HomeMy WebLinkAboutBLD2021-00038 - 07B ENGINEERINGR. Mumbower HiLine Homes Page 1 of 20
ABDELOUAHAB ABROUS, Ph.D., P.E.
Oregon License No: 81419PE
Design & Engineering Department
PROJECT INFORMATION AND CRITERIA
2. STRUCTURAL DESIGNER INFORMATION
Special Design Provisions for Wind and Seismic
(2015 Edition)
Structural specifications
2015 International Building Code (IBC) for
Washington & 2019 Oregon Structural Specialy
Code (OSSC) for Oregon
Phone: (253) 770-2244 Ext. 2132
Email: Wabrous@HiLinehomes.com
2015 International Residential Code (IRC) for
Washington & 2017 Oregon Residential Specialy
Code (ORSC) for Oregon
OWNER:
1. PROJECT INFORMATION
PLAN 1248-15 [pg = 30 psf, VULT = 140 mph, Exp. C, SDC D2]
HiLine Homes
LATERAL ENGINEERING ANALYSIS OF WIND
AND SEISMIC FORCES
REFERENCE CODES AND STANDARDS
American Society for Testing Materials (ASTM)
Standard A307
American Society of Civil Engineers (ASCE)
Standard 7-16
TYPE OF DESIGN
2015 National Design Specification (NDS)
EXTENT OF DESIGN
ALFRED & SUSAN LATHAM
251 KENNEDY ROAD, PORT HADLOCK, WA 98339
1003-1585
SITE ADDRESS:
JOB NUMBER:
3. SCOPE OF DESIGN
Idaho License No: P-14132
11306 62ND Ave E., Puyallup, WA 98373
Washington License No: 36110
Revised
12/2/2020
PROJECT INFORMATION AND CRITERIA
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
12/3/2020
R. Mumbower HiLine Homes Page 2 of 20
GROUND SNOW LOAD:
FLAT ROOF SNOW LOAD PER ASCE (LIVE LOAD):
ROOF DEAD LOAD:
EXTERIOR WALL DEAD LOAD:
INTERIOR WALL DEAD LOAD:
SEISMIC DESIGN CATEGORY:
NOMINAL WIND SPEED:
ASCE DESIGN WIND SPEED:
WIND EXPOSURE FACTOR:
ALLOWABLE SOIL PRESSURE:
Concrete Strength @ 28-days: 3,000-psi
Page 1
Page 3
Page 3
Page 3
Table A. Page 5
Table B.Page 9
Table C. Page 10
Table D. Page 11
Table E-1. Page 12
Table E-2.Page 13
Table F-1. Page 14
Table F-2.Page 15
Table G. Page 16
Table H. Page 17
Table I. Page 18
Table J.Page 19
Table K.Page 20
1,500-psf
C
140-mph
110-mph
SDC D2
4. DESIGN CRITERIA
Wood Structural Panels: APA Rated.
10d Nails Diameter: 0.148-in
8d Nails Diameter: 0.131-in
Framing Material: No. 2 Douglas-Fir minimum.
CONTENTS
Dwall = 15-psf
MATERIAL SPECIFICATIONS:
Wind Loads (Garage)
Droof = 15-psf
pg = 30-psf
pf = 25-psf
Dwall = 10-psf
Anchor Bolts: ASTM A307 Steel
Minimum Wind Loads (House)
Seismic Loads
Minimum Wind Loads (Garage)
Seismic Shear Wall Loads
Roof Diaphragm Load Calculations
Project Information and Criteria
Description
Specifications and Design Criteria
Engineering Calculations
LIST OF TABLES
Wind Shear Wall Loads
Structural Specifications and Allowable Loads
Building Data
Wind Design Criteria
Seismic Design Criteria
Wind Loads (House)
Controlling Shear Loads
Revised
12/2/2020
PROJECT INFORMATION AND CRITERIA
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 3 of 20
Seismic design loads are based on Site Class D soils per ASCE, Section 11.4.2 and Table 20.3-
1 for stiff soils. The Equivalent Lateral Force Procedure of the American Society of Civil
Engineers (ASCE), Section 12.8 is used for calculating seismic forces.
ENGINEERING CALCULATIONS
Wind loads and overturning moments are calculated in Table E for two orthogonal directions,
transverse and longitudinal. Calculated values are linked to Table H, Controlling Shear Loads to
determine if wind, minimum wind, or seismic loads control design of lateral restraint. Unit uplift on
the building is also calculated for both the transverse and longitudinal directions. Overturning
loads due to design base winds are calculated with a link to Table G, Seismic Loads where they
are compared to seismic and building restoring loads.
ASCE,Section 28.5,"Enclosed Simple Diaphragm Low-Rise Building"method isused for
determining wind loads. Wind design criteria are based on a 110-mph nominal wind speed and
Building Height and Exposure Factor (Ȝ)C. Overturning moments due to wind forces are less
than allowable restorative dead load moments as shown in Table G. Uplift loads for roof
tributaries are calculated assuming the maximum uplift for wind Zone E or F applies to the
tributary area.
Structural specifications and design criteria are provided in Tables A, B, C, and D as discussed in the
following paragraphs.
SPECIFICATIONS AND DESIGN CRITERIA
Engineering calculations are documented in Tables E through K based on specifications in Tables B, C, and
D. These tables provide the following information:
Table F. Minimum Wind
This report provides engineering calculations and structural design specifications for HiLine Homes Plan
1248. This one-story house is 1248-sf in area plus an optional two-car garage. Design specifications are
provided in Table A, building data are given in Table B, and wind and seismic criteria, including calculations,
are included in Tables C and D, respectively. Lateral engineering calculations are provided in Tables E
through K. Calculations are performed using Microsoft Excel worksheets.
Table B. Building Data
Specifications are provided for size and spacing of anchors bolts, shear wall hold-downs, shear
wall sheathing and nailing, shear transfer, and roof framing. Structural specifications are
identified with respect to Wall Lines, which are shown on Plan Sheet S2.
The building geometrical dimensions are specified, including lengths of exterior walls, and interior
partitions for the transverse and longitudinal directions. The maximum ground snow load is Pg of
30-psf.
Table A. Specifications of Structural Components and Fasteners
Table D. Seismic Design Criteria
Minimum wind loads are provided in Table F based on horizontal pressures equal to 16-psf for
zones A and C,8-psf for zones B and D, and vertical pressures equal to zero per ASCE, Section
28.6.4. Calculations are performed for both transverse and longitudinal directions and linked to
Table H for comparison to wind and seismic loads.
Table E. Wind Loads
DESCRIPTION
Table C. Wind Design Criteria
Revised
12/2/2020
PROJECT INFORMATION AND CRITERIA
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 4 of 20
Table G. Seismic Loads
Table H provides roof diaphragm load calculations for determining diaphragm shear for seismic
loads and comparing these loads with wind and minimum wind loads from Table H. Shear wall
and roof diaphragm deflections are calculated to confirm that the diaphragm is flexible as allowed
by ASCE, Section 12.3.1.1. Strength level seismic unit shear values are used to calculate
deflections. Calculations are based on American Plywood Association (APA) Report T2002-17,
Estimating Wood Structural Panel Diaphragm and Shear Wall Deflection, April 17, 2002. Uplift
due to design base wind loads are calculated assuming that the roof experiences a maximum
uplift pressure from wind zone E or Zone F. Allowable roof dead loads plus truss connections
exceed uplift by an acceptable margin.
Table G provides seismic shear loads based on seismic design criteria in Table D. Calculations
are based on seismic design criteria in Table D and the Lateral Force Procedure method of
ASCE, Section 12.8. This procedure is valid for Risk Category I or II buildings of light frame
construction not exceeding three stories in height for SDC D and higher per ASCE, Table 12.6.1.
Seismic loads are calculated for transverse and longitudinal directions. Overturning moments are
calculated in the table and compared to allowable restoring dead load moments. The building is
stable with respect to overturning.
Table H. Controlling Shear Loads
Table H provides a summary of seismic shear loads. Shear load values from Tables E, F, and G
are compared to determine controlling lateral forces. The controlling values are linked to Tables I
and K for calculating maximum shear wall loads for wind and seismic forces, respectively.
Table H provides transverse and longitudinal loads on the building structure including wall length,
applied unit shear, shear wall length, resistive unit shear, unit dead load on shear walls, and hold-
down loads for the various shear wall lengths based on controlling wind shear loads from Table
H. Shear wall hold-downs are calculated based on wind and dead load combinations using the
allowable stress design method per ASCE, Section 2.4.
Table J provides transverse and longitudinal loads on the building structure including wall length,
applied unit shear, shear wall length, resistive unit shear, unit dead load on shear walls, and hold-
down loads for the various shear wall lengths based on seismic shear loads from Table H. Shear
wall hold-down loads are calculated based on wind and dead load combinations using the
allowable stress design method per ASCE, Section 2.4.
Table K. Roof Diaphragm Calculations
Table I. Wind Shear Loads
Table J. Seismic Shear Loads
Revised
12/2/2020
PROJECT INFORMATION AND CRITERIA
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 5 of 20
Maximum Applied Shear per Tables I or J (lb)3,193
Wall length under maximum applied shear per Tables I or J (ft)36
Minimum number of anchor bolts when installed at 72-in o.c. minimum 2 anchors/mudsill 7
Maximum anchor bolt Load @ 72-in o.c. minimum 2 anchors per mudsill (lb) 456
Basic allowable single shear for fastening 1.5-in Douglas Fir framing to concrete with 1/2-in dia. ASTM A307
bolts with minimum 7-in embedment = 650-lb per NDS Table 11E. Adjustment for 10-minute wind/seismic
loads = 1.6 per NDS Table 2.3.2. Allowable shear load = (1.6)(650) = 1040-lb.
1,040
Maximum overturning tension due to wind load per Table I (lb)2,592
Maximum overturning tension due to seismic load per Table J (lb)1,980
Maximum wind shear (V) per Tables I or J (lb)2,128
Maximum seismic shear (V) per Tables I or J (lb)1,658
Shear Wall Clear Height (ft)9.1
Maximum Opening Height (ft)6.0
Percentage of Full-Height sheathing (%)54.0
Ratio of Maximum Opening Height to Wall Clear Height 0.66
Shear Resistance Adjustment Factor (C0) per SDPWS Table 4.3.3.5 0.66
Sum of Perforated Shear Wall Segment Lengths (ft)7
Design Wind Shear Capacity of Wall - 4-in edge nailing (lb)2,462
Design Seismic Shear Capacity of Wall - 4-in edge nailing (lb)1,756
CHECK IF SHEAR CAPACITY OF PERFORATED SHEAR WALL IS ADEQUATE YES
Hold-Down Wind Tension Load, T = Vh/C0ȈLi (lb)4,192
Effective Wind Shear, v = V/C0ȈLi (lb/ft)461
Hold-Down Seismic Tension Load, T = Vh/C0ȈLi (lb)3,265
Effective Seismic Shear, v = V/C0ȈLi (lb/ft)359
Allowable Wind Tension Load for Simpson STHD14 Strap Ties at corner location is 4,935-lb 4,935
Allowable Seismic Tension Load for Simpson STHD14 Strap Ties at corner location is 3,695-lb 3,695
Maximum overturning tension due to wind load per Table I (lb)1,430
Maximum overturning tension due to seismic load per Table J (lb)609
Allowable Wind Tension Load for Simpson STHD10 StrapTies at endwall location is 1,635-lb 1,635
TABLE A. STRUCTURAL SPECIFICATIONS AND ALLOWABLE LOADS
FOUNDATION ANCHORING SPECIFICATIONS (ALL WALL LINES)
SHEAR WALL HOLD-DOWN SPECIFICATIONS
EXPLANATION OF WALL LINES
Shear walls and structural specifications are identified with Wall Lines on plan Sheet S2.Lettered Wall Lines are
generally identified from the front to the rear of the building and Numbered Wall Lines start at the left and continue to
the right (STANDARD PLAN). For reversed plans, Lettered Wall Lines remain the same and the Numbered Wall Lines
start at the right of the plan (REVERSED PLAN).
THIS TABLE PROVIDES SUMMARY STRUCTURAL SPECIFICATIONS. ADDITIONAL DETAILS FOR STANDARD
SPECIFICATIONS AND CALCULATION OF ALLOWABLE LOADS ARE PROVIDED AT THE END OF THIS TABLE.
STRUCTURAL SPECIFICATIONS
Install 1/2-in dia. ASTM A307 anchor bolts @ 72-in o.c., minimum 7-in embedment in concrete and maximum 12-
in from end of mudsills with minimum 2 anchors per mudsill.
Wall Line B (Perforated Shear Wall Analysis)
At both ends of the wall line, install Simpson STHD14 Strap Tie Holdowns at each corner per manufacturer's
instructions as shown on the plan. Fasten to minimum 3-in framing with 30-16d sinker nails (total of 2
STHD14s). Apply 7/16-in. OSB wood structural panels to Hem-Fir framing members with 8d nails @ 4-in o.c.on
panel edges, 12-in o.c. in the field, and all edges blocked.
Wall Line C (Garage Portals)
Revised
12/2/2020
STRUCTURAL SPECIFICATIONS AND ALLOWABLE LOADS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 6 of 20
TABLE A. STRUCTURAL SPECIFICATIONS AND ALLOWABLE LOADS
Allowable Seismic Tension Load for Simpson STHD10 StrapTies at endwall location is 1,435-lb 1,435
Maximum resistive unit wind shear load per Table I (lb/ft)228
Maximum resistive unit seismic shear load per Table J (lb/ft)160
Basic allowable shear for wind loads =730-lb/ft per SPECIAL DESIGN PROVISIONS FOR WIND AND
SEISMIC Table 4.3A for 8d nails @ 6-in o.c.on edges., 12-in o.c. in the field, & framing @ 16-in o.c. per note
2. Adjustments 0.50 for ASD. Allowable shear = (0.50)(730) = 365-lb/ft.
365
Basic allowable shear for seismic loads =520-lb/ft per SPECIAL DESIGN PROVISIONS FOR WIND AND
SEISMIC Table 4.3A for 8d nails staggered @ 6-in o.c.on edges, 12-in o.c. in the field & framing @ 16-in o.c.
per Note 2. Adjustments are 0.50 for ASD. Allowable shear = (0.50)(520) = 260-lb/ft.
260
Maximum resistive unit wind shear load per Table I (lb/ft)304
Maximum resistive unit seismic shear load per Table J (lb/ft)237
Maximum resistive unit wind shear load per perforated shear wall analysis (lb/ft)461
Maximum resistive unit seismic shear load per perforated shear wall analysis (lb/ft)359
Basic allowable shear for wind loads =1,065-lb/ft per SPECIAL DESIGN PROVISIONS FOR WIND AND
SEISMIC Table 4.3A for 8d nails staggered @ 4-in o.c.on edges, 12-in o.c. in the field, & framing @ 16-in o.c.
per Note 2. Framing on panel edges is 3-in nominal. Adjustments are 0.50. Allowable shear =
(0.50)(0.93)(1,065) = 533-lb/ft.
533
Basic allowable shear for seismic loads =760-lb/ft per SPECIAL DESIGN PROVISIONS FOR WIND AND
SEISMIC Table 4.3A for 8d nails staggered @ 4-in o.c.on edges, 12-in o.c. in the field & framing @ 16-in o.c.
per Note 2. Adjustments are 0.50 for ASD. Allowable shear = (0.50)(760) = 380-lb/ft.
380
Maximum applied unit wind shear per Table I (lb/ft)164
Maximum applied unit seismic shear per Table J (lb/ft)128
Basic allowable single shear for 10d common toenails with 1.5-in thickness Douglas Fir side members =
(0.83)(118)=98-lb per NDS Table 11N. Adjustment for 10-minute wind/seismic loads = 1.6. Allowable shear
load = (1.6)(0.83)(118) = 156-lb.
156
Allowable load for 2-10d common toenails @ 16-in o.c. = (0.83)(2)(12/16)(1.6)(118) = 235-lb/ft. 235
Maximum Allowable Seismic Unit Shear seismic loads = 150-lb/ft per SDPWS Section 4.1.7 150
All Wall Lines
Wall Lines A, B, D & 1 (Gables)
Fasten double top plates together with 10d nails @ 12-in o.c. and 6-in o.c. at splices. Overlap splices 4-ft.
minimum. Fasten OSB wall sheathing between shear wall segments at same fastener spacing as on shear
walls.
Apply 7/16-in. OSB wood structural panels to Douglas Fir framing members with 8d nails @ 6-in o.c. per
standard specification.
SHEAR WALL SHEATHING SPECIFICATIONS
Fasten OSB panels to mudsills with minimum 8d nails @ 6-in o.c.
Wall Line B
SHEAR TRANSFER SPECIFICATIONS
Apply 7/16-in. OSB wood structural panels to Douglas Fir framing members with 8d nails @ 4-in o.c. per
standard specification.
At both ends of each garage portal, install Simpson STHD10 Strap Tie Holdowns at each corner per
manufacturer's instructions as shown on the plan. Fasten to minimum 3-in framing with 24-16d nails (total of 4
STHD10s). Apply 7/16-in. OSB wood structural panels to Hem-Fir framing members with 8d nails @ 6-in o.c.on
panel edges, 12-in o.c. in the field, and all edges blocked.
All Exterior Wall Lines (Except Wall Line B)
Fasten gable-end trusses to double top plates with 2-10d toenails @ 16-in o.c. or 1-10d toenail @ 8-in o.c.
Revised
12/2/2020
STRUCTURAL SPECIFICATIONS AND ALLOWABLE LOADS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 7 of 20
TABLE A. STRUCTURAL SPECIFICATIONS AND ALLOWABLE LOADS
Maximum applied unit wind shear per Table I (lb)89
Maximum applied unit seismic shear per Table J (lb/ft)62
Fasten per Roof Framing Specification for truss connections and blocking.381
Maximum applied load per Tables I, J (lb)1,125
Basic allowable single shear for 10d common nails with 1.5-in thickness Hem-Fir side members = 102-lb per
NDS Table 11N. Adjustment for 10-minute wind/seismic loads = 1.6. Allowable shear load = (1.6)(102) = 163-
lb.
163
Maximum applied unit wind shear per Table I (lb/ft)164
Maximum applied unit seismic shear per Table J (lb/ft)128
Basic allowable unit shear for wind/seismic loads = 645/460-lb/ft per SDPWS Table 4.2C for 7/16-in
unblocked panel diaphragms. Adjustment Factor (AF) for ASD = 0.5. Adjusted allowable unit shear =
(0.50)(645/460) = 323/230-lb/ft.
323/230
Maximum applied unit shear per Table H (lb/ft)101
Maximum applied unit shear per Tables I and J (lb/ft)62
Basic allowable single shear for 10d common toenails with 1.5-in thickness Douglas Fir side members =
(0.83)(118)=98-lb per NDS Table 11N. Adjustment for 10-minute wind/seismic loads = 1.6. Allowable shear
load = (1.6)(0.83)(118) = 156-lb.
156
Allowable load for 2-10d common toenails = (0.83)(2)(1.6)(118) = 313-lb/ft. 313
Simpson H2.5A/H1 Seismic & Hurricane Tie lateral load resistance F2 = 110/190-lb 110/190
Simpson H2.5A/H1 Seismic & Hurricane Tie longitudinal load resistance F1 = 110/510-lb 110/510
Allowable load for 2-10d common toenails = (2)(0.83)(1.6)(118) = 313-lb per truss end. Allowable load for
H2.5A or H1 Seismic & HurricaneTies = 110-lb per truss end for Douglas Fir. Total allowable load per truss
end = 313 + 110 = 423-lb per truss end = 423-lb (H2.5A ties control lateral loads).
423
Maximum allowable ground snow load for 7/8-in APA Span Rated 60/32 with supports @ 24-in o.c. is 360-psf
Structural panels shall conform to guidelines outlined in Section 1.4.3. Thickness of panels shall be determined
by snow load unless otherwise specified as follows:
Maximum allowable ground snow load for 7/16-in APA Span Rated 24/16 with supports @ 24-in o.c. is 45-psf
Maximum allowable ground snow load for 15/32-in APA Span Rated 32/16 with supports @ 24-in o.c. is 75-psf
Wall Line C (Connection Garage to House)
DRAG STRUT CALCULATIONS
Nail a 2x laid to the garage side top plates and to the adjacent truss with (10) 10d nails on each side.
See Roof Framing Specification for truss connections and blocking.
Wall Lines 2, 3, C & D (Eaves)
See Truss Connection below for additional requirements.
Fasten truss tails to top plates with 2-10 toenails and a Simpson H2.5A or H1 Seismic & Hurricane Tie fastened
to truss and top plates per manufactures instructions. (see sheet S3, Roof Framing Plan).
Truss Connections (Lateral Loads)
Fasten 2X4 vent blocking in each truss bay with 1-10d toenail into truss, each side. Fasten roof diaphragm to
blocking with 8d nails @ 6-in o.c.
ROOF DIAPHRAGM FRAMING SPECIFICATIONS
Truss Connections (Longitudinal Loads)
Truss Blocking & Boundary Nailing
Roof Sheathing
Maximum allowable ground snow load for 5/8-in APA Span Rated 40/20 with supports @ 24-in o.c. is 170-psf
Maximum allowable ground snow load for 23/32-in APA Span Rated 48/24 with supports @ 24-in o.c. is 205-psf
Revised
12/2/2020
STRUCTURAL SPECIFICATIONS AND ALLOWABLE LOADS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 8 of 20
TABLE A. STRUCTURAL SPECIFICATIONS AND ALLOWABLE LOADS
Allowable load for Simpson RBC Clip @ 24-in o.c. = (12/24)*(445) = 222-lb/ft. 222
Maximum net uplift on truss connection for 85 mph, Exposure C per Table K (lb). -165
Maximum net uplift on truss connection for 95 mph, Exposure C per Table K (lb). -253
Maximum net uplift on truss connection for 110 mph, Exposure C per Table K (lb). -448
Allowable uplift for H2.5A/H1 Seismic & Hurricane Ties = 520/400-lb for Douglas-Fir framing.520/400
Allowable uplift for H10 Seismic & Hurricane Ties = 855-lb for Douglas Fir framing.855
Maximum applied chord tension load per Tables J, C = T = M/b = vrL2/b8 (lb). 698
Allowable chord splice tension load for 10d nails @ 6-in o.c.1,699
Fasten exterior wall top plate splices together with 10d nails @ 6-in o.c. Minimum splice length = 48-in.
Truss Chord Splice Nailing
Truss Connections (Uplift Loads)
Fasten truss tails to top plates with H2.5A or H1 Seismic & Hurricane Ties for 85-mph wind speeds. Use H10A
Ties for higher speeds.
Nail roof sheathing to blocking with 8d nails @ 6-in o.c. Fasten blocking to top plates with Simpson RBC clips
@ 24-in o.c. - fill all nail holes.
Revised
12/2/2020
STRUCTURAL SPECIFICATIONS AND ALLOWABLE LOADS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 9 of 20
Description Value Description Value
Transverse Width of Building (ft) 32.0 Roof Diaphragm Dead Load (psf)15
Longitudinal Length of Building (ft)42.0 Exterior Walls Dead Load (psf)15
Partition Walls Dead Load (psf)10
Roof Slope (5/12)0.42
Length of Gable-End Roof Overhang (ft)1.0
Length of Eave-End Roof Overhang (ft)1.3 Roof Height (ft)9.1
Maximum Truss Span (ft)32.0 Mean Height (ft)12.4
Maximum Height (ft)15.8
Wall Height (ft)9.1
Transverse Exterior Walls Length (ft)64.0 Least horizontal Building Dimension, b (ft)32.0
Longitudinal Exterior Walls Length (ft)84.0 0.4 * Mean Building Height (ft)4.97333
Total Exterior Walls Length (ft)148.0 0.1*b (ft)3.2
Total Partitions Weight (lb) - ASCE 12.7.2 12,480 End Zone Dimension, a (ft)3.2
Adjusted End Zone Dimension, a (ft)3.2
Length of End Zone, 2a (ft)6.4
Building Enclosed Area (sf)1,248.0
Garage Enclosed Area (sf)440.0
Building and Garage Enclosed Area (sf)1,688.0
Wall Height (ft)9.1 Least horizontal Building Dimension, b (ft)20.0
Transverse Width of Garage (ft)20.0 0.4 * Mean Building Height (ft)4.47333
Longitudinal Length of Garage (ft)22.0 0.1*b (ft)2
Transverse Exterior Walls Length (ft)40.0 End Zone Dimension, a (ft)2.0
Longitudinal Exterior Walls Length (ft)44.0 Adjusted End Zone Dimension, a (ft)3.0
Maximum Truss Span (ft)20.0 Length of End Zone, 2a (ft)6.0
Mean Height (ft)11.2
Maximum Height (ft)13.3
Total Exterior Walls Length (ft)84.0
Total Partitions Weight (ft) - ASCE 12.7.2 0
Assumed 30.0
ASCE Table 7-2, for Exposure C 1.0
ASCE Table 7-3, for Residences 1.2
ASCE Table 1.5-2, for Category II 1.0
ASCE Figure 7-2a 1.0
ASCE Equation 7.3-1, pf = 0.7 Ce Ct Is pg 25.2
Snow Importance Factor, Is
TABLE B. BUILDING DATA
BUILDING DIMENSIONS
MAIN FLOOR DIMENSIONS
BUILDING INERTIAL DATA
MEAN AND MAXIMUM BUILDING HEIGHTS
Exposure Factor, Ce
Thermal Factor, C t
GARAGE LENGTH OF END ZONE, 2a
Transverse Width is measured perpendicular to the ridge line and longitudinal length parallel to the ridge line.
BUILDING ENCLOSED AREA
GARAGE DIMENSIONS
Flat Roof Snow Load, p f (psf)
Maximum Ground Snow Load, p g (psf)
CALCULATION OF LENGTH OF END ZONE, 2a
Slope Factor, Cs
SNOW DATA
Note:
Revised
12/2/2020
BUILDING DATA
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 10 of 20
Description Value Description Value
Nominal Wind Speed V 3s (mph)110
ASCE Design Wind Speed (mph)140
Wind Exposure Category C Transverse Zones A & B Width (ft) 6.4
Simplified Procedure per ASCE 28.5 Yes Transverse Zones C & D Width (ft) 35.6
Exposure & Height Factor, ʄ 1.21 Transverse Zones A & C Height (ft) 9.1
Topographical Factor, Kzt 1.00 Transverse Zones B & D Height (ft) 6.7
Transverse Roof Zones E & F Width (ft) 6.4
Transverse Roof Zones G & H Width (ft) 35.6
A - End Zone of Wall 40.9 Transverse Roof Zones E & F Length (ft) 16.0
B - End Zone of Roof -2.2 Transverse Roof Zones G & H Length (ft) 16.0
C - Interior Zone of Wall 28.4
D - Interior Zone of Roof 0.3
E - End Zone of Windward Roof -26.9
F - End Zone of Leeward Roof -24.8 Longitudinal Zone A Width (ft)6.4
G - Interior Zone of Windward Roof -19.0 Longitudinal Zone C Width (ft)25.6
H - Interior Zone of Leeward Roof -19.3 Longitudinal Zone A Height (ft)10.4
Eo - End Zone of Windward OVHG Roof -41.9 Longitudinal Zone C Height (ft)12.9
Go - Interior Zone of Windward OVGH Roof -33.9
Longitudinal Roof Zones E & F Width (ft)6.4
A - End Zone of Wall 31.1 Longitudinal Roof Zones G & H Width (ft)25.6
B - End Zone of Roof -16.1 Longitudinal Roof Zones E & G Length (ft)21.0
C - Interior Zone of Wall 20.6 Longitudinal Roof Zones F & H Length (ft)21.0
D - Interior Zone of Roof -9.6
E - End Zone of Windward Roof -37.3
F - End Zone of Leeward Roof -21.2
G - Interior Zone of Windward Roof -26.0
H - Interior Zone of Leeward Roof -16.4
Eo - End Zone of Windward OVHG Roof -52.3
Go - Interior Zone of Windward OVGH Roof -40.9
Transverse Zones A & B Width (ft) 6.0
Transverse Zones C & D Width (ft) 16.0
Transverse Zones A & C Height (ft) 9.1
Transverse Zones B & D Height (ft) 4.2
Longitudinal Zone A Width (ft)6.0
Longitudinal Zone C Width (ft)14.0
Longitudinal Zone A Height (ft)10.4
Longitudinal Zone C Height (ft)11.5
LONGITUDINAL BUILDING ZONE DATA
Horizontal Wind Force Loading
Vertical Windforce Loading
Note:
Transverse Width is measured perpendicular to the ridge line and longitudinal length parallel to the ridge line.
LONGITUDINAL BUILDING ZONE DATA
GARAGE
LONGITUDINAL DIRECTION (CASE B)
TRANSVERSE BUILDING ZONE DATA
Horizontal Wind Force Loading
Horizontal Wind Force Loading
TRANSVERSE DIRECTION (CASE A)
TABLE C. WIND DESIGN CRITERIA
WIND DESIGN CRITERIA
DESIGN WIND PRESSURES (psf)
Horizontal Wind Force Loading
Vertical Wind Force Loading
TRANSVERSE BUILDING ZONE DATA
MAIN FLOOR
Revised
12/2/2020
WIND DESIGN CRITERIA
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 11 of 20
Description Reference/Calculation Value
Building Risk Category ASCE, Table 1-5.1 II
Seismic Importance Factor, Ie ASCE, Table 1.5-2 1.0
Default Seismic Site Classification ASCE, Table 20.3-1 D
Seismic Design Category IRC Table R301.2.2.1.1 D2
Response Modification Coefficient, R ASCE, Table 12.2-1 6.5
Building Period Parameter: Ct ASCE, Table 12.8-2 0.02
Redundancy Factor, ʌ ASCE, Section 12.3.4.2 1.000
Site Short Period Design Acceleration, SDS (g)IRC Table R301.2.2.1.1 0.878
Mapped MCE Long Period Acceleration, SM1 (g)ASCE, Figure 22-2 0.600
Ground Snow Load (psf)Building Department 30.0
Flat Roof Snow Load (psf)Calculation, See Table B 25.2
Mean Building Height, h (ft) Per Plan (Calculated in Table B)12.4
Building Period, Ta = Cth3/4 (sec)ASCE, Section 12.8.2.1 0.132
Site Long Design Period Acceleration, SD1 (g)ASCE, 11.4.4, SD1 = 2/3SM1 0.400
T0 = 0.2*SD1/SDS (sec)ASCE, Section 11.4.5 0.091
Ts = SD1/SDS (sec)ASCE, Section 11.4.5 0.456
Seismic Design Coefficient: Cs = SDS*Ie/R ASCE, Section 12.8.1.1 0.135
TABLE D. SEISMIC DESIGN CRITERIA
SEISMIC GROUND MOTION VALUES AND SITE SPECIFICATIONS
COMPUTATION OF DESIGN RESPONSE SPECTRUM DATA
COMPUTATION OF SEISMIC DESIGN COEFFICIENT
Revised
12/2/2020
SEISMIC DESIGN CRITERIA
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 12 of 20
Zone
Wind
Pressure
(psf)
Zone Width
(ft)
Zone
Ht./Leng.
(ft)
Zone Area
(sf)
Zone Force
(lb)
Moment
Arm (ft)
Moment
(ft-lb)
Transverse Wall Zone A 40.9 6.4 9.1 58.2 2,882 4.6 13,114
Transverse Roof Zone B 0.0 6.4 6.7 42.7 0 9.1 0
Transverse Wall Zone C 28.4 35.6 9.1 324.0 11,133 4.6 50,653
Transverse Roof Zone D 0.3 35.6 6.7 237.3 86 9.1 784
7,094 64,551
4,256 38,731
Transverse Roof Zone E -26.9 6.4 16.0 102.4 -3,333 24.0 79,992
Transverse Roof Zone F -24.8 6.4 16.0 102.4 -3,073 8.0 24,583
Transverse Roof Zone G -19.0 35.6 16.0 569.6 -13,095 24.0 314,282
Transverse Roof Zone H -19.3 35.6 16.0 569.6 -13,302 8.0 106,415
Roof Overhang Zone E -41.9 6.4 1.3 8.5 -432 32.7 14,097
Roof Overhang Zone F -24.8 6.4 1.3 8.5 -255 -0.7 -170
Roof Overhang Zone G -33.9 35.6 1.3 47.3 -1,942 32.7 63,441
Roof Overhang Zone H -19.3 35.6 1.3 47.3 -1,106 -0.7 -735
-36,538 601,905
-21,923 361,143
399,874
-17.6
Longitudinal Wall Zone A 31.1 6.4 10.4 66.8 2,513 5.2 13,108
Longitudinal Wall Zone B 0.0 6.4 0.0 0.0 0 9.1 0
Longitudinal Wall Zone C 20.6 25.6 12.9 331.1 8,253 6.5 53,368
Longitudinal Wall Zone D 0.0 25.6 0.0 0.0 0 9.1 0
6,766 66,476
4,060 39,886
Longitudinal Roof Zone E -37.3 6.4 21.0 134.4 -6,066 31.5 191,075
Longitudinal Roof Zone F -21.2 6.4 21.0 134.4 -3,448 10.5 36,200
Longitudinal Roof Zone G -26.0 25.6 21.0 537.6 -16,913 31.5 532,756
Longitudinal Roof Zone H -16.4 25.6 21.0 537.6 -10,668 10.5 112,015
Roof Overhang Zone E -52.3 6.4 1.0 6.4 -405 42.5 17,213
Roof Overhang Zone F -21.2 6.4 1.0 6.4 -164 -0.5 82
Roof Overhang Zone G -40.9 25.6 1.0 25.6 -1,267 42.5 53,844
Roof Overhang Zone H -16.4 25.6 1.0 25.6 -508 -0.5 -254
-39,439 942,932
-23,663 565,759
605,645
-19.0
Total Overturning Moment Due to Transverse Wind Loading (ASD)
LONGITUDINAL WIND LOADING
Horizontal Wind Loads
STRENGTH LEVEL Lateral Force/Moment
Vertical Wind Loads
STRENGTH LEVEL Uplift Force and Overturning Moment on Building
Unit Uplift on Building (psf)
Unit Uplift on Building (psf)
(+) and (-) signs signify wind pressures acting toward and away from the projected surfaces, respectively per ASCE.
Note:
Total Overturning Moment Due to Longitudinal Wind Loads (ASD)
CONVERT TO ALLOWABLE STRESS DESIGN
CONVERT TO ALLOWABLE STRESS DESIGN
TABLE E-1. WIND LOADS (HOUSE)
Horizontal Wind Loads
STRENGTH LEVEL Lateral Force/Moment
Vertical Wind Loads
STRENGTH LEVEL Uplift Force and Overturning Moment on Building
CONVERT TO ALLOWABLE STRESS DESIGN
CONVERT TO ALLOWABLE STRESS DESIGN
TRANSVERSE WIND LOADING
Revised
12/2/2020
WIND LOADS - HOUSE
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 13 of 20
Zone
Wind
Pressure
(psf)
Zone Width
(ft)
Zone
Ht./Leng.
(ft)
Zone Area
(sf)
Zone Force
(lb)
Moment
Arm (ft)
Moment
(ft-lb)
Transverse Wall Zone A 40.9 6.0 9.1 54.6 2,702 4.6 12,295
Transverse Roof Zone B 0.0 6.0 4.2 25.0 0 9.1 0
Transverse Wall Zone C 28.4 16.0 9.1 145.6 5,003 4.6 22,765
Transverse Roof Zone D 0.3 16.0 4.2 66.7 24 9.1 220
3,877 35,280
2,326 21,168
Transverse Roof Zone E -26.9 6.0 10.0 60.0 -1,953 15.0 29,294
Transverse Roof Zone F -24.8 6.0 10.0 60.0 -1,800 5.0 9,002
Transverse Roof Zone G -19.0 16.0 10.0 160.0 -3,678 15.0 55,176
Transverse Roof Zone H -19.3 16.0 10.0 160.0 -3,736 5.0 18,682
Roof Overhang Zone E -41.9 6.0 1.3 8.0 -405 20.7 8,361
Roof Overhang Zone F -24.8 6.0 1.3 8.0 -239 -0.7 -159
Roof Overhang Zone G -33.9 16.0 1.3 21.3 -873 20.7 18,038
Roof Overhang Zone H -19.3 16.0 1.3 21.3 -497 -0.7 -330
-13,182 138,064
-7,909 82,838
104,007
-6.3
Longitudinal Wall Zone A 31.1 6.0 10.4 62.1 2,337 5.2 12,093
Longitudinal Wall Zone B 0.0 6.0 0.0 0.0 0 9.1 0
Longitudinal Wall Zone C 20.6 14.0 11.5 161.6 4,027 5.8 23,238
Longitudinal Wall Zone D 0.0 14.0 0.0 0.0 0 9.1 0
3,749 35,331
2,249 21,199
Longitudinal Roof Zone E -37.3 6.0 11.0 66.0 -2,979 16.5 49,150
Longitudinal Roof Zone F -21.2 6.0 11.0 66.0 -1,693 5.5 9,312
Longitudinal Roof Zone G -26.0 14.0 11.0 154.0 -4,845 16.5 79,940
Longitudinal Roof Zone H -16.4 14.0 11.0 154.0 -3,056 5.5 16,808
Roof Overhang Zone E -52.3 6.0 1.0 6.0 -380 22.5 8,543
Roof Overhang Zone F -21.2 6.0 1.0 6.0 -154 -0.5 77
Roof Overhang Zone G -40.9 14.0 1.0 14.0 -693 22.5 15,589
Roof Overhang Zone H -16.4 14.0 1.0 14.0 -278 -0.5 -139
-14,077 179,280
-8,446 107,568
128,767
-6.8Unit Uplift on Building (psf)
Note:
(+) and (-) signs signify wind pressures acting toward and away from the projected surfaces, respectively per ASCE.
STRENGTH LEVEL Lateral Force/Moment
CONVERT TO ALLOWABLE STRESS DESIGN
Vertical Wind Loads
STRENGTH LEVEL Uplift Force and Overturning Moment on Building
CONVERT TO ALLOWABLE STRESS DESIGN
Total Overturning Moment Due to Longitudinal Wind Loads (ASD)
STRENGTH LEVEL Uplift Force and Overturning Moment on Building
CONVERT TO ALLOWABLE STRESS DESIGN
Total Overturning Moment Due to Transverse Wind Loading (ASD)
Unit Uplift on Building (psf)
LONGITUDINAL WIND LOADING
Horizontal Wind Loads
TABLE E-2. WIND LOADS (GARAGE)
TRANSVERSE WIND LOADING
Horizontal Wind Loads
STRENGTH LEVEL Lateral Force/Moment
CONVERT TO ALLOWABLE STRESS DESIGN
Vertical Wind Loads
Revised
12/2/2020
WIND LOADS - GARAGE
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 14 of 20
Zone
Wind
Pressure
(psf)
Zone Width
(ft)
Zone
Ht./Leng.
(ft)
Zone Area
(sf)
Zone Force
(lb)
Moment
Arm (ft)
Moment
(ft-lb)
Transverse Wall Zone A 16.0 6.4 9.1 58.2 932 4.6 4,240
Transverse Roof Zone B 8.0 6.4 6.7 42.7 341 9.1 3,106
Transverse Wall Zone C 16.0 35.6 9.1 324.0 5,183 4.6 23,584
Transverse Roof Zone D 8.0 35.6 6.7 237.3 1,899 9.1 17,278
5,298 48,208
3,179 28,925
Transverse Roof Zone E 0.0 6.4 16.0 102.4 0 24.0 0
Transverse Roof Zone F 0.0 6.4 16.0 102.4 0 8.0 0
Transverse Roof Zone G 0.0 35.6 16.0 569.6 0 24.0 0
Transverse Roof Zone H 0.0 35.6 16.0 569.6 0 8.0 0
Roof Overhang Zone E 0.0 6.4 1.3 8.5 0 32.7 0
Roof Overhang Zone F 0.0 6.4 1.3 8.5 0 -0.7 0
Roof Overhang Zone G 0.0 35.6 1.3 47.3 0 32.7 0
Roof Overhang Zone H 0.0 35.6 1.3 47.3 0 -0.7 0
00
00
28,925
0.0
Longitudinal Wall Zone A 16.0 6.4 10.4 66.8 1,068 5.2 5,573
Longitudinal Wall Zone B 8.0 6.4 0.0 0.0 0 9.1 0
Longitudinal Wall Zone C 16.0 25.6 12.9 331.1 5,297 6.5 34,257
Longitudinal Wall Zone D 8.0 25.6 0.0 0.0 0 9.1 0
4,036 39,830
2,422 23,898
Longitudinal Roof Zone E 0.0 6.4 21.0 134.4 0 31.5 0
Longitudinal Roof Zone F 0.0 6.4 21.0 134.4 0 10.5 0
Longitudinal Roof Zone G 0.0 25.6 21.0 537.6 0 31.5 0
Longitudinal Roof Zone H 0.0 25.6 21.0 537.6 0 10.5 0
Roof Overhang Zone E 0.06.41.06.4 042.5 0
Roof Overhang Zone F 0.0 6.4 1.0 6.4 0 -0.5 0
Roof Overhang Zone G 0.0 25.6 1.0 25.6 0 42.5 0
Roof Overhang Zone H 0.0 25.6 1.0 25.6 0 -0.5 0
00
00
23,898
0.0Unit Uplift on Building (psf)
Note:
(+) and (-) signs signify wind pressures acting toward and away from the projected surfaces, respectively per ASCE.
STRENGTH LEVEL Lateral Force/Moment
CONVERT TO ALLOWABLE STRESS DESIGN
Vertical Wind Loads
STRENGTH LEVEL Uplift Force and Overturning Moment on Building
CONVERT TO ALLOWABLE STRESS DESIGN
Total Overturning Moment Due to Longitudinal Wind Loads (ASD)
STRENGTH LEVEL Uplift Force and Overturning Moment on Building
CONVERT TO ALLOWABLE STRESS DESIGN
Total Overturning Moment Due to Transverse Wind Loading (ASD)
Unit Uplift on Building (psf)
LONGITUDINAL WIND LOADING
Horizontal Wind Loads
TABLE F-1. MINIMUM WIND LOADS (HOUSE)
TRANSVERSE WIND LOADING
Horizontal Wind Loads
STRENGTH LEVEL Lateral Force/Moment
CONVERT TO ALLOWABLE STRESS DESIGN
Vertical Wind Loads
Revised
12/2/2020
MINIMUM WINDOW LOADS - HOUSE
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 15 of 20
Zone
Wind
Pressure
(psf)
Zone Width
(ft)
Zone
Ht./Leng.
(ft)
Zone Area
(sf)
Zone Force
(lb)
Moment
Arm (ft)
Moment
(ft-lb)
Transverse Wall Zone A 16.0 6.0 9.1 54.6 874 4.6 3,975
Transverse Roof Zone B 8.0 6.0 4.2 25.0 200 9.1 1,820
Transverse Wall Zone C 16.0 16.0 9.1 145.6 2,330 4.6 10,600
Transverse Roof Zone D 8.0 16.0 4.2 66.7 533 9.1 4,853
2,335 21,248
1,401 12,749
Transverse Roof Zone E 0.0 6.0 10.0 60.0 0 15.0 0
Transverse Roof Zone F 0.0 6.0 10.0 60.0 0 5.0 0
Transverse Roof Zone G 0.0 16.0 10.0 160.0 0 15.0 0
Transverse Roof Zone H 0.0 16.0 10.0 160.0 0 5.0 0
Roof Overhang Zone E 0.0 6.0 1.3 8.0 0 20.7 0
Roof Overhang Zone F 0.0 6.0 1.3 8.0 0 -0.7 0
Roof Overhang Zone G 0.0 16.0 1.3 21.3 0 20.7 0
Roof Overhang Zone H 0.0 16.0 1.3 21.3 0 -0.7 0
00
00
12,749
0.0
Longitudinal Wall Zone A 16.0 6.0 10.4 62.1 994 5.2 5,142
Longitudinal Wall Zone B 8.0 6.0 0.0 0.0 0 9.1 0
Longitudinal Wall Zone C 16.0 14.0 11.5 161.6 2,585 5.8 14,916
Longitudinal Wall Zone D 8.0 14.0 0.0 0.0 0 9.1 0
2,123 20,058
1,274 12,035
Longitudinal Roof Zone E 0.0 6.0 11.0 66.0 0 16.5 0
Longitudinal Roof Zone F 0.0 6.0 11.0 66.0 0 5.5 0
Longitudinal Roof Zone G 0.0 14.0 11.0 154.0 0 16.5 0
Longitudinal Roof Zone H 0.0 14.0 11.0 154.0 0 5.5 0
Roof Overhang Zone E 0.06.01.06.0 022.5 0
Roof Overhang Zone F 0.0 6.0 1.0 6.0 0 -0.5 0
Roof Overhang Zone G 0.0 14.0 1.0 14.0 0 22.5 0
Roof Overhang Zone H 0.0 14.0 1.0 14.0 0 -0.5 0
00
00
12,035
0.0Unit Uplift on Building (psf)
Note:
(+) and (-) signs signify wind pressures acting toward and away from the projected surfaces, respectively per ASCE.
STRENGTH LEVEL Lateral Force/Moment
CONVERT TO ALLOWABLE STRESS DESIGN
Vertical Wind Loads
STRENGTH LEVEL Uplift Force and Overturning Moment on Building
CONVERT TO ALLOWABLE STRESS DESIGN
Total Overturning Moment Due to Longitudinal Wind Loads (ASD)
STRENGTH LEVEL Uplift Force and Overturning Moment on Building
CONVERT TO ALLOWABLE STRESS DESIGN
Total Overturning Moment Due to Transverse Wind Loading (ASD)
Unit Uplift on Building (psf)
LONGITUDINAL WIND LOADING
Horizontal Wind Loads
TABLE F-2. MINIMUM WIND LOADS (GARAGE)
TRANSVERSE WIND LOADING
Horizontal Wind Loads
STRENGTH LEVEL Lateral Force/Moment
CONVERT TO ALLOWABLE STRESS DESIGN
Vertical Wind Loads
Revised
12/2/2020
MINIMUM WIND LOADS - GARAGE
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 16 of 20
Building Component Load (psf)
Height/
Width (ft)
Length
(ft)Area (sf)
Seismic
Weight
(lb)
Seismic
Shear
(lb)
Roof Diaphragm & Ceiling 15.0 1,248 18,720 2,529
20% of Flat Roof Snow Load > 30-psf 0.0 1,248 00
One-Half Exterior Walls 15.0 9.1 148.0 1,347 10,101 1,364
One-Half Partitions 10.0 1,248 6,240 843
51,402
35,061
4,736
3,315
Roof Diaphragm & Ceiling 15.0 440 6,600 892
20% of Flat Roof Snow Load > 30-psf 0.0 440 0 0
One-Half Exterior Walls 15.0 9.1 84.0 764 5,733 774
One-Half Partitions 10.0 0 00
18,066
12,333
1,666
1,166
Building Component Force (lb)
Dist.
(ft)
Moment
(ft-lb)
Roof Diaphragm & Ceiling 2,529 9.1 23,011
Exterior Walls 1,364 9.1 12,416
Partitions 843 9.1 7,670
Total Dead Load 51,402 16.0 822,432
43,097
399,874
822,432
493,459
Building Component Force (lb)
Dist.
(ft)
Moment
(ft-lb)
Roof Diaphragm & Ceiling 2,529 9.1 23,011
Exterior Walls 1,364 9.1 12,416
Partitions 843 9.1 7,670
Total Dead Load 51,402 21.0 1,079,442
43,097
605,645
1,079,442
647,665
OVERTURNING ANALYSIS DUE TO LONGITUDINAL LOADS
Total Moment Due to Longitudinal Seismic Forces
Total Moment Due to Longitudinal Wind Forces
Total Restoring Moment in Longitudinal Loading
6/10 of Total Restoring Moment in Longitudinal Loading
OVERTURNING STABILITY YES
TABLE G. SEISMIC LOADS
SEISMIC SHEAR LOADS ON HOUSE
STRENGTH LEVEL BASE SHEAR
Roof Diaphragm Tributary Dead Load
CONVERT TO ALLOWABLE STRESS DESIGN BASE SHEAR
Total Dead Load for Restoring Moment
Total Moment Due to Transverse Seismic Forces
Total Restoring Moment in Transverse Loading
OVERTURNING STABILITY YES
Total Moment Due to Transverse Wind Forces
6/10 of Total Restoring Moment in Transverse Loading
OVERTURNING ANALYSIS DUE TO TRANSVERSE LOADS - HOUSE
SEISMIC SHEAR LOADS ON GARAGE
Total Dead Load for Restoring Moment
Roof Diaphragm Tributary Dead Load
STRENGTH LEVEL BASE SHEAR
CONVERT TO ALLOWABLE STRESS DESIGN BASE SHEAR
Revised
12/2/2020
SEISMIC LOADS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 17 of 20
Floor Level
Type Load Transverse Longitudinal Transverse Longitudinal
ASD Wind Load (lb) 4,256 4,060 N/A N/A
ASD Minimum Wind Load (lb) 3,179 2,422 N/A N/A
ASD Controlling Wind Load (lb) 4,256 4,060 N/A N/A
ASD Seismic Diaphragm Load (lb)3,315 3,315 N/A N/A
Nature of Controlling Load WIND WIND N/A N/A
ASD Maximum wind/seismic load (lb)4,256 4,060 N/A N/A
Type Load Transverse Longitudinal Transverse Longitudinal
ASD Wind Load (lb) 2,326 2,249 N/A N/A
ASD Minimum Wind Load (lb) 1,401 1,274 N/A N/A
ASD Controlling Wind Load (lb) 2,326 2,249 N/A N/A
ASD Seismic Diaphragm Load (lb)1,166 1,166 N/A N/A
Nature of Controlling Load WIND WIND N/A N/A
ASD Maximum wind/seismic load (lb)2,326 2,249 N/A N/A
NOTE: ASD = ALLOWABLE STRESS DESIGN
TABLE H. CONTROLLING SHEAR LOADS
House
Main Floor Level Second Floor Level
Garage
Revised
12/2/2020
CONTROLLING LOADS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 18 of 20
Floor Level
Wall Identification A B C D Check
Wall Type OSB OSB OSB OSB Total
Tributary Load Distance (ft) - H 3.0 21.0 18.0 42.0
Tributary Load Fraction - H 0.071 0.500 0.429 1.0
Tributary Load Distance (ft) - G 10.0 10.0 20.0
Tributary Load Fraction - G 0.500 0.500 1.0
Applied Shear (lb)304 2,128 1,125 1,824 5,381
Wall Length (ft)13.0 13.0 22.0 54.0
Applied Unit Shear (lb/ft)23 164 51 34
Shear Wall Length (ft)7.0 7.0 6.0 36.0
Resistive Unit Shear (lb/ft) 43 304 187 51
Shear Wall Height (ft) 9.1 9.1 9.1 9.1
Unit DL on Wall (lb/ft)167 167 306 166.5
0.60*[Unit DL on Wall] (lb/ft)100 100 184 99.9
Max. Hold-Down 3.0-ft SW (lb) 1,430 311
Max. Hold-Down 3.5-ft SW (lb)220 2,592
286
Max. Hold-Down 4.0-ft SW (lb) 261
Max. Hold-Down 22.0-ft SW (lb) -638
Floor Level
Wall Identification 1 2 3 Check
Wall Type OSB OSB OSB Total
Tributary Load Distance (ft) - H 16.0 16.0 32.0
Tributary Load Fraction - H 0.500 0.500 1.0
Tributary Load Distance (ft) -G 11.0 11.0 0.0 22.0
Tributary Load Fraction - G 0.500 0.500 0.000 1.0
Applied Shear (lb)1,163 3,193 2,030 6,386
Wall Length (ft)20.0 36.0 42.0
Applied Unit Shear (lb/ft)58 89 48
Shear Wall Length (ft)15.0 14.0 31.0
Resistive Unit Shear (lb/ft) 78 228 65
Shear Wall Height (ft)9.1 9.1 9.1
Unit Wall DL (lb/ft)167 396 396
0.6*[Unit DL on Wall] (lb/ft)100 238 238
Max. Hold-Down 4.0-ft SW (lb) 120
Max. Hold-Down 7.5-ft SW (lb)-296
Max. Hold-Down 14.0-ft SW (lb)410
Max. Hold-Down 15.0-ft SW (lb)-44
Max. Hold-Down 19.5-ft SW (lb) -1,723
Main Floor Level
TABLE I. WIND SHEAR WALL LOADS
TRANSVERSE LOADS
Main Floor Level
LONGITUDINAL LOADS
Revised
12/2/2020
WIND SHEAR WALL LOADS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 19 of 20
Floor Level
Wall Identification A B C D Check
Wall Type OSB OSB OSB OSB Total
Tributary Load Distance (ft) - H 3.0 21.0 18.0 42.0
Tributary Load Fraction - H 0.071 0.500 0.429 1.0
Tributary Load Distance (ft) - G 10.0 10.0 20.0
Tributary Load Fraction - G 0.500 0.500 1.0
Applied Shear (lb)237 1,658 583 2,004 4,481
Wall Length (ft)13.0 13.0 22.0 54.0
Applied Unit Shear (lb/ft)18 128 27 37
Shear Wall Length (ft)7.0 7.0 6.0 36.0
Resistive Unit Shear (lb/ft) 34 237 97 56
Shear Wall Height (ft) 9.1 9.1 9.1 9.1
Unit DL on Wall (lb/ft)167 167 306 166.5
0.60*[Unit DL on Wall] (lb/ft)100 100 184 99.9
Max. Hold-Down 3.0-ft SW (lb) 609 357
Max. Hold-Down 3.5-ft SW (lb)133 1,980
332
Max. Hold-Down 4.0-ft SW (lb) 307
Max. Hold-Down 22.0-ft SW (lb) -592
Floor Level
Wall Identification 1 2 3 Check
Wall Type OSB OSB OSB Total
Tributary Load Distance (ft) - H 0.0 16.0 16.0 32.0
Tributary Load Fraction - H 0.000 0.500 0.500 1.0
Tributary Load Distance (ft) -G 11.0 11.0 0.0 22.0
Tributary Load Fraction - G 0.500 0.500 0.000 1.0
Applied Shear (lb)583 2,241 1,658 4,481
Wall Length (ft)20.0 36.0 42.0
Applied Unit Shear (lb/ft)29 62 39
Shear Wall Length (ft)15.0 14.0 31.0
Resistive Unit Shear (lb/ft) 39 160 53
Shear Wall Height (ft)9.1 9.1 9.1
Unit Wall DL (lb/ft)167 396 396
0.6*[Unit DL on Wall] (lb/ft)100 238 238
Max. Hold-Down 4.0-ft SW (lb) 11
Max. Hold-Down 7.5-ft SW (lb)-405
Max. Hold-Down 14.0-ft SW (lb)-209
Max. Hold-Down 15.0-ft SW (lb)-396
Max. Hold-Down 19.5-ft SW (lb) -1,833
TABLE J. SEISMIC SHEAR WALL LOADS
TRANSVERSE LOADS
Main Floor Level
LONGITUDINAL LOADS
Main Floor Level
Revised
12/2/2020
SEISMIC SHEAR WALL LOADS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
R. Mumbower HiLine Homes Page 20 of 20
Maximum Transverse Shear Load (lb) Calculation V = 4,256
Diaphragm Span (ft) Design Drawings b = 32
Diaphragm Length (ft) Design Drawings L = 42.0
Diaphragm Unit Shear (lb/ft) Calculation w = V/Length =101
Diaphragm Maximum Moment (ft-lb)Calculation M = wL2/8 =22,345
Diaphragm Chord Force (lb) Calculation C = T = M/b =698
Allowable Nail Load (lb)NDS Table 11N D-F & 10d Common
118
Adjustment For Wind/Seismic Loads NDS Table 2.3.2 10-minute loads 1.6
Adjusted Allowable Nail Load (lb)Calculation F = 1.6FNail 188.8
Minimum Number of Nails Required At Splices Calculation NN-Min = C/FA 3.7
Maximum Nail Spacing at Splices (in)Design Drawings S =6.0
Minimum Splice Length (in)Calculation LSplice = SNN-Min 22.2
Design Splice Length (in) Design Drawings Design Specification 48.0
Allowable Diaphragm Chord Force (lb) Calculation 10d @ 6-in o.c.1,699
Cross Sectional Area of Shear Wall Chords (in 2)Design Drawings AChord = 2(1.5)(5.5) =16.5
Axial Chord Stess (psi)Calculation Fc/t = C/A = T/A 42
Allowable Parallel Compressive Stress (psi) WWPA Table 1 No. 2 Douglas Fir Larch 1,350
Allowable Parallel Tensile Stress (psi) WWPA Table 1 No. 2 Douglas Fir Larch 575
Roof Truss Span, b (ft)Design Drawings 32.0
Tributary Area to Truss Connection (sf) Trusses @ 24-in o.c. A = 2b/2 = b 32.0
Maximum Wind Uplift Pressure, 85 mph, C (psf)Calculated [0.5*(0.6*(23.1+16.0)] x 1.21 -14.2
Maximum Wind Uplift Pressure, 95 mph, C (psf)Calculated [0.5*0.6*(27.4+19.1)] x 1.21 -16.9
Maximum Wind Uplift Pressure, 110 mph, C (psf)-23.0
Maximum Wind Uplift Load At Connection (lb)85 mph, Exp. C FUp = pA -453
Maximum Wind Uplift Load At Connection (lb)95 mph, Exp. C FUp = pA -541
Maximum Wind Uplift Load At Connection (lb)110 mph, Exp. C FUp = pA -736
Roof Unit Dead Load, wdl (psf)Design Criteria 15.0
Roof Dead Load to Truss Connection (lb)FDL =0.6 wdlA 288
Net Load to Truss Connection (lb)85 mph, Exp. C FNet = FUp + FDL -165
Net Load to Truss Connection (lb)95 mph, Exp. C FNet = FUp + FDL -253
Net Load to Truss Connection (lb)110 mph, Exp. C FNet = FUp + FDL -448
Allowable Uplift for Simpson H10A Clip (lb)855
Allowable Uplift For Simpson H2.5A Clip (lb)565
Allowable Uplift For Simpson H1 Clip (lb)480
DF with 160% Increase
DF with 160% Increase
DIAPHRAGM CHORD SPLICE & STRESS CALCULATIONS
ROOF UPLIFT CALCULATIONS
Calculated [0.5*0.6*(37.3+26.0)] x 1.21
TABLE K. ROOF DIAPHRAGM CALCULATIONS
DF with 160% Increase
Revised
12/2/2020
ROOF DIAPHRAGM CALCULATIONS
Plan 1248-15 p_g 30-PSF, V_ult 140 mph, Exp C, SDC D2_LATHAM
Printed
12/3/2020
ABDELOUAHAB ABROUS, Ph.D., P.E.
FOOTING CALCULATION PACKAGE
HILINE HOMES PLAN 1248
Alfred & Susan Latham
1003-1585
251 Kennedy Road, Port Hadlock, WA 98339
Hiline Homes
Design & Engineering Department
11306 62nd AVE E, Puyallup, WA 98373
(253) 770-2244 EXT. 2132
wabrous@hilinehomes.com
DESIGNDATA FOUNDATIONDATA
GroundSnowLoad30.0 psf StemWallHeight1.5 ft
RoofLiveLoad 25.2 psf StemWallWidth0.5 ft
RoofDeadLoad 15.0 psf FootingHeight0.5 ft
WallDeadLoad 15.0 psf FootingWidth1.0 ft
FloorLiveLoad40.0 psf FootingFootprintAreaperFoot 1.0 ft2/ft
FloorDeadLoad 10.0 psf ConcreteVolumeperFoot 1.3 ft3/ft
TrussTailProjection 1.33 ft FoundationWeightperFoot 188 plf
AllowableSoilPressure 1,500 psf
ROOFLOADS UPPERFLOORLOADS
MaximumTrussSpan 32.0 ft WallHeight 0.0 ft
TributaryLengthonWall 17.3 ft WallLoad 0.0 plf
LiveLoadonTopofWall 437 plf TributaryFloorLength 0.0 ft
DeadLoadonTopofWall 260 plf FloorLiveLoad 40.0 plf
TotalRoofLoadperFoot 697 plf FloorDeadLoad 10.0 plf
4ft 0.0 plf
510 plf 0.0 plf
303 plf
MAINFLOORLOADS CHECKFORFOOTINGADEQUACY
WallHeight 9ft TotalWeightonSoilperFoot 1,235 plf
WallLoad 135 plf 1,235 psf
TributaryFloorLength 2 ft 726 plf
FloorLiveLoad 80 plf 1,155 plf
FloorDeadLoad 20 plf 1,084 plf
155 plf 1,155 plf
TotalMainFloorLoad 235 plf 1,155 psf
FOOTING=ACCEPTABLE
Pleasefeelfreetocontactmeifyouhaveanyquestions.
Thankyouforyourconsideration,
RaynaMumbower
RaynaMumbower
HiLineHomes
1130662ndAveE
Puyallup,WA98373
(253)770Ͳ2244,Ext.2301
Thisletteraddressestheprojectat251KennedyRoad,PortHadlock,WA98339 .Ihavereviewedthefooting
specificationsdetailedinthesubmittedplansanddeterminedthattheyareadequate.
Revised:Wednesday,December2,2020
Printed:Thursday,December3,2020
JOBNUMBER:1003Ͳ1585
PLANNUMBER:1248
OWNER(S):Alfred&SusanLatham
Belowarethecalculationsrelativetothefoundationfootingsizeunderneaththeloadbearingwalls.
OpeningWidth(if>2*StemHt.)TotalFloorLiveLoad
TotalRoofLiveLoadUnderOpening TotalFloorDeadLoad+WallDL
ActualSoilPressureFactored
TotalRoofDeadLoadUnderOpening
SoilPressureWithoutLoadFactor
D+L
D+Lr
D+.75L+.75Lr
TotalDeadLoad MAX(D+L,D+Lr,D+.75L+.75Lr)
hank you for your consideration,
ayna Mumbower
DESIGNDATA FOUNDATIONDATA
GroundSnowLoad30.0 psf StemWallHeight1.5 ft
RoofLiveLoad 25.2 psf StemWallWidth0.5 ft
RoofDeadLoad 15.0 psf FootingHeight0.5 ft
WallDeadLoad 15.0 psf FootingWidth1.0 ft
FloorLiveLoad40.0 psf FootingFootprintAreaperFoot 1.0 ft2/ft
FloorDeadLoad 10.0 psf ConcreteVolumeperFoot 1.3 ft3/ft
GableRoofProjection 1.00 ft FoundationWeightperFoot 188 plf
AllowableSoilPressure 1,500 psf
ROOFLOADS UPPERFLOORLOADS
TrussSpacing 2.0 ft WallHeight 0.0 ft
TributaryLengthonWall 5.0 ft WallLoad 0.0 plf
LiveLoadonTopofWall 126 plf TributaryFloorLength 0.0 ft
DeadLoadonTopofWall 75 plf FloorLiveLoad 40.0 plf
TotalRoofLoadperFoot 201 plf FloorDeadLoad 10.0 plf
6ft 0.0 plf
189 plf 0.0 plf
113 plf
MAINFLOORLOADS CHECKFORFOOTINGADEQUACY
WallHeight 9ft TotalWeightonSoilperFoot 974 plf
WallLoad 135 plf 974 psf
TributaryFloorLength 7 ft 785 plf
FloorLiveLoad 280 plf 694 plf
FloorDeadLoad 70 plf 843 plf
205 plf 843 plf
TotalMainFloorLoad 485 plf 843 psf
FOOTING=ACCEPTABLE
Pleasefeelfreetocontactmeifyouhaveanyquestions.
Thankyouforyourconsideration,
RaynaMumbower
RaynaMumbower
HiLineHomes
1130662ndAveE
Puyallup,WA98373
(253)770Ͳ2244,Ext.2301
Thisletteraddressestheprojectat251KennedyRoad,PortHadlock,WA98339.Ihavereviewedthefooting
specificationsdetailedinthesubmittedplansanddeterminedthattheyareadequate.
Revised:Wednesday,December2,2020
Printed:Thursday,December3,2020
JOBNUMBER: 1003Ͳ1585
PLANNUMBER: 1248
OWNER(S): Alfred&SusanLatham
TotalRoofDeadLoadUnderOpening
SoilPressureWithoutLoadFactor
D+L
D+Lr
OpeningWidth(if>2*StemHt.)
Belowarethecalculationsrelativetothefoundationfootingsizeunderneaththegablewalls.
TotalFloorLiveLoad
TotalFloorDeadLoad+WallDLTotalRoofLiveLoadUnderOpening
TotalDeadLoad MAX(D+L,D+Lr,D+.75L+.75Lr)
ActualSoilPressureFactored
D+.75L+.75Lr
hank you for your consideration,
ayna Mumbower
DESIGNDATA FOUNDATIONDATA
GroundSnowLoad30.0 psf StemWallHeight1.5 ft
RoofLiveLoad 25.2 psf StemWallWidth0.5 ft
RoofDeadLoad 15.0 psf FootingHeight0.5 ft
WallDeadLoad 15.0 psf FootingWidth1.0 ft
FloorLiveLoad100.0 psf FootingFootprintAreaperFoot 1.0 ft2/ft
FloorDeadLoad 50.0 psf ConcreteVolumeperFoot 1.3 ft3/ft
TrussTailProjection 1.33 ft FoundationWeightperFoot 188 plf
AllowableSoilPressure 1,500 psf
ROOFLOADS UPPERFLOORLOADS
MaximumTrussSpan 20.0 ft WallHeight 0.0 ft
TributaryLengthonWall 11.3 ft WallLoad 0.0 plf
LiveLoadonTopofWall 286 plf TributaryFloorLength 0.0 ft
DeadLoadonTopofWall 170 plf FloorLiveLoad 40.0 plf
TotalRoofLoadperFoot 455 plf FloorDeadLoad 10.0 plf
0ft 0.0 plf
286 plf 0.0 plf
170 plf
MAINFLOORLOADS CHECKFORFOOTINGADEQUACY
WallHeight 9ft TotalWeightonSoilperFoot 1,078 plf
WallLoad 135 plf 1,078 psf
TributaryFloorLength 2 ft 792 plf
FloorLiveLoad 200 plf 878 plf
FloorDeadLoad 100 plf 947 plf
235 plf 947 plf
TotalMainFloorLoad 435 plf 947 psf
FOOTING=ACCEPTABLE
Pleasefeelfreetocontactmeifyouhaveanyquestions.
Thankyouforyourconsideration,
RaynaMumbower
RaynaMumbower
HiLineHomes
1130662ndAveE
Puyallup,WA98373
(253)770Ͳ2244,Ext.2301
Thisletteraddressestheprojectat251KennedyRoad,PortHadlock,WA98339.Ihavereviewedthefooting
specificationsdetailedinthesubmittedplansanddeterminedthattheyareadequate.
Revised:Wednesday,December2,2020
Printed:Thursday,December3,2020
JOBNUMBER: 1003Ͳ1585
PLANNUMBER: 1248
OWNER(S): Alfred&SusanLatham
Belowarethecalculationsrelativetothefoundationfootingsizeunderneaththegarageloadbearingwalls.
OpeningWidth(if>2*StemHt.)TotalFloorLiveLoad
TotalRoofLiveLoadUnderOpening TotalFloorDeadLoad+WallDL
ActualSoilPressureFactored
TotalRoofDeadLoadUnderOpening
SoilPressureWithoutLoadFactor
D+L
D+Lr
D+.75L+.75Lr
TotalDeadLoad MAX(D+L,D+Lr,D+.75L+.75Lr)
hank you for your consideration,
ayna Mumbower
ABDELOUAHAB ABROUS, Ph.D., P.E.
(253) 770-2244 EXT. 2132
11306 62nd AVE E, Puyallup, WA 98373
Design & Engineering Department
Hiline Homes
wabrous@hilinehomes.com
251 Kennedy Road, Port Hadlock, WA 98339
HILINE HOMES PLAN 1248
BEAM CALCULATION PACKAGE
Alfred & Susan Latham
1003-1585
Wood Beam
HiLine HomesLic. # : KW-06012728
DESCRIPTION:3-1/2X13-1/2 GLB GARAGE HEADER
Hiline Homes
11306 62nd Ave E
Puyallup, WA 98373
(253) 770-2244
Software copyright ENERCALC, INC. 1983-2020, Build:12.20.5.31
File: LATHAM RESIDENCE PLAN 1248 JOB 1003-1585.ec6
Project Title:Alfred & Susan Latham
Engineer:Rayna Mumbower
Project ID:1003-1585
Printed: 3 DEC 2020, 2:25PM
Project Descr:1248
CODE REFERENCES
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Completely Unbraced
Load Resistance Factor D
DF/DF
24F-V4
2,400.0
1,850.0
1,650.0
650.0
1,800.0
950.0
265.0
1,100.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
1,600.0 ksi
850.0 ksi
Ebend- yy
Eminbend - yy
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loads
Uniform Load : D = 0.0150, L = 0.030 ksf, Tributary Width = 11.330 ft, (Roof)
DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.850: 1
Load Combination +1.20D+1.60L
Span # where maximum occurs Span # 1
Location of maximum on span 8.250 ft
172.91 psi=
=
3,433.38 psi
3.5x13.5Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +1.20D+1.60L
=
=
=
457.92 psi==
Section used for this span 3.5x13.5
Maximum Shear Stress Ratio 0.378 : 1
0.000 ft=
=
2,919.63 psi
Maximum Deflection
0 <360
293
Ratio =0 <240
Max Downward Transient Deflection 0.441 in 448Ratio =>=360
Max Upward Transient Deflection 0.000 in Ratio =
Max Downward Total Deflection 0.675 in Ratio =>=240
Max Upward Total Deflection 0.000 in
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+L 1 0.6754 8.310 0.0000 0.000
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Overall MAXimum 4.291 4.291
Overall MINimum 2.804 2.804
D Only 1.487 1.487
+D+L 4.291 4.291
+D+0.750L 3.590 3.590
+0.60D 0.892 0.892
L Only 2.804 2.804
Wood Beam
HiLine HomesLic. # : KW-06012728
DESCRIPTION:3-1/2X7-1/2 GLB LIVING ROOM WINDOW HEADER
Hiline Homes
11306 62nd Ave E
Puyallup, WA 98373
(253) 770-2244
Software copyright ENERCALC, INC. 1983-2020, Build:12.20.5.31
File: LATHAM RESIDENCE PLAN 1248 JOB 1003-1585.ec6
Project Title:Alfred & Susan Latham
Engineer:Rayna Mumbower
Project ID:1003-1585
Printed: 3 DEC 2020, 2:25PM
Project Descr:1248
CODE REFERENCES
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Completely Unbraced
Load Resistance Factor D
DF/DF
24F-V4
2,400.0
1,850.0
1,650.0
650.0
1,800.0
950.0
265.0
1,100.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
1,600.0 ksi
850.0 ksi
Ebend- yy
Eminbend - yy
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loads
Uniform Load : D = 0.0150, L = 0.030 ksf, Tributary Width = 17.330 ft, (Roof)
Point Load : D = 0.570, L = 1.140 k @ 2.0 ft, (Girder Truss Support)
DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.791: 1
Load Combination +1.20D+1.60L
Span # where maximum occurs Span # 1
Location of maximum on span 2.586 ft
272.35 psi=
=
4,089.82 psi
3.5x7.5Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +1.20D+1.60L
=
=
=
457.92 psi==
Section used for this span 3.5x7.5
Maximum Shear Stress Ratio 0.595 : 1
0.000 ft=
=
3,234.16 psi
Maximum Deflection
0 <360
379
Ratio =0 <240
Max Downward Transient Deflection 0.136 in 572Ratio =>=360
Max Upward Transient Deflection 0.000 in Ratio =
Max Downward Total Deflection 0.205 in Ratio =>=240
Max Upward Total Deflection 0.000 in
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+L 1 0.2055 3.155 0.0000 0.000
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Overall MAXimum 3.737 3.079
Overall MINimum 2.479 2.040
D Only 1.258 1.039
+D+L 3.737 3.079
+D+0.750L 3.117 2.569
+0.60D 0.755 0.623
L Only 2.479 2.040
Wood Beam
HiLine HomesLic. # : KW-06012728
DESCRIPTION:2X6 D.F.#2 GABLE END HEADERS
Hiline Homes
11306 62nd Ave E
Puyallup, WA 98373
(253) 770-2244
Software copyright ENERCALC, INC. 1983-2020, Build:12.20.5.31
File: LATHAM RESIDENCE PLAN 1248 JOB 1003-1585.ec6
Project Title:Alfred & Susan Latham
Engineer:Rayna Mumbower
Project ID:1003-1585
Printed: 3 DEC 2020, 2:25PM
Project Descr:1248
CODE REFERENCES
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Completely Unbraced
Load Resistance Factor D
Douglas Fir-Larch
No.2
900
900
1350
625
1600
580
180
575 31.21
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loads
Uniform Load : D = 0.0150, L = 0.030 ksf, Tributary Width = 3.0 ft, (Roof)
DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.899: 1
Load Combination +1.20D+1.60L
Span # where maximum occurs Span # 1
Location of maximum on span 3.250 ft
101.87 psi=
=
1,864.88 psi
2x6Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +1.20D+1.60L
=
=
=
311.04 psi==
Section used for this span 2x6
Maximum Shear Stress Ratio 0.328 : 1
6.049 ft=
=
1,677.25 psi
Maximum Deflection
0 <360
469
Ratio =0 <240
Max Downward Transient Deflection 0.109 in 713Ratio =>=360
Max Upward Transient Deflection 0.000 in Ratio =
Max Downward Total Deflection 0.166 in Ratio =>=240
Max Upward Total Deflection 0.000 in
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+L 1 0.1661 3.274 0.0000 0.000
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Overall MAXimum 0.445 0.445
Overall MINimum 0.293 0.293
D Only 0.152 0.152
+D+L 0.445 0.445
+D+0.750L 0.371 0.371
+0.60D 0.091 0.091
L Only 0.293 0.293
Wood Beam
HiLine HomesLic. # : KW-06012728
DESCRIPTION:5-1/2X9 GLB FRONT PORCH FRONT BEAM
Hiline Homes
11306 62nd Ave E
Puyallup, WA 98373
(253) 770-2244
Software copyright ENERCALC, INC. 1983-2020, Build:12.20.5.31
File: LATHAM RESIDENCE PLAN 1248 JOB 1003-1585.ec6
Project Title:Alfred & Susan Latham
Engineer:Rayna Mumbower
Project ID:1003-1585
Printed: 3 DEC 2020, 2:25PM
Project Descr:1248
CODE REFERENCES
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Load Resistance Factor D
DF/DF
24F-V4
2,400.0
1,850.0
1,650.0
650.0
1,800.0
950.0
265.0
1,100.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
1,600.0 ksi
850.0 ksi
Ebend- yy
Eminbend - yy
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loads
Load for Span Number 1
Uniform Load : D = 0.0150, L = 0.030 ksf, Extent = 6.0 -->> 19.0 ft, Tributary Width = 4.30 ft, (Roof)
Varying Uniform Load : D= 0.0150->0.0150, L= 0.030->0.030 ksf, Extent = 0.0 -->> 6.0 ft, Trib Width = 1.0->4.30 ft, (Roof)
DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.497: 1
Load Combination +1.20D+1.60L
Span # where maximum occurs Span # 1
Location of maximum on span 9.708 ft
77.09 psi=
=
4,147.20 psi
5.5x9Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +1.20D+1.60L
=
=
=
457.92 psi==
Section used for this span 5.5x9
Maximum Shear Stress Ratio 0.168 : 1
18.307 ft=
=
2,059.30 psi
Maximum Deflection
0 <360
241
Ratio =0 <240
Max Downward Transient Deflection 0.595 in 382Ratio =>=360
Max Upward Transient Deflection 0.000 in Ratio =
Max Downward Total Deflection 0.946 in Ratio =>=240
Max Upward Total Deflection 0.000 in
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+L 1 0.9457 9.639 0.0000 0.000
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Overall MAXimum 1.542 1.893
Overall MINimum 0.960 1.194
D Only 0.582 0.699
+D+L 1.542 1.893
+D+0.750L 1.302 1.595
+0.60D 0.349 0.419
L Only 0.960 1.194
Wood Beam
HiLine HomesLic. # : KW-06012728
DESCRIPTION:4X10 D.F.#2 FRONT PORCH SIDE BEAM
Hiline Homes
11306 62nd Ave E
Puyallup, WA 98373
(253) 770-2244
Software copyright ENERCALC, INC. 1983-2020, Build:12.20.5.31
File: LATHAM RESIDENCE PLAN 1248 JOB 1003-1585.ec6
Project Title:Alfred & Susan Latham
Engineer:Rayna Mumbower
Project ID:1003-1585
Printed: 3 DEC 2020, 2:25PM
Project Descr:1248
CODE REFERENCES
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Load Resistance Factor D
DouglasFir-Larch
No.2
900.0
900.0
1,350.0
625.0
1,600.0
580.0
180.0
575.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loads
Load for Span Number 1
Varying Uniform Load : D= 0.0150->0.0150, L= 0.030->0.030 ksf, Extent = 0.0 -->> 6.0 ft, Trib Width = 7.330->1.330 ft, (Roof)
DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.173: 1
Load Combination +1.20D+1.60L
Span # where maximum occurs Span # 1
Location of maximum on span 2.672 ft
33.49 psi=
=
1,866.24 psi
4x10Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +1.20D+1.60L
=
=
=
311.04 psi==
Section used for this span 4x10
Maximum Shear Stress Ratio 0.108 : 1
0.000 ft=
=
322.21 psi
Maximum Deflection
0 <360
4486
Ratio =0 <240
Max Downward Transient Deflection 0.010 in 6971Ratio =>=360
Max Upward Transient Deflection 0.000 in Ratio =
Max Downward Total Deflection 0.016 in Ratio =>=240
Max Upward Total Deflection 0.000 in
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+L 1 0.0160 2.934 0.0000 0.000
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Overall MAXimum 0.741 0.471
Overall MINimum 0.480 0.300
D Only 0.261 0.171
+D+L 0.741 0.471
+D+0.750L 0.621 0.396
+0.60D 0.157 0.103
L Only 0.480 0.300