" TABLE E SERIES DS-3 HORIZONTAL SIDEWALL, DRY-TYPE SPRINKLERS (ECOH) — PART NUMBER SELECTION - • Copyright®2011 Tyco Fire Protection Products.All rights reserved. VICO TEFLON is trademark of The DuPont Corporation. 94 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • Vico Fire & Building Products Technical Services:Tel:(800) 381-93121 Fax (800) 791-5500 Model 513 (13) Riser Manifold 1-1/2 thru 6 Inch (DN40 thru DN 150) For NFPA 13 Sprinkler Systems General Technical Description Data � ® The Figure 513 (13) Riser Manifolds Approvals described in this technical data sheet The Figure 513 (13) Riser Manifolds provide the necessary waterflow with a cover tamper switch for the wa- alarm, pressure gauge, alarm test ori- terflow alarm switch are UL Listed, • Tice, drain, and sight glass equipment ULC Listed, and FM Approved. ..• in a single assembly for use in NFPA The Figure 513 (13) Riser Manifolds ,. 1 13 sprinkler systems as follows: . . without a cover tamper switch for the NFPA 13` waterflow alarm switch are UL Listed "1111 and FM Approved. 7.... • 1-1/2 Inch (DN40) Male Thread x Female Thread Maximum Working Pressure • 1-1/2 thru 6 Inch (DN40 thru DN150) 175 psi (12,1 bar) Groove x Groove Test Orifice 5.6K(80K) 'Although the Riser Manifold described in Assembly nections and/or listed mechanical this data sheet is intended for NFPA 13 The manifold body of the Figure 513 is grooved connections, as applicable sprinkler systems,it may be used for NFPA ductile iron, whereas the manifold 13D or 13R residential sprinkler systems, body of the Figure 13 is cast iron.The Step 2. Connect the drain line, and w a test orifice of 5.6K MK))is accept- two assemblies are completely inter- then close the drain valve. abhere le. changeable in function, application, Step 3. Refer to Figure 3 for wiring The variety of sizes and grooved end and end-to-end laying length. guidance. All wiring must be per- connections allow cost effective and Finish formed in accordance with the Author- easy transition to check valves,control Red painted. ity Having Jurisdiction and/or the Na- valves, and system piping. The Riser tional Electrical Code. Manifolds may be installed in either the Installation Step 4. Refer to Figure 4 for optional horizontal (flow switch on top)or verti- relief valve. cal (flow going up) for both single sprinkler rises and floor control in high The Riser Manifolds may be installed Step 5.Place the system in service by rises. in either the horizontal (flow switch on filling the system with water.When fill- top) or vertical (flow going up). The ing the system, partially open the con- WARNING inlet of the Riser Manifold may be di- trol valve to slowly fill the system. Fill- The Riser Manifolds described herein rectly connected to a shut-off control ing the system slowly will help avoid must be installed and maintained in valve. damaging the waterflow alarm switch. compliance with this document, as NOTES After the system is fully pressurized, well as with the applicable standards completely open the control valve. of the National Fire Protection Asso- Where applicable pipe thread sealant ciation, in addition to the standards of is to be applied sparingly. Use of a Step 6. Secure all supply valves any other authorities having jurisdic- non-hardening pipe thread sealant is open. tion. Failure to do so may impair the recommended. performance of these devices. Never remove any piping component The owner is responsible for maintain- nor correct or modify any piping defi- ing their fire protection system and de- ciencies without first depressurizing vices in proper operating condition. and draining the system. • The installing contractor or sprinkler Step 1. Install the manifold body with manufacturer should be contacted the flow arrow pointing in the down- with any questions. stream position using threaded con- Page 1 of 6 APRIL6 2006 TFP962 CAMP PARSONS MATERIAL SUBMITTAL Page 2 of 6 JOB#1406073 TFP962 NO. DESCRIPTION QTY- P/N • 1 1-1/2"Manifold Body, Male x Female NPT 1 N/A NOTES: Grooves Groove 1 N/A 1. Approximate weight,11.2 lbs.(5,1 kg). 2 Watertlow Alarm Switch: 2. ULC Listed Manifolds are equipped with VSR-SF with Paddle. Cover Tamper Switches installed internal UUFM 1 971-096-00 to the Waterflow Alarm Switches. VSR-SF with Paddle and Cover Tamper Switch, 3. CH:Common Hardware ULC/FM 1 976-519-02 3 300 psi/2000 kPa Water Pressure Gauge .. 1 2341 3 / F. z 10"(254,0 mm) I -- �•P I. lin 14-1/4" Male x Female NPT. I ,_ (362,0 mm) Groove x Groove Manifolds ' I. t3 all 11-1/8"(282,6 mm) Inspector's Test all; Malex Male NPT &Drain Valve m■®0 Drain Valve Manifolds (Normally set ■.-4 i (Normally to"Drain") 4 Closed) 061 O 1 O EJ } 2 • 3/4" 5.3/16" (19,1 mm) NPT (131.6 mm) (88.9 mm) f 6-118" _ (155,6 mm) 12-5/8" (320,7 mm) FIGURE 1 1-7/2 INCH(DN40)RISER MANIFOLD ASSEMBLY AND DIMENSIONS • 97 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Page S of 6 TFP962 • 2 INCH(DN50)MANIFOLD 4 INCH(DN100)MANIFOLD 6 INCH(DN150)MANIFOLD NO. DESCRIPTION QTY. PIN NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N 1 2"Manifold Body. 1 4"Manifold Body, 1 6"Manifold Body, Groove x Groove 1 N/A Groove x Groove 1 N/A Groove x Groove N/A 2 Waterflow Alarm Switch: 2 Water(low Alarm Switch: 2 Water(low Alarm Switch: VSC with Paddle, VSC with Paddle, VSC with Paddle, UL/FM 1 976-357-04 UUFM 1 976-357-05 VSC w 1 976-357-01 UUFM VSC with Paddle and VSC r with Paddle i and VSC v with Paddle and Cover Tamper Switch, Cover Tamper Switch, Cover Tamper Switch, ULC/FM 1 976-520-01 ULC/FM 1 976-520-04 ULC/FM 1 976-520-05 3 300 psi/2000 kPa 3 300 psi/2000 kPa 3 300 psi/2000 kPa Water Pressure Gauge .. 1 2341 Water Pressure Gauge .. 1 2341 Water Pressure Gauge .. 1 2341 2-112 INCH(DN65)MANIFOLD Manifold Nominal Installation Dimensions in Inches and(mm) Drain Size lb s.Weight Size A B C D E F G H t NO. DESCRIPTION QTY. PIN 2 Inch 16-314 13 9/16 5-3/6 6-3/8 13-1/16 3-112 1"NPT 13.5 1 2-112"Manifold Body. (DN50) (425,5) (330,2) (14,3) (136,5) (161,9) (331,8) (88,9) (6.1) Groove x Groove 1 NIA 2.112 Inch 17-3/16 13 1 5-3/4 6-7/8 13-3/4 3-1/2 1.1/4,.NPT 16.8 2 Waterflow Alarm Switch: (DN65) (436,6) (330,2) (25,4) (146,1) (174,6) (349,3) (88,9) (7.5) VSC with Paddle, 3 Inch 17-3/16 13 1 6 7-1/8 14-1/4 3-1/2 1.1/4"NPT 18.7 UUFM 1 976-357-02 (DN80) (436.6) (330,2) (25.4) (152,4) (181,0) (362,0) (68,9) (6.5) VSC with Paddle and Cover Tamper Switch, 4 Inch 20-1/2 13 4-5/16 7-9116 9-1/16 16-5/6 4-1/2 2"NPT 32,8) ULC/FM 1 976-520-02 (DN100) (520.7) (330,2) (109.5) (192,1) (230,2) (422,3) (114,3) 3 300 psi/2000 kPa 6 Inch 20-1/2 13 4-5/16 8-1/2 10 18-1/2 6-5/8 2„NPT 41.6 Water Pressure Gauge .. 1 2341 (DN150) (5207) (330,2) (109,5) (215,9) (254,0) (469,9) (166,3) (18,9) 3 INCH(DN80)MANIFOLD NO. DESCRIPTION QTY. P/N 1 3 / • 1 3"Manifold Body, Groove x Groove 1 NIA 2 Waterflow Alarm Switch: VSC with Paddle. ■ . me,i■Illa UUFM 1 976-357-03 _ VSC with Paddle and Drain Valve 7I '-qt> 1� IPi Cover Tamper Switch, (Normally ULC/FM 1 976-520-03 Closed) JO 3 300 r Press rPz Water Pressure Gauge .. 1 2341 i m 2 NOTES: p' m 1. ULC Listed Manifolds are equipped with A1011110) I o _Cover Tamper Switches installed internal B f to the Waterflow Alarm Switches. _ _ 2. CH:Common Hardware E7 1.-� I. [I] , rte.. - m....1 1 - Test C D &Drain Valve (Normally set E to"Drain") H - F • FIGURE 2 2 thru 6 INCH(DN50 thru DN150)RISER MANIFOLD ASSEMBLY AND DIMENSIONS 98 • CAMP PARSONS MATERIAL SUBMITTAL Page 4 of 6 JOB#1406073 TFP962 • SWITCH TERMINAL CONNECTIONS UNINSULATED CLAMPING SEVERED LOOPED SECTION CAUTION: PLATE STRIPPED SINGLE An uninsulated section of a TERMINAL ENDS CONDUCTOR single conductor is not �� SEPARATE CLAMPING permitted to be looped around CONDUCTORS PLATE separate terminal and serve The two , TERMINAL separate connections.The �` wire must be severed to serve 'INCOMING as two separate connections, thereby providing supervision of the connection the event that the wire becomes dislodged from the terminal. OUTGOING IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS CONTACTS SPDT(Form C) END OF LINE LOCAL RESISTOR CONTACT RATING .... 5A @ 125 VAC SIGNAL 2.5A @ 30 VDC DEVICE Er -____ b NO NC NC NO• NC NO COM COM COM POWER CONTROL PANEL NO FLOW NON-SUPERVISED STYLE B/CLASS B CONDITION CIRCUIT SUPERVISED CIRCUIT (SEE NOTE) • NOTE: For supervised circuits,see"Switch Terminal Connections'above.The Waterflow Alarm Switch has two switches,one cart be used to operate a central station,proprietary or remove signaling unit,while the other contact is used to operate a local audible or visual annunciator. COVER TAMPER SWITCH(ULC ASSEMBLIES ONLY) CONTACTS SPDT(Form C) CONTACT RATING .... 3A @ 250 VAC 5A @ 125 VAC 1 mA @ 5 VDC min. NO\ • NC COM CONTACTS SHOWN WITH COVER IN PLACE FIGURE 3 WIRING GUIDANCE 99 ■ CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Page 5 of 6 ' TFP962 • 1-112"(DN40)Manifold Only: NO DESCRIPTION QTY. PIN NO. DESCRIPTION QTY. P/N To install optional Pressure Relief Trim on Relief Valve, a 1-112"(DN40)Manifold,a 1/2"NPT outlet 2 Pressure 1 3/8"Copper Tubing, must be provided by the installer on the 2"(DN50)Manifolds .... 1 971-124-01 175 psi,Nonadjustable . 1 198-066-00 system outlet piping,and a connection back 2-1/2"(DN65)and 3 90°Compression Fitting 3"(DN80)Manifolds .... 1 971-124-02 Fitting 2"Reducing Hex to the manifold drain trim must be fabricated g 2 CH with installer supplied 3/8"copper tubing. 4 4"(DN100)and 1 CH Discard unused trim components. 6"(DN150)Manifolds ... 1 971-124-03 Bushing CH:Common Hardware 3 1/2"NPT Installer Outlet Provided _ System Outlet 1 3 4 !lS Piping Installer !l� • Fabricated 1•I P / 3/a"Copper �T�IIII ;I '- P II Tubing • Ell 2"(DN50),2.112"(DN65), EIS j1u1 �a -3"(DN80),4"(DN700),or <I I> 1100111.9. 6"(DN150)Manifold y '3 l, Manifold iTri _ Drain Trim ... r• ®� I-- I. 1.112"(DN40) /^a erdesi Hi irop61 11,,, (� Manifold � O O all IIIII • FIGURE 4 OPTIONAL PRESSURE RELIEF VALVE Riser Manifold component in the field. Alarm/Flow Test Procedure Care and Only the pressure gauge, waterflow alarm switch, or relief valve can be Step 1.Place the test&drain Valve in Maintenance replaced. If any other problems are the"test"position. encountered the entire riser manifold Step 2. Fully open the drain valve. The following inspection procedure must be replaced. Make certain that drainage water will must be performed as indicated,in ad- The alarm/flow test procedure will re- not cause any damage or injury. dition to any specific requirements of o suit in operation of the associated the NFPA, and any impairment must p Step 3.Verify operation of associated be immediately corrected. alarms. Consequently, notification alarms. must be given to the owner and the fire The owner is responsible for the in- department, central station, or other Step 4. Close the drain valve. spection, testing, and maintenance of signal station to which the alarms are Step 5. Place the test&drain Valve in their fire protection system and de- connected, and notification must be the"drain"position. vices in compliance with this docu- given to the building occupants. ment, as well as with the applicable Step 6. Verify that the residual (flow- Before closing a fire protection system in pressure indicated by the pres- t on Association is of the National Fire Prate n control valve for inspection or mainte- g) p y tion Association (e,g., NFPA 25), in sure gauge is no less that originally addition to the standards of any Hance work on the fire protection sys- recorded for the system when it was authority having jurisdiction. The in- tem that it controls,permission to shut first installed. stalling contractor or product manufac- down the effected fire protection sys- turer should be contacted relative to tem must first be obtained from the Step 7.Close the drain valve. any questions. proper authorities and all personnel Step 8.Verify that the static(not flow- who may be affected by this action ing) pressure indicated by the pres- It is recommended that automatic must be notified. sure gauge is no less that originally sprinkler systems be inspected, After placing a fire protection system recorded for the system when it was Inspection and maintained a qualified in service,notify the proper authorities first installed. nspecc tioan Service in accordance rdance with and advise those responsible for moni- local requirements and/or national taring proprietary and/or central sta • codes. sta- tion alarms. NOTES No attempt is to be made to repair any 100 CAMP PARSONS MATERIAL SUBMITTAL Page 6 of 6 JOB#1406073 TFP962 Limited Ordering Warranty Information Products manufactured by Tyco Fire& Riser Manifold: Building Products (TFBP) are war- Specify; Size (specify), Figure 513, ranted solely to the original Buyer for (specify connection type inlet x outlet) ten(10)years against defects in mate- Riser Manifold (specify - without or rial and workmanship when paid for with) a cover tamper switch for the and properly installed and maintained watertlow alarm switch, P/N (specify). under normal use and service. This warranty will expire ten (10) years NOTES from date of shipment by TFBP. No Orders for Figure 513 may be filled warranty is given for products or corn- with a Figure 73. The two assemblies ponents manufactured by companies are completely interchangeable in not affiliated by ownership with TFBP function, application, and end-to-end or for products and components which laying length. have been subject to misuse,improper installation, corrosion, or which have If a ULC Listing is required, the Riser not been installed, maintained, modi- Manifold must be ordered with a cover fied or repaired in accordance with ap- tamper switch for the water tlow alarm plicable Standards of the National Fire switch. Protection Association, and/or the standards of any other Authorities UL/ULC/FM Assemblies Having Jurisdiction. Materials found With Cover Tamper Switch by TFBP to be defective shall be either 1-1/2 Inch(DN40) repaired or replaced, at TFBP's sole MT x FT P/N 4086 option. TFBP neither assumes, nor 1-1/2 Inch(DN40) authorizes any person to assume for it, Inch( NS x P/N 4087 2I any other obligation in connection with nG x G0) the sale of products or parts of prod- 2-1/2 Inch(DN65) P/N 4090 ucts.TFBP shall not be responsible for G x c P/N 4091 sprinkler system design errors or inac- 3 Inch(Gnleo)G x G P/N 4092 • 4 curate or incomplete information sup- D plied by Buyer or Buyer's repre- Inch P/N 4095 sentatives. 