HomeMy WebLinkAboutBLD2021-00280 - 07 PLANSTITLE SHEET
ANDERSON LAKE
FA#: 10092414
CROWN CASTLE: SITE# 846384
GENERATOR INSTALLATION PROJECT
30KW KOHLER DIESEL GENERATOR
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
T-1
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
SITE INFORMATION:
SITE ADDRESS:413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
COUNTY:JEFFERSON
COORDINATES:48.02417° / -122.82295° (FOR NAVIGATION ONLY)
PROPERTY LANDLORD
OR OWNER:CROWN CASTLE: SITE# 846384
TAX ID #:901081022
ZONING:RR
OCCUPANCY GROUP:U - UNMANNED
CONSTRUCTION TYPE:II-B
POWER COMPANY:PUGET SOUND ENERGY
TELCO COMPANY:...
A.D.A. COMPLIANCE:FACILITY IS UNMANNED AND NOT FOR HUMAN
HABITATION
at t &
VICINITY MAP:
SITE
SCOPE OF WORK:
INSTALL (1) STANDBY DIESEL GENERATOR WITH BASE FUEL TANK ON
CONCRETE PAD AND ATS / EQUIPMENT WITHIN PROPOSED COMPOUND
EXPANSION NEAR EXISTING AT&T EQUIPMENT AREA.
INTEGRATE NEW GENERATOR WITH EXISTING SERVICE.
NOTE: NO CHANGES OR ALTERATIONS TO THE TOWER, MOUNTS,
ANTENNAS, FEEDLINES, ETC. IS PROPOSED AS A PART OF THIS SCOPE
OF WORK.
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
N
GOOGLE MAPS 2020
APPROVALS :
AT&T MANAGER
______________________________________________
CONSTRUCTION
MANAGER
______________________________________________
SITE ACQ.
MANAGER
______________________________________________
PROPERTY
OWNER
______________________________________________
LANDLORD
______________________________________________
R
DIG LINE:
THE PLANS SHOW SOME KNOWN SUBSURFACE STRUCTURES, ABOVE
GROUND STRUCTURES, AND/OR EXISTING UTILITIES BELIEVED TO BE IN
THE WORKING AREA. IT IS THE RESPONSIBILITY OF THE CONTRACTOR
TO VERIFY ALL UTILITIES, PIPELINES AND OTHER STRUCTURES SHOWN
OR NOT SHOWN ON THESE PLANS.
ANY DAMAGE TO EXISTING
UTILITIES SHALL BE REPAIRED
TO THE SATISFACTION OF THE
OWNER AND ENGINEER AT THE
CONTRACTOR'S EXPENSE.
AREA MAP:
SITE
GOOGLE MAPS 2020DO NOT SCALE DRAWINGS:
CONTRACTOR SHALL VERIFY ALL PLANS, EXISTING DIMENSIONS, CONDITIONS ON
THE JOB SITE AND SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING OF ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR
THE SAME.
CONTACT INFORMATION:
APPLICANT:AT&T MOBILITY
1375 CAMINO REAL STE 120
SAN BERNARDINO, CA 92408
PHONE: 951.534.8967
PROJECT MANAGER:GENERAL DYNAMICS WIRELESS SERVICES, LLC.
19240 DES MOINES DR. S. BLDG C STE 300
SEA TAC, WA 98048
PHONE: 425.606.8785
CONTACT: CHRISTOPHER HERMAN
ARCHITECTURE &
ENGINEERING:
GEOSTRUCTURAL, LLC.
