HomeMy WebLinkAboutBLD2020-00498 - 07 STRUCTURAL CALCSDigitally signed
by David L.
Starkel
Date: 2020.09.08
15:46:59 -07'00'
ASCE 7 Hazards Report
Address:
6892 Flagler Rd
Nordland, Washington
98358
Standard:ASCE/SEI 7-10
Risk Category:II
Soil Class:D - Stiff Soil
Elevation:35.01 ft (NAVD 88)
Latitude:
Longitude:
48.04702
-122.69025
Wind
Results:
Data Source:
Date Accessed:
Wind Speed: 110 Vmph
10-year MRI 72 Vmph
25-year MRI 79 Vmph
50-year MRI 85 Vmph
100-year MRI 91 Vmph
ASCE/SEI 7-10, Fig. 26.5-1A and Figs. CC-1–CC-4, incorporating errata of
March 12, 2014
Tue Sep 08 2020
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear
interpolation between contours. Wind speeds are interpolated in accordance with the 7-10 Standard. Wind speeds
correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability =
0.00143, MRI = 700 years).
Site is not in a hurricane-prone region as defined in ASCE/SEI 7-10 Section 26.2.
Mountainous terrain, gorges, ocean promontories, and special wind regions should be examined for unusual wind
conditions.
Page 1 of 3https://asce7hazardtool.online/Tue Sep 08 2020
SS : 1.303
S1 : 0.524
F a : 1
F v : 1.5
SMS : 1.303
SM1 : 0.786
SDS : 0.869
SD1 : 0.524
T L : 16
PGA : 0.54
PGA M : 0.54
F PGA : 1
Ie : 1
Design Response Spectrum
S (g) vs T(s)a
MCE Response SpectrumR
S (g) vs T(s)a
Seismic
Site Soil Class:
Results:
Seismic Design Category
D - Stiff Soil
D
Data Accessed:
Date Source:
Tue Sep 08 2020
USGS Seismic Design Maps based on ASCE/SEI 7-10, incorporating
Supplement 1 and errata of March 31, 2013, and ASCE/SEI 7-10 Table 1.5-2.
Additional data for site-specific ground motion procedures in accordance with
ASCE/SEI 7-10 Ch. 21 are available from USGS.
Page 2 of 3https://asce7hazardtool.online/Tue Sep 08 2020
Snow
Results:
Ground Snow Load, p : 15 lb/ftg
2
Elevation: 35.0 ft
Data Source: ASCE/SEI 7-10, Fig. 7-1.
Date Accessed: Tue Sep 08 2020
Values provided are ground snow loads. In areas designated "case study
required," extreme local variations in ground snow loads preclude mapping at
this scale. Site-specific case studies are required to establish ground snow
loads at elevations not covered.
The ASCE 7 Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of
any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers;
or has been extrapolated from maps incorporated in the ASCE 7 standard. While ASCE has made every effort to use data obtained from
reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability,
currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement,
affiliation, relationship, or sponsorship of such third-party content by or from ASCE.
ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent
professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such
professionals in interpreting and applying the contents of this Tool or the ASCE 7 standard.
In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors,
employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential
damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by
law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data
provided by the ASCE 7 Hazard Tool.
Page 3 of 3https://asce7hazardtool.online/Tue Sep 08 2020
Project Designer
Location Project No.
Client
1.5 PSF 1.0 PSF
1.5 PSF 2.3 PSF
1.5 PSF 3.3 PSF
3.3 PSF 1.3 PSF
1.6 PSF 5.6 PSF
2.2 PSF 1.5 PSF
PSF PSF
PSF 15.0 PSF
11.6 PSF 40.0 PSF
SLOPE CORRECTION "X:12"6.00 1.1
2.0 PSF
15.0 PSF PSF
25.0 PSF PSF
N/A PSF PSF
16.0 PSF PSF
- PSF
PSF
4.0 PSF
1.5 PSF
1.7 PSF PSF
0.8 PSF PSF
0.5 PSF PSF
2.2 PSF PSF
0.3 PSF PSF
11.0 PSF PSF
PSF
- PSF
PSF
4.4 PSF
1.1 PSF
0.5 PSF
0.8 PSF
1.2 PSF
8.0 PSF
SOILS REPORT
GEOTECHNICAL ENGINEER DATE OF REPORT
1,500 PSF N/A PCF
N/A %N/A
N/A %N/A PCF
1,500 PSF N/A PCF
N/A PSF
Floor Covering
Floor Shtg
Floor Joist
Insulation
DESIGN LIVE AND DEAD LOADS
ROOF LOAD :FLOOR LOAD
Asphalt Shingles
Re-Roof
Roof Shtg
Truss @ 24" oc
DLS
20-051
Colden Residence Relocation Foundation
6892 Flagler Rd, Nordland, WA 98358
John Colden Revised 15-Sep-18Design Live and Dead Loads, Soil Data
DECK OR BALCONY DEAD LOAD
EXTERIOR WALL LOAD
SUB-TOTAL
MISCELLANEOUS
ROOF DEAD LOAD
FLOOR LIVE LOAD
DECK DEAD LOAD
DECK LIVE LOAD
Gypsum Sheathing
Mech., Elec., & Misc.
INCREASE FOR DEPTH
MAX. SOIL PRESSURE
ISOLATED FOUNDATIONS
Insulation
Gypsum Shtg
ROOF SNOW LOAD
REDUCED SNOW LOAD
ROOF LIVE LOAD
Siding
N/A
INTERIOR WALL DEAD LOAD
BASIC BEARING PRESSURE
FLOOR DEAD LOAD
INTERIOR WALL LOAD
Wall Shtg
2x6 @ 16" oc
Bottom & Top Plates
Insulation
Gypsum Shtg
Mech., Elec., & Misc.
EXTER. WALL DEAD LOAD
2X4 @ 16" oc
Bottom & Top Plates
Insulation
SOIL FRICTION
N/A
Mech., Elec., & Misc.
INCREASE FOR WIDTH
N/A
SOILS DATA
PADS & CONT. FND
E.F.P. (Cantilever)
E.F.P. (Restrained)
Pacific Northwest
Structural Group, Inc.
ACTIVE SOIL PRESSURE
PASSIVE PRESSURE
FLOOR DEAD LOAD
FLOOR LIVE LOAD
Gypsum Shtg
C:\Users\dlsta\Dropbox\PNW Project Files\2020 Projects\20-051 Colden Foundation\ENGR\20-051 Design Criteria 2018.xlsxLoads
9/8/2020
Project Designer
Location Project No.
Client
110 MPH Figure 1609
Exposure B 1609.4
Roof Pitch 6.00 :12 B C D
θ=26.57
Building Length 46.00 ft
Building Width 25.00 ft
1st Level Plate Height 8.00 ft
2nd Level Plate Height 8.00 ft
3rd Level Plate Height - ft
Gable Height 22.25 ft
Roof Height 6.25 ft
Mean Roof Height h =19.13 ft
0.85
1.00
0.62 ASCE 7-10, 27.3-1
psf
psf
psf
psf
psf
1st Level Plate 146.4 plf 78.6 plf
2nd Level Plate 99.3 plf 70.0 plf
3rd Level Plate - plf - plf
Colden Residence Relocation Foundation DLS
6892 Flagler Rd, Nordland, WA 98358 20-051
John Colden Revised 15-Sep-182015 IBC Section 1609.6 Wind Loads
BUILDING DATA:
Ultimate Design Wind Speed, Vult
Wind directionality factor, Kd
Topographic Factor, Kzt
Velocity pressure factor, Kz
Exposure
Condition 1
1609.6 Alternate All-Heights Method
+ Internal
pressure
- Internal
pressure
0.43 0.73
(0.51) (0.21)
(0.66) (0.35)
Windward Wall
Leeward Wall
Sidewall
Windward roof slopes
(0.66) (0.35)
(1.09) (0.79)
0.06
Wind perpendicular to ridge Leeward roof or flat roof
Wind parallel to ridge and flat roofs
Windward Wall
Leeward Wall
Sidewall
Pressure
18.81
16.38
16.38
6.97
Pacific Northwest
Structural Group, Inc.
Allowable Uniform Wind Load
Level Transverse Longitudinal
11.68
Wind perpendicular to ridge Leeward roof or flat roof
Windward roof slopes
Description
0.37
Description
IBC 2015 Table 1609.6.2, Net Pressure Coefficients, Cnet
C:\Users\dlsta\Dropbox\PNW Project Files\2020 Projects\20-051 Colden Foundation\ENGR\20-051 Design Criteria 2018.xlsxIBC
1609.6 Method
9/8/2020
Project Designer
Location Project No.
Client
Soil Site Class D
Response Spectral Acc. (0.2 sec) Ss 1.30
Response Spectral Acc.( 1.0 sec) S1 0.52
Site Coefficient Fa 1.00
Site Coefficient Fv 1.50
Max Considered Earthquake Acc. SMS 1.303
Max Considered Earthquake Acc. SM1 0.786
@ 5% Damped Design S DS 0.869
S D1 0.524
II
Yes
Yes
Yes
Seismic Design Category (SDC)-
Seismic Design Category for 0.1 sec D
Seismic Design Category for 1.0 sec D
S1 < .75g -
Seismic Design Category (SDC)D
-
-
-
ASCE 7 Section Where Detailing
Requirements Are Specified
Building ht. hn 19.13 ft
Ct 0.020 x 0.75
Cu 1.400
Approximate Fundamental Period, Ta 0.183 sec
Ts 0.603 sec SD1/SDS
TL 16.00 sec
Period for Computing Drift 0.256 sec Cu.Ta
Fundamental Period, T 0.183 sec
0.8Ts 0.483 sec
Response Modification Coef. R 6.50
Design Category Consideration:
Footnotes -
-
ASCE 7-10 11.4.5
Seismic Force-Resisting System
ASCE 7-10 (12.8-7)Ct.(hn)x
ASCE 7-10 Table 12.8-2
for SD1 of 0.524g ASCE 7-10 Table 12.8-1
ASCE 7-10 11.4.5
ASCE 7-10 Table 1-1
15. Light-frame (wood) walls sheathed with wood structural panels rated for shear resistance or
steel sheets
A. BEARING WALL SYSTEMS
ASCE 7-10 11.4.1
ASCE 7-10 Table 11.6-1
In each of the two orthogonal directions, the approximate fundamental period of the
structure, Ta, determined in accordance with Section 12.8.2.1 is less than 0.8Ts,
where Ts is determined in accordance with Section 11.4.5.
Colden Residence Relocation Foundation DLS
6892 Flagler Rd, Nordland, WA 98358 20-051
John Colden
2015 IBC Section 1613 Earthquake Loads Revised 15-Sep-18
Fv.S1
ASCE 7-10 & IBC 2015 Section 1613, EARTHQUAKE LOADS
ASCE 7-10 11.4.2 ( Default=D)
ASCE 7-10 Table 11.4-1
ASCE 7-10 Table 11.4-2
ASCE 7-10 (11.4-1)
ASCE 7-10 (11.4-2)
ASCE 7-10 11.6
Fa.Ss
ASCE 7-10 Figure(s) 22-1
through 22-18
In each of two orthogonal directions, the fundamental period of the structure used
to calculate the story drift is less than Ts.
Diaphragms are rigid as defined in Section 12.3.1 or for diaphragms that are
flexible, the distance between vertical elements of the seismic force-resisting
system does not exceed 40 ft.
ASCE 7-10 (11.4-3)
ASCE 7-10 (11.4-4)
2/3.SMS
2/3.SM1
Risk Category
Pacific Northwest
Structural Group, Inc.
ASCE 7-10 Table 12.14-1
-
ASCE 7-10 11.6
14.1 and 14.5
0.8(SD1/SDS) ASCE 7-10 11.6
Limited Building Height (ft) = 65
ASCE 7-10 11.6
ASCE 7-10 Table 11.6-2
C:\Users\dlsta\Dropbox\PNW Project Files\2020 Projects\20-051 Colden Foundation\ENGR\20-051 Design Criteria 2018.xlsxSeismic
9/8/2020
Project Designer
Location Project No.
Client
Colden Residence Relocation Foundation DLS
6892 Flagler Rd, Nordland, WA 98358 20-051
John Colden
2015 IBC Section 1613 Earthquake Loads Revised 15-Sep-18
Pacific Northwest
Structural Group, Inc.
Over Strength Factor Ωο 3.00
Deflection Amplification Factor, Cdb 4.00
Importance factor IE 1.00
Cs 0.134
T<=TL therefore Cs need not to exceed 0.441
T<TL therefore (12.8-4) N/A N/A
Cs 0.038
S1 < 0.6g (12.8-6) N/A N/A
Use Cs 0.134
Design Base Shear V 0.134 W
Design Service Level Base Shear V 0.094 W
ASCE 7-10 (12.8-2)
ASCE 7-10 (12.8-4)SD1.TL/T2(R/IE)
ASCE 7-10 (12.8-6)
SDS/R/IE
0.044SDS.IE ≥ 0.01
SD1/(T(R/IE))ASCE 7-10 (12.8-3)
ASCE 7-10 (12.8-5)
0.5S1/(R/IE)
ASCE 7-10 (12.8-1)Control
ASCE 7-10 Table 12.14-1
ASCE 7-10 Table 1.5-2, UFC 3-301-01
Table 2-2
ASCE 7-10 Table 12.14-1
C:\Users\dlsta\Dropbox\PNW Project Files\2020 Projects\20-051 Colden Foundation\ENGR\20-051 Design Criteria 2018.xlsxSeismic
9/8/2020
Project Designer
Location Project No.
Client
Ground Snow Load, pg PSF
Exposure Category
Exposure of Roof
Thermal Condition
Risk Category
Snow load importance factor, Is
Snow exposure factor, Ce
Thermal factor, Ct
Flat-roof snow load, pf PSF
Min. Design Flat Roof Snow Load, pm PSF
Design Flat Roof Snow Load, pf PSF
Roof Pitch :12
Roof Slope, Θ o
Roof Surface
Warm Roof Slope Factor, Cs
Slope Roof Design Snow Load, ps PSF
All Other Surfaces
1.00
B ASCE 7-10 26.7.3 Exposure Categories
ASCE 7-10 7..4 pg ≤ 20 PSF Ispg, pg > 20 PSF 20Is
21.0 ASCE-7-10 (7-.4-1) Cs*pf
ASCE 7-10 Section 7.4.1, 7.4.2, 7.4.3 Figure(s)
72 72b & 72
26.57
ASCE 7-10 Table 1.5-1, UFC 3-301-01 Table 2-2
ASCE 7-10 7.3 FLAT ROOF SNOW LOAD
ASCE 7-10 7.2
ASCE 7-10 Table 7-2 Exposure Factor
ASCE 7-10 (7.3-1) 0.7CeCtIspg
1.0
Colden Residence Relocation Foundation DLS
6892 Flagler Rd, Nordland, WA 98358 20-051
Revised 18-May-18
Partially Exposed
21.0
30.0
1.00
1.00
ASCE 7-10 Table 1.5-2, UFC 3-301-01 Table 2-2
ASCE 7-10 Table 7-2 Exposure Factor
ASCE 7-10 Table 7-3 Thermal Factor
II
All structures except as indicated below
20.0
Pacific Northwest
Structural Group, Inc.John Colden
ASCE 7-10 Snow Loads
ASCE 7-10 7.4 SLOPE ROOF SNOW LOAD
6
21.0
C:\Users\dlsta\Dropbox\PNW Project Files\2020 Projects\20-051 Colden Foundation\ENGR\20-051 Design Criteria 2018.xlsxSnow Load
9/8/2020
DATE: 9/8/2020 COMPANY: Pacific Northwest Structural Group, LLC
VITRUVIUS BUILD: Base DESIGNED BY: David Starkel
CUSTOMER: REVIEWED BY: David Starkel
PROJECT LOCATION:
,PROJECT SUMMARY
Governing Codes:Building Code: 2018 International Building CodeASCE: ASCE 7-16Steel: AISC 360-16Concrete: ACI 318-14Masonry: TMS 402/602-16
Page 1
2018 International Building CodeProject Name: 20-051 Foundation
Module Type: Continuous Footing
Material Type: Concrete
Member Dimensions: 1 ft. wide X 6 in. tall
Section Adequacy:0.5%
Controlling Factor: Soil Bearing Pressure
Rebar - Longitudinal: (2) #4 Bars
Module Type: Isolated Footing
Material Type: Concrete
Member Dimensions: 3 ft. wide X 10 in. tall X 6 ft long
Section Adequacy:27.8%
Controlling Factor: Soil Bearing Pressure
Reinforcement Bars: Size #4, No. Bars Short (4), No. Bars Long: (10)
Module Type: Isolated Footing
Material Type: Concrete
Member Dimensions: 1.5 ft. wide X 8 in. tall X 1.5 ft long
Section Adequacy:4.6%
Controlling Factor: Soil Bearing Pressure
Reinforcement: Unreinforced (Plain)
FTG-1 DIAGRAMS
DATE: 9/8/2020 COMPANY: Pacific Northwest Structural Group, LLC
VITRUVIUS BUILD: Base DESIGNED BY: David Starkel
CUSTOMER: REVIEWED BY: David Starkel
PROJECT LOCATION:
,
LEVEL: Basement LOADING:
LOCATION: FTG-1 CODE: 2018 International Building Code
TYPE: CONTINUOUS FOOTING ACI: ACI 318-14
MATERIAL: CONCRETE
1 (ft) Wide X 6 (in) Deep Soil Depth TOF: 0 (ft) Longit: (2) #4 Bars
MATERIAL PROPERTIES
fc' (psi) Ec (psi) Density (lbf/ft³) Width (ft) Depth (in)
2500 2880952 145 1 6
Width (in) Height (in) Material Offset (in)
618Concrete0
Bearing Strength (lbf/ft²) Density (lbf/ft³) Cohesion Friction Angle Depth (ft) Rankine Coefficient (Kp)
1500 140 0 30 0 0
Bar Size # Transv. Spacing (in) # Longit. Bars fy (psi) Es (psi)
4 None 2 60000 2.9E+07
PASS-FAIL
Soil Bearing Pressure (lbf/ft²)
One-Way Shear Y (lbf)
Moment Y (lbf-ft)
PASS/FAIL
PASS (0.5%)
PASS (72.5%)
PASS (33.7%)
MAGNITUDE
1492.3
619.2
265.4
STRENGTH
1500.0
2250.0
400.0
LOAD COMBO
D+0.75L+0.75S
1.2D+1.6L+0.5S
1.2D+1.6L+0.5S
LOAD LIST
Uniform (lbf/ft) 338 338 0 1 Snow Z
Uniform (lbf/ft) 668 668 0 1 Live Z
Uniform (lbf/ft) 629 629 0 1 Dead Z
Stemwall Weight (lbf/ft) 108.75 108.75 0 1 Dead Z
Page 2
2018 International Building CodeProject Name: 20-051 Foundation
NOTES
The footing requires a minimum area of dowel bars equal to 0.0864 in²/ft into the stem wall ACI 11.6.1.
Page 3
2018 International Building CodeProject Name: 20-051 Foundation
Chimney FTG DIAGRAMS
DATE: 9/8/2020 COMPANY: Pacific Northwest Structural Group, LLC
VITRUVIUS BUILD: Base DESIGNED BY: David Starkel
CUSTOMER: REVIEWED BY: David Starkel
PROJECT LOCATION:
,
LEVEL: Basement LOADING:
LOCATION: Chimney FTG CODE: 2018 International Building Code
TYPE: ISOLATED FOOTING ACI: ACI 318-14
MATERIAL: CONCRETE
3 (ft) X 6 (ft) X 10 (in) Soil Depth TOF: 0 (ft) (4) #4 Long, (10) #4 Short
MATERIAL PROPERTIES
fc' (psi) Ec (psi) Density (lbf/ft³) Width (ft) Length (ft) Depth (in) Volume (ft³)
2500 2880952 145 3 6 10 15
Bo (in) Φ-X Φ-Y
194 0.6 0.6
width (in) length (in) Height (in) Volume (ft³) Material Offset (in)
24 60 12 10 Concrete 0
Bearing Strength (lbf/ft²) Density (lbf/ft³) Cohesion Friction Angle Depth (ft) Rankine Coefficient (Kp)
1500 140 0 30 0 3
Bar Size # # Bars Long # Bars Short fy (psi) Es (psi)
4 4 10 60000 2.9E+07
PASS-FAIL
Soil Bearing Pressure (lbf/ft²)
Two-Way Shear (Punching) (lbf)
Moment X (lbf-ft)
Moment Y (lbf-ft)
Crushing (lbf)
PASS/FAIL
PASS (27.8%)
PASS (82.7%)
PASS (88.2%)
PASS (88.2%)
PASS (98.6%)
MAGNITUDE
1083.3
27300.0
568.8
1137.5
19.0
STRENGTH
1500.0
157950.0
4800.0
9600.0
1381.3
LOAD COMBO
D
1.4D
1.4D
1.4D
1.4D
LOAD LIST
Point (lbf) 18050 - 0 - Dead Z
Pedestal Weight (lbf) 1450 - 0 - Dead Z
Page 4
2018 International Building CodeProject Name: 20-051 Foundation
NOTES
The footing requires a minimum area of dowel bars equal to 7.2 in² into the column ACI 16.3.4.1
Page 5
2018 International Building CodeProject Name: 20-051 Foundation
Typical Pad FTG DIAGRAMS
DATE: 9/8/2020 COMPANY: Pacific Northwest Structural Group, LLC
VITRUVIUS BUILD: Base DESIGNED BY: David Starkel
CUSTOMER: REVIEWED BY: David Starkel
PROJECT LOCATION:
,
LEVEL: Basement LOADING:
LOCATION: Typical Pad FTG CODE:2018 International Building Code
TYPE: ISOLATED FOOTING ACI: ACI 318-14
MATERIAL: CONCRETE
1.5 (ft) Dia. X 8 (in) Soil Depth TOF: 0 (ft) Unreinforced (Plain) Concrete
MATERIAL PROPERTIES
fc' (psi) Ec (psi) Density (lbf/ft³) Width (ft) Length (ft) Depth (in) Volume (ft³)
2500 2880952 145 1.5 1.5 8 1.5
Bo (in) Φ-X Φ-Y
34 0.6 0.6
Width (in) Length (in) Material Offset (in)
4 4 Wood 0
Bearing Strength (lbf/ft²) Density (lbf/ft³) Cohesion Friction Angle Depth (ft) Rankine Coefficient (Kp)
1500 140 0 30 0 3
Bar Size # # Bars Long # Bars Short fy (psi) Es (psi)
None None None 40000 2.9E+07
PASS-FAIL
Soil Bearing Pressure (lbf/ft²)
Two-Way Shear (Punching) (lbf)
One-Way Shear X (lbf)
Moment X (lbf-ft)
One-Way Shear Y (lbf)
Moment Y (lbf-ft)
Crushing (lbf)
PASS/FAIL
PASS (4.6%)
PASS (83.6%)
PASS (92.4%)
PASS (74.9%)
PASS (92.4%)
PASS (74.9%)
PASS (82.9%)
MAGNITUDE
1431.7
3772.0
317.3
330.3
317.3
330.3
235.8
STRENGTH
1500.0
22950.0
4201.8
1316.2
4201.8
1316.2
1381.3
LOAD COMBO
D+L
1.2D+1.6L+0.5Lr
1.2D+1.6L+0.5Lr
1.2D+1.6L+0.5Lr
1.2D+1.6L+0.5Lr
1.2D+1.6L+0.5Lr
1.2D+1.6L+0.5Lr
LOAD LIST
Point (lbf) 1840 - 0 - Live Z
Point (lbf) 690 - 0 - Dead Z
Page 6
2018 International Building CodeProject Name: 20-051 Foundation