6 Inch(DN150) In no event shall TFBP be liable, in G x G P/N 4096 contract, tort, strict liability or under any other legal theory, for incidental, UL/FM Assemblies indirect,special or consequential dam- Without Cover Tamper switch ages, including but not limited to labor 1-1/2I MT x FT x FT P/N 4055 charges, regardless of whether TFBP 1-1/2 Inch (DN40) was informed about the possibility of MT x MT P/N 4056 such damages, and in no event shall 2 Inch(DN50) TFBP's liability exceed an amount G x c P/N 4060 2 equal to the sales price. 2-1/2 X C (DN65) P/N 4061 The foregoing warranty is made in lieu 3 I Gn(GNao) of any and all other warranties, ex- 4 Inch(DN100) P/N 4062 .r- or u. '-. 'r .•' a I .. .r G x G P/N4065 of merchantability and fitness for a par- 6 Inch(DN150) titular Purpose, c x G PIN floss This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- Optional Pressure Relief Valve: als or components, whether the claim Valve and Operational Trim for use with Relief is made in contract, tort, strict liability Valve igu Trim for 13 web (sp Riser or any other legal theory. size) Figure 513 or 13 Series Riser Manifold, P/N (specify). This warranty will apply to the full ex- tent permitted by law.The invalidity,in 1-1/2'or 2" P/N 4063 whole or part, of any portion of this 2-1/2"or 3" P/N 4072 4"or6° P/N ao73 warranty will not affect the remainder. Replacement Parts: Specify: (description)for use with Fig- ure 513 or 13 Riser Manifold,P/N(Ref. • Figure 1 or 2, as applicable). TYCO FIRE&BUILDING PRODUCTS,451 Nor Cannon hCannon Avenue,Lansdale,Pennsylvania 19446 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • SECTION 2. 5 • AUTOMATIC DRAIN DEVICE • 102 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 Brass Trim ■ 1,0 [��� CI Miscellaneous Brass F P P 1' • Ball Drips, Brass FPPI Ball Drips feature two piece brass construction. Their designed use is to prevent moisture accumulation on the"dry'side of Fire . Department Connections when used in conjunction with an approved li check valve. Part No. Description Box Qty. i 08-540-00 11/2" IPS Ball Drip 10 08-541-00 3/4" IPS Ball Drip 10 08-542-00 1/4"x 1 6" IPS Ball Drip 20 z s Extension Nipples, Brass Designed to be used to correct sprinkler head elevation without , eq t= removing or re-cutting sprinkler drop.THIS PRODUCT IS COVERED P ,: ; _ N BY ADDITIONAL DISCLAIMERS REGARDING SUITABILITY AND "'"t - rti USE. PURCHASER AND USER TAKE FULL RESPONSIBILITY FOR - 0 THE USE OF THIS PRODUCT. FPPI WILL NOT BE HELD LIABLE ' FOR PRODUCT FAILURE OR DAMAGE CAUSED BY USE. SEE ' MSDS FOR DETAILS. W r n ' A E o .... Part No. Description Box Qty. �? 08-570-00 1h" takeout x 1/2" IPS Br. Spr. Ext. 100 Q G 08-571-00 3/4" takeout x 1/2" IPS Br.Spr. Ext. 75 ";♦ 08-572-00 1" takeout x 1/2" IPS Br. Spr. Ext. 50 ?� 08-573-00 11/2" takeout x W IPS Br. Spr. Ext. 50 • 08-574-00 2" takeout x 1" IPS Br. Spr. Ext. 25 CV 08-575-00 1/21" takeout x 3/4" IPS Br. Spr. Ext. 50 cV co 08-576-00 3/4" takeout x 34" IPS Br. Spr. Ext. 50 er •cl- M Orifice Union c Part No. Description Box Qty. co 08-537-00 Orifice Union 1" IPS x1/2" 5 08-539-00 Orifice Union 1/2" IPS x 3/32" �-- i ' 10 t"iS"� -1„,,,,"°r Sight Glass, Brass FPPI Sight Glasses feature brass construction with Lexan view windows for observation of flow. Typical use is for the sprinkler systems Inspectors'Test trim.Available in straight and restricted orifice patterns. Part No. Description Box Qty. i ° 08-529-00 1" Sight Glass MxF 3 % .. 4.14'r A,.,10 • 08-530-00 1" IPS Sight 1/2" Orifice FxF 5 08-532-00 1" Sight Glass 1762" Orifice FxF 5 I 08-531-00 11%" IPS Sight Glass MxF 4 08-533-00 11/2" IPS Sight Glass FxF 1 • 08-535-00 2" IPS Sight Glass FxF 1 103 19 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • HANGERS AND SWAY • BRACING • 104 ® TOLCO www.tolco.com NIBCO Revision 12/18/2008 Fig. 200 - "Trimline" Adjustable Band Hanger Fig. 200R (Import) - "Trimline" Adjustable Band Hanger c 0 U9L1SrEo w/Retainer Ring .4:00• Size Range — 1/2" thru 8" pipe Material — Carbon Steel, Mil. Galvanized to G90 specifications Function — For fire sprinkler and other general pipin g _ ,, `J purposes. Knurled swivel nut design permits hanger adjustment after installation. Features — -� • (1/2" thru 2") Flared edges ease installation for ' ' B ' all pipe types and protect CPVC plastic pipe s / i i ! �; from abrasion. Captured design keeps adjusting I %j %i nut from separating with hanger. Hanger is eas- ily installed around pipe. '.__:;'' A • (2h/2" thru 8")Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. Fig.2001"-2" Fig.200 21"-8" Approvals — Underwriters' Laboratories listed (1/2" thru 8") in the USA(UL)and Canada(cUL) for steel and CPVC plastic pipe and Factory Mutual �U�• Engineering Approved (3/4" thru 8"). Conforms to �+ Federal Specifications WW H-171 E, Type 10 and 8 U1_ • Manufacturers Standardization Society SP-69, Type =- �`' 10. B 1 Maximum Temperature — 650°F 1`' /// Finish — Mil. Galvanized. Stainless Steel materials will be supplied with (2) hex nuts in place of a knurl nub. Order By — Figure number and pipe size Note — Figure 200R (import) with retainer ring and non-captured knurl nut. A ti - \\_ Fig.200R 21 -8" Fig.200R 1/2"-2" Dimensions•Weights Pipe Rod Size Max.Rec. Approx. Size Inch Metric A B Load Lbs. Wt./100 1/2 3/8 8mm or 10mm 31% 2% 400 11 3/4 3/8 8mm or 10mm 31/2 21 400 11 1 3/8 8mm or 10mm 3% 2% 400 12 11/4 3/8 8mm or 10mm 33/4 27/s 400 13 11/2 3/8 8mm or 10mm 3% 2% 400 14 2 3/8 8mm or 10mm 41% 3 400 15 21 3/8 10mm 5% 41/4 600 27 3 3/8 10mm 5% 4 600 29 31/2 3/8 10mm 73/s 51% 600 34 4 3/8 10mm 7% 5 1000 35 5 1/2 12mm 91/2 61/4 1250 66 • 6 1/2 12mm 10175 63/4 1250 73 8 1/2 12mm 131/2 83/4 1250 136 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AM.CORONA,CA 92879•PH. 951 737 5599•FAX 951.737.0330 CUSTOMER SERVICE•800 786 5266 wwwtolco.com WIN MITT RSTM nt I r..., rt --4.---1.mgalr,i +Ririt,,P''''SI D E R�t ALA C) u N T 'good Nut Driver 1/4" 8018957 4016 SWG 100 1/4 X 1 25 9.38 125 Use#14SVVNut Dneer 1/4" 8019957 300 SWG200 1/4X2 25 10.00 125 fa Sidewinders and 1/2'Rod Sarnmys 3/8" 8020957 18 SWG 10 1/4 X 1 25 7.50 125 Ait. 3/8" 8021957 19 SWG 20 1/4 X 2 25 8.75 125 ,,,- 3/8" 8022925 26 SWG 25-380 3/8 X 2-1/2 25 12.81 125 3/8" 8023925 25 SWG 30 1/4 X 3 25 10.63 125 �; g steel 3/8" 8050957 39 SWD 10 1/4-14 X 1 25 7.50 125 3/8" 8051957 40 SWD 15 1/4-14 X 1-1/2 25 9.38 125 Part#8114910 3/8" 8052957 41 SWD20 1/4-14X2 25 8.13 125 Item#101 3/8" 8053957 42 SWD 516 5/18-18 X 1-1/4 25 815 125 3/8" 8054957 46 SWDR 1-1/2" 1/4-20X1-1/2 25 9.06 125 3/8" 8055957 43 SWDR 1" 1/4-20 X 1 25 8.75 125 4' 3/8" 8056957 44 SWDR 516 5/16-18 X 1-1/4 25 10.31 125 ill 3/8" 8057957 45 SWT 15 12-24 X 1-1/2 25 7.81 125 Approvals Size Part# Item# Model Screw Box Weight Case ff_y Descriptions Q . (per 125) Qty C. oncrete 1/4" 8062957 1900 SWC 200 E/1 ■X 1-1!2 25 9.38 123 ID 3/8" 8061957 65 SWC 20 5/16 X 1-1/2 25 9.38 125 • Most Items Available in Stainless Steel s. NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! * Use with 3/8" Sammy Swivel HeadTM 0 Approvals Part# Item# Model Screw Box Weight Case Descriptions Qty. (per 125) Qty U.S.Patent No • 17°deflection from vertical " 6,443,680 • Accommodates up to 8139957 4702 SH-GST 20 1/4 x 2 25 9.38 125 't. 3-1/2 x 12 pitch roof ' 8140957 4703 SH-GST22SS 1/4x2 25 9.38 125 • Also available in stainless steel 8141957 4704 SH-GST 30 1/4 x 3 25 10.94 125 ' 8142957 4705 SH-GST 30SS 1/4 x 3 25 10.94 125 • Use#14 Nut Driver(black) 'W° 8137957 4700 SH-DSTR 1 1/4-20 x 1 25 9.38 125 ▪ 8138957 4701 SH-DSTR 1-SS 1/4-20 x 1 25 9.38 125 dedRodDirecti Patent Pending SAMMY X-PREssTM Threa eMetat Steel Screw Box Weight Case Nang Gaug Approvals Part# Item# Model g tromThnn purhn a Gam Descriptions Qty. (per 125) Qty. peck& It ":tom �?`h_D.1 ,w'"" 75TEEt i.F- ,, Ut., 22-20 8150922 500 XP 20 1/420 x 1-1/8 25 10.3 125 Sammy X-Press 20 , 18-18 8153922 503 XP 35 1/4-20 x 1-1/8 Sammy X-Press 35 25 10.3 125 • Uninstalled . ``�1 ,r •` Sammy X-Press It 8151910 501 XPIT 1 1.02 1 SIAMM Installation Tool RE4M TN ° (Kit includes:Sleeve,Bit Receiver, Hex Wrench,and 25/64"Drill Bil) Installed 8152910 502 XPDB 25/64"Drill Bit 1 0.14 1 107 SAMMYSTM t t i i ! od Appra 1/4" 8001957 20 GST.750 1/4 x 3/4 25 5.93 125 1/4" 8002957 21 GST 100 1/4 x 1 25 6.25 125 1/4" 8003957 22 GST 200 1/4 x 2 25 8.13 125 1/4" 8004957 23 GST 300 1/4 x 3 25 9.38 125 1/4" 8005925 24 GST 600 1/4 x6 25 11.25 125 3/8" 8006957 10 GST.750 1/4 x 3/4 25 5.63 125 3/8" 8007957 11 GST 10 1/4 x 1 25 5.93 125 NFPA 3/8" 8008957 12 GST 20 1/4 x 2 25 7.50 125 NFPA 3/8" 8009925 27 GST 25-380 3/8 x 2-1/2 25 11.56 125 NFPA 3/8" 8010957 30 GST 30 1/4 x 3 25 8.75 125 NFPA 3/8" 8011925 403 GST 40 1/4 x 4 25 10.00 125 NFPA 3/8" 8012925 14 GST 60 1/4 x 6 25 11.25 125 1/2" 8013925 8 GST 2 1/4 X 2 25 8.75 125 1/2" 8014925 6 GST 2.5-380 3/8 X 2-1/2 25 12.50 125 1/2" 8015925 15 GST 3 1/4 X 3 25 13.13 125 1/2" 8016925 16 GST 4 1/4 X 4 25 13.25 125 1/2" 8017925 17 GST 6 1/4 X 6 25 13.69 125 steel • 1/4" 8024957 50 DSTR 100 1/4-20 X 1 25 7.81 125 1/4" 8025957 51 DST 100 1/4-14 X 1 25 6.56 125 1/4" 8026957 52 DST 150 1/4-14 X 1-1/2 25 6.88 125 1/4" 8027957 53 DST 200 1/4-14 X 2 25 7.50 125 1/4" 8028957 54 DST 250 1/4-12 X 2-1/2 25 8.44 125 1/4" 8029957 55 DST 300 1/4-14 X 3 25 9.06 125 R 1/4" 8030957 56 TEK 500 12-24 X 1-1/2 25 6.88 125 Nut Driver k " NFPA 3/8" 8037957 29 DSTR 1-1/2" 12-24 X 1-1/2 25 7.75 125 Use#14Nut Driver ,= NFPA 3/8" 8038957 30 DSTR 1" 1/4-20 X 1 25 7.19 125 forSammysand HeadSvovel NFPA 3/8" 8039957 31 DSTR 516 5/16-18 X 1-1/4 25 7.06 125 NFPA 3/8" 8040957 32 DST 10 1/4-14 X 1 25 5.94 125 NFPA 3(8" 8041957 33 DST 15 1/4-12 X 1-1/2 25 6.56 125 NFPA 3/8" 8042957 34 DST 20 1/4-14 X 2 25 6.88 125 NFPA 3/8" 8043957 35 DST 25 1/4-14 X 2-1/2 25 7.81 125 NFPA 3/8" 8044957 36 DST 30 1/4-14 X 3 25 8.44 125 .0' NFPA 3/8" 8045957 37 DST 516 5/16-18 X 1-1/4 25 7.50 125 NFPA 3/8" 8046957 38 TEK 50 12-24 X 1-1/2 25 6.88 125 1/2" 8031925 601 DST 2.0 1/4-14 X 2 25 8.44 125 Part#8113910 Item#100 1/2" 8032925 1113 DST 2.5 1/4-4142X0 2-1/2 25 9.06 125 1/2" 8033925 422 DSTR 1.0 1/4-20 X 1 25 6.25 125 1/2" 8034925 28 DSTR 5.16 5/16-18 X 1-1/4 25 10.00 125 1/2" 8035925 443 DST 5.16 5/16-18 X 1-1/4 25 8.44 125 1/2" 8036925 5 TEK 5.0 12-24 X 1-1/2 25 7 50 125 Screw Box Weight Case Approvals Rod Part# Item_# Mode! Descriptions Qty. (per 125) Qty ..loncrete ',' 1 . � t .,: s • 1/4" 8058957 64 CST 200 5/16 x 1-1/2 25 8.44 125 3/8" 8059957 61 CST 20 5/16 X 1-1/2 25 7.81 125 NFPA 1/2" 8060925 66 108 CST 2 5/16 X 1-1/2 25 8.75 125 ® TOLCD NIBCO Revision 3/7/2007 • Component of State of Fig. 4 - Standard Pipe Clamp California OSHPD Approved a®us Ma Seismic Restraints System Fig. 4F - Standard Pipe Clamp Felt Lined 4> . Fig. 4PVC - Standard Pipe Clamp PVC Coated Size Range — (Fig. 4) Size 1/2" thru 30" pipe. Size Range — (Fig. 4F) Size 1/2" thru 21/2" copper tubing Material — Carbon Steel Function — Recommended for the suspension of non-insulated pipe or insulated pipe with Fig. 220 shields. (Use Fig. 330 Weldless Eye Nut, Fig. 102 Eye Rod or Fig. 101 Welded Eye Rod.) Also recommended for attachment of sway bracing up to 31/2" pipe size, for larger pipe sizes use Fig. 4A. Fig. 4F and Fig. 4PVC are designed to reduce noise and vibration and/or prevent electrolysis. Approvals — Underwriters' Laboratories Listed in the USA(UL), Canada(cUL)1/2" -8", l and approved by Factory Mutual Engineering, 3/4" -8". Federal Specification WW-H-171 E, Type 4, 11/2" thru 24" and Manufacturers Standardization Society SP-69,Type 4. Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development(OSHPD1, For additional load, spat- Fig. 4 ing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note — When the Fig. 4 is used as a sway brace, to ensure performance, the UL Listing requires that it must be used with other TOLCO® r, 1 brace products. : P ' ,r (:). Maximum Temperature — 750°F Finish — Plain • Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, pipe size and finish. Fig. 4F Fig. 4PVC Order Note — When ordering Fig.4F allow for 3/16" felt on each half of clamp. Dimensions•Weights Max.Design Load Lbs. Pipe For Service Temp. Approx. Size A B C D Bolt Size 650° 750°F WtJ100 1/2 37/6 1/4 11/2 11/2 5/16 500 445 29 3/4 39/6 1/4 11/4 11/4 5/16 500 445 31 1 39/2 1/4 V/4 15/16 5/16 500 445 35 11/4 43/16 3/8 13/e 111/46 5/16 500 445 40 11/2 49/5 3/8 1% 11 5/16 800 715 42 2" 59/16 3/8 2 21/4 3/8 1040 930 93 21/2« 67/6 3/8 21/2 23/4 1/2 1040 930 126 3° 7 3/8 23/4 31Ae 1/2 1040 930 141 31/2° 7t1/A6 3/8 31/a 31/2 1/2 1040 930 154 4 81/2 5/8 35/16 311/1, 1/2 1040 930 229 5 93/4 3/4 37/e 41 5/8 1040 930 261 6 11% 3/4 47/e 51/2 3/4 1615 1440 537 8 136/6 1 5% 6 3/4 1615 1440 625 10 161/2 1 71/4 71/4 7/8 2490 2220 1378 12 181 1 81/4 81/4 7/8 2490 2220 1574 14 20 11/2 9 9 7/8 2490 2220 2103 16 23 11/2 101/4 101/4 7/8 2490 2220 2314 18 257/a 11/4 111h 111 1 3060 2730 3276 20 26 11/2 121 121/2 11/2 3060 2730 3863 • 24 331h 15/e 151/4 151/a 1/a 3060 2730 5222 30 411 2 19 19 13/4 3500 3360 10511 'Meets UL 203A requirements for attachment of sway bracing. Horizontal design load for 1/2'-2"-380#,21/2"-395#,3"-435#,31/2'-540# OFRCE)MANUFACTURINO FACILITY•1375 SAMPSON MAO CORONA,CA 92879•PH: 951.737.5599•FAX 951 737 0330 CUSTOMER SERVICE•800 786 5266 II www.toko.com ®TOLCO Fig. 4A - Pipe Clamp for Sway Bracing Component of State of CaliforniaOSHPDApproved c®in Seismic Restraints System Size Range — 4"thru 8" pipe. For sizes smaller than 4"use TOLCO®Fig.4. LOUD Material — Carbon Steel Y Function — For bracing pipe against sway and seismic disturbance. ,r l�.f Approvals — Underwriters' Laboratories Listed in the USA(UL)and Canada(cUL) ,:- 4"thru 8". Included in our Seismic Restraints Catalog approved by the State of /` 1 California Office of Statewide Health Planning and Development(OSHPD). +# 1 Installation Instructions —The Fig.4A is the"braced pipe"attachment / �'/ \ \1 A component of a longitudinal, lateral or riser brace assembly. It is intended to a be combined with the"bracing pipe"and TOLCO transitional and structural attachment component(s)to form a complete bracing assembly.NFPA 13 and/or i / j OSHPD guidelines should be followed. ' `- J I To Install — Place the Fig.4A over the pipe to be braced.Attach TOLCO `'- transitional fitting,either Fig.980,910 or 909,to the clamp ears.Tighten bolts and h nuts;torque requirement is a minimum of 50 ft.lbs.Transitional fitting attachment can pivot for adjustment to proper brace angle. _ I Finish — Plain Note— Available in Electro-Galvanized and HDG finish or Stainless Steel materials. C Order By— Figure number,pipe size and finish • ?3 ^ 1 /a P' r / / iY �Pp Fig.4A-Longitudinal Brace 1 Fig.4A-Lateral Brace Cooper B-Line,Inc.'s("Cooper B-Line")seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components, resulting in a listed seismic bracing assembly.Cooper B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty, Cooper B-Line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. Dimensions •Weights Pipe Max.Horizontal Approx. Sizes A B C D Bolt Size Design Load Wt./100 4 81 %c 31 3''t 1/2 1600 221 5 9 V. tis 31 4 Ye 1/2 1600 253 6 111 Vs 5 5/ Y2 2015 513 8 1314 3/4 6"As 6A 'Y2 2015 601 COOPER B-LINE 1375 Sampson Ave•Corona,CA 92879•800.786.5266•FAX:951.737.0330 • www.tolco.com 12 COOPER B-Line (its TOLCO www.toico•com NIBCO Revision 12/3/2008 • Fig. 1001 - Sway Brace Attachment Component of State of C OOS LISTER California OSHPD Approved Seismic Restraints System 4>eis Size Range — Pipe size to be braced: 2'h" thru 8" IPS.* Pipe size S used for bracing: 1" and 11/4" Schedule 40 IPS. Material — Carbon Steel Function — For bracing pipe against sway and seismic distur- bance. The pipe attachment component of a sway brace system: The Fig. 1001 is used in conjunction with a TOLCO 900 Series fitting and joined together with bracing pipe per NFPA 13, forming a com- plete sway brace assembly. t`�Features — Can be used to brace schedules 7 through 40 IPS. Field adjustable, making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no threading of brac- ing pipe. Can be used as a component of a four-way riser brace. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation. See installation note below. Installation Note — Position Fig. 1001 over the pipe to be braced and tighten two hex head cone point set bolts until heads bottom out. A minimum of 1" pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Maximum Design Load Approvals — Underwriters Laboratories Listed in the USA(UL) Sch. 7 - 1600 lbs. and Canada(cUL). Approved by Factory Mutual Engineering (FM). Sch. 10 &40 w/1" Brace Pipe 2015 lbs. Included in our Seismic Restraints Catalog approved by the State Sch. 10&40 w/11/4" Brace Pipe 2765 lbs. of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information FM Approved Design Loads* • relating to OSHPD projects, please refer to the TOLCO Seismic 2t/2" 2400 lbs. Restraint Systems Guidelines. 3" - 4 -2500 lbs. Finish — Plain 5" - 8" - 1500 lbs. Note — Available in Electro-Galvanized and HDG finish. Order By — Indicate pipe size to be braced followed by pipe size used for bracing,figure number and finish. Important Note — The Fig. 1001 is precision manufactured to perform its function as a critical component of a complete brac- ing assembly. To ensure performance.the UL Listing requires that the Fig. 1001 must be used only with other TOLCO bracing products. The Fig 1001 Is not intended for use with the Fig.907 4-Way Longitudinal Brace Attachment. r (K1 . P .W t _Y ( , r S \') I • ® OFRCE/MANUFACTURING FACILITY•1375 SAMPSON AVE1-090RONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0338 CUSTOMER SERVICE•800.786.5266 www.tofco.com ® TOLCO - NIBCO Revision 3/10/2010 • Component of State of Fig. 906 - Sway Brace Multi-Fastener Adapter California OSHPDApproved c0 us um Seismic Restraints System Size Range — Use with 1" and 11/4" TOLCO UL listed Fig. 900 Series Earthquake Brace Attachments. Material — Carbon Steel Application — Allows sway brace fittings to develop greater load carrying ability by providing multiple fastener attachments. The National Fire Protection (NFPA) provides information on fastener loads to various structures. Refer to NFPA 13 (2010)9.3.5.9.1. Approvals — Underwriters Laboratories Listed in the USA H1 (UL)and Canada (cUL) only when used with TOLCO 900 B ill Series Earthquake Brace Attachments. Included in our Seismic Restraints Catalog approved by the State of California dr r Office of Statewide Health Planning and Development D (OSHPD). For additional load, spacing and placement infor- mation relating to OSHPD projects, please refer to the TOLCO ,,,,, 0. Seismic Restraint Systems Guidelines. Installation Instructions — The Fig. 906 is a multiple fastener structural attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with a H1 TOLCO transitional attachment, "bracing pipe" and a TOLCO "braced pipe" attachment to form a complete bracing assem- A bly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Attach the Fig. 906 to the structural surface as C per fastener design guidelines. Attach other TOLCO transi- tional attachment fitting Fig. 909, 910, 980 or 986. Transitional • fitting attachment can pivot for adjustment to proper brace angle. Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number and specify dimensions H1 and H2. Dimensions •Weights Approx. A B C D H1 H2 WtJ100 12 9 2 1/4 Specify Specify Varies TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components,resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components,in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any • kind,including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFRCEJMANUFACTURING FACILITY•1375 SAMPSON AV9.6 CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.786.5266 WWW.WOICO.COm ® T O O www.tolco.com NIBCO Revision 1/21/2011 • Fig. 980 - Universal Swivel Sway Brace Attachment c .�L US LISTED Size Range — One size fits bracing pipe l'' thru 2", TOLCO 12 gauge channel, and all structural steel up to 1/4" thick. Component of State of Material — Carbon Steel �` California OSH of Approved Function — Multi-functional attachment to structure or Seismic Restraints System braced pipe fitting. Features — This product's design incorporates a concen- : . H tric attachment opening which is critical to the performance of structural seismic connections. NFPA 13 (2010) 9.3.5.8.4 . indicates clearly that fastener table load values are based I (al\` only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. Ilitil 006,1/4 Installation — The Fig.980 is the structural or transitional A attachment component of a longitudinal or lateral sway B brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until set bolt head breaks off. Attachment can pivot for adjustment to proper brace angle. Approved by Factory Mutual Approvals — Underwriters Laboratories Listed in the USA(UL) and Canada (cUL). App Y N Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office • of Statewide Health Planning and Development(OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000, Fig. 2002, Fig. 4A, Fig. 4B or Fig. 4L Pipe Clamp make up a sway brace system of UL Listed attachments and bracing materials which satisfies the require- ments of Underwriters' Laboratories and the National Fire Protection Association (NFPA) Finish — Plain �` _ Note — Available in Electro-Galvanized finish. ,.;, Order By — Figure number and finish. / Pat.#6,273,372, Pat.#6,517,030, Pat.#6,953,174, Pat.#6,708,930,Pat.#7,191,987,Pat.#7,441,730, �I � , y , Pat.#7,669,806 Lateral Brace Dimensions •Weights Max. Design Max. Design Approx. A B H* Load Lbs. Load Lbs.** Wt./100 (cULus) (FM) 51/4 11/2 17/32 2765 2800 132 Available with hole sizes to accommodate up to 3/4"fastener. Consult factory. "*The loads listed are axial loads on the brace.The horizontal load capacity, H,of the brace is:H=F x sin 0,where 0 is the installation angle measured from the vertical. TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components,resulting in a Listed seismic bracing assembly. DISCLAIMER— NIBCO does NOT warrant against the failure of TOLCO®brand bracing components,in the instance that such TOLCO®brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under • the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON Ails CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.786.5266 www.rolco.com CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 • SUPERVISORY DEVICES • • 119 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 P P011ER BELLS The Symbol of Protection PBA-AC & MBA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC f' 12VDC(10.2 to 15.6)Polarized 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm General Signaling Burglar Alarm Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWG stranded wires �L 0ro DC Bells-Terminal strip ' Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model B111(-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA-6-12 1750070 .12A 85 76 8(200) 12VDC MBA-8-12 1750080 .12A 90 77 10(250) 12VDC MBA-10-12 1750060 .12A 92 78 6(150) 24VDC MBA-6-24 1750100 .06A 87 77 8(200) 24VDC MBA-8-24 1750110 .06A 91 79 10(250) 24VDC MBA-10-24 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing WlARNI G In outdoor or wet installations,bell most be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company, LLC • St. Louis, MO, • Phone: 866-572-3005/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400776-REV V-I PAGE 1 OF 2 01/13 120 CAMP PARSONS MATERIAL SUBMITTAL JOB#1406073 P POTFER BELLS ' ® The Symbol of Protection PBA-AC & MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. 1 Fig.3 A.C. BELLS in" wxITEONI �� :ii:(2U0) " CAMON: J 211/16•• I� WHEN ELECTRICAL SUPERVISION IS REQUIRES USE IN AND OL I L I AD,AS SHOWN. I (68) DINGS OR! NOTES) 1.WHEN USING AC BELLS.TERMINATE EACH EXTRA WIRE SEPARATE LVAE I ER LAST BELL. 2.ENIXOF-LINE RESISTOR IS NOT REOUIREDON AC BELLS. Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP Box has one threaded I/2"conduit entrance At Ii,• _____.. R S.5/c 0 _ 33/8 5^ (1461 (55) (1271 __ ToNext Device or End-of-Line ITS � .• Resistor SIR" l lR (all (86) 4 114" UWUP 7742 os) Installation I. The bell shall be installed in accordance with NFPA 13,72,or local AEU.The top of the device shall be no less than 90"AFT and Inot less than 6"below the ceiling. 2. Remove the gong. x / 3, Connect wiring(see Fig.3). 4. Mount bell mechanism to backbox(bell mechanism must be �D mounted with the striker pointing down). 0 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). g 6. Test all bells for proper operation and observe that they can aBxa be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). AWARNING Failure to install striker down Ai,ilI prevent hell Iron)operating. IP PRINTED IN USA MFG.#5400775-REV Y-I PAGE.2 OF 2 01!13 121