PO BOX 2621
BOISE, ID 83701
PHONE: 530.539.4787
CONTACT: DON GEORGE
CODE COMPLIANCE:
ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN
ACCORDANCE WITH THE CURRENT EDITIONS OF ALL GOVERNING CODES AS
ADOPTED BY THE LOCAL GOVERNING AUTHORITIES. NOTHING IN THESE
PLANS ARE TO BE CONSTRUCTED TO PERMIT WORK NOT CONFORMING TO
THESE CODES:
INTERNATIONAL BUILDING CODE (IBC) 2018
NATIONAL ELECTRICAL CODE (NEC) 2017
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 13, 30, 37, 70, 72, 110, 111
AMERICAN CONCRETE INSTITUTE (ACI) 318
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA) 222
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA) 607
SHEET INDEX:
SHEET DESCRIPTION
T-1 TITLE SHEET
N-1 GENERAL NOTES
A-0 PARCEL SITE PLAN
A-1 OVERALL SITE PLAN
A-2 ENLARGED SITE PLAN
A-3 ELEVATION VIEWS
S-1 GENERATOR PAD DETAILS & STRUCTURAL NOTES
S-2 GENERAL STRUCTURAL DETAILS
S-3 FENCE & GATE DETAILS
S-4 COMPOUND DETAIL
E-1 ELECTRICAL DETAILS
E-2 ELECTRICAL DETAILS
E-3 ELECTRICAL DETAILS
E-4.0 GENERATOR SPECIFICATIONS
E-4.1 GENERATOR SPECIFICATIONS
E-4.2 GENERATOR SPECIFICATIONS
E-5.0 ATS SPECIFICATIONS
E-5.1 CAM-LOCK BOX SPECIFICATIONS
Apr 03 2021
K
NOTES TO SUBCONTRACTOR:
1. THE GENERAL SUBCONTRACTOR MUST VERIFY ALL DIMENSIONS, CONDITIONS AND ELEVATIONS
BEFORE PROCEEDING WITH THE WORK. ALL DISCREPANCIES SHALL BE RESOLVED BEFORE
PROCEEDING WITH THE WORK. ALL WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN
ACCORDANCE WITH ACCEPTED CONSTRUCTION PRACTICES.
2. IT IS THE INTENTION OF THESE DRAWINGS TO SHOW THE COMPLETED INSTALLATION. THE
SUBCONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING, SHORING, TIES, FORM
WORK, ETC. IN ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL ORDINANCES, TO SAFELY
EXECUTE ALL WORK AND SHALL BE RESPONSIBLE FOR SAME. ALL WORK SHALL BE IN
ACCORDANCE WITH LOCAL CODES.
3. THE SUBCONTRACTOR SHALL USE ADEQUATE NUMBER OF SKILLED WORKMAN WHO ARE
THOROUGHLY TRAINED AND EXPERIENCED IN THE NECESSARY CRAFTS AND WHO ARE COMPLETELY
FAMILIAR WITH THE SPECIFIED REQUIREMENTS AND METHOD NEEDED FOR PROPER PERFORMANCE
OF THE WORK.
4. SUBCONTRACTOR AGREES THAT IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION
PRACTICES, CONSTRUCTION SUBCONTRACTOR WILL BE REQUIRED TO ASSUME SOLE AND COMPLETE
RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THE
PROJECT, INCLUDING THE SAFETY OF ALL PERSONS AND PROPERTY, THAT THIS REQUIREMENT SHALL
BE MADE TO APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS AND
SUBCONTRACTOR FURTHER AGREES TO INDEMNIFY AND HOLD DESIGN ENGINEER HARMLESS FROM
ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH PERFORMANCE OF WORK ON THIS
PROJECT.
5. SITE GROUNDING SHALL COMPLY WITH AT&T WIRELESS SERVICES TECHNICAL SPECIFICATIONS
FOR FACILITY GROUNDING FOR CELL SITE STANDARDS, LATEST EDITION, AND COMPLY WITH AT&T
TOWERS GROUNDING CHECKLIST, LATEST VERSION. WHEN NATIONAL AND LOCAL GROUNDING
CODES ARE MORE STRINGENT THEY SHALL GOVERN.
6. ALL WORK SHALL COMPLY WITH OSHA AND STATE SAFETY REQUIREMENTS. PROCEDURES FOR
THE PROTECTION OF EXCAVATIONS, EXISTING CONSTRUCTION AND UTILITIES SHALL BE
ESTABLISHED PRIOR TO FOUNDATION INSTALLATION.
7. ALL WORK SHALL BE ACCOMPLISHED IN ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL
CODES OR ORDINANCES. THE MOST STRINGENT CODE WILL APPLY IN THE CASE OF
DISCREPANCIES OR DIFFERENCES IN THE CODE REQUIREMENTS.
8. ANY DAMAGE TO THE ADJACENT PROPERTIES WILL BE CORRECTED AT THE SUBCONTRACTOR'S
EXPENSE TO THE SATISFACTION OF THE LANDOWNER AND THE CONSTRUCTION MANAGER.
9. THE COMPLETE BID PACKAGE INCLUDES THESE CONSTRUCTION DRAWINGS ALONG WITH THE
SPECIFICATIONS. SUBCONTRACTOR IS RESPONSIBLE FOR REVIEW OF TOTAL BID PACKAGE PRIOR
TO BID SUBMITTAL.
10. SUBCONTRACTOR SHALL VERIFY LOCATION OF ALL EXISTING UTILITIES WITHIN CONSTRUCTION
LIMITS PRIOR TO CONSTRUCTION.
11. THE SUBCONTRACTOR IS RESPONSIBLE FOR MAINTAINING POSITIVE DRAINAGE ON THE SITE
AT ALL TIMES. SILT AND EROSION CONTROL SHALL BE MAINTAINED ON THE DOWNSTREAM SIDE
OF THE SITE AT ALL TIMES. ANY DAMAGE TO ADJACENT PROPERTIES WILL BE CORRECTED AT THE
SUBCONTRACTOR'S EXPENSE.
12. CLEARING OF TREES AND VEGETATION ON THE SITE SHOULD BE HELD TO A MINIMUM. ONLY
THE TREES NECESSARY FOR CONSTRUCTION OF THE FACILITIES SHALL BE REMOVED. ANY
DAMAGE TO THE PROPERTY OUTSIDE THE LEASED PROPERTY SHALL BE REPAIRED BY THE
SUBCONTRACTOR.
13. ALL SUITABLE BORROW MATERIAL FOR BACK FILL OF THE SITE SHALL BE INCLUDED IN THE BID.
EXCESS TOPSOIL AND UNSUITABLE MATERIAL SHALL BE DISPOSED OF OFF SITE AT LOCATIONS
APPROVED BY GOVERNING AGENCIES PRIOR TO DISPOSAL.
14. PERMITS: THE SUBCONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND INCURRING
THE COST OF ALL REQUIRED PERMITS, INSPECTIONS, CERTIFICATES, ETC.
15. RECORD DRAWINGS: MAINTAIN A RECORD OF ALL CHANGES, SUBSTITUTIONS BETWEEN
WORK AS SPECIFIED AND INSTALLED. RECORD CHANGES ON A CLEAN SET OF CONTRACT
DRAWINGS WHICH SHALL BE TURNED OVER TO THE CONSTRUCTION MANAGER UPON COMPLETION
OF THE PROJECT.
16. THE PLANS SHOW SOME KNOWN SUBSURFACE STRUCTURES, ABOVE GROUND STRUCTURES
AND/OR EXISTING UTILITIES BELIEVED TO BE IN THE WORKING AREA. IT IS THE RESPONSIBILITY OF
THE SUBCONTRACTOR TO VERIFY ALL UTILITIES, PIPELINES AND OTHER STRUCTURES SHOWN OR
NOT SHOWN ON THESE PLANS. THE SUBCONTRACTOR SHALL CONTACT THE LOCAL
LOCATE SERVICE BEFORE DIGGING OR DRILLING. ANY DAMAGE TO EXISTING
UTILITIES SHALL BE REPAIRED TO THE SATISFACTION OF THE OWNER AND ENGINEER AT THE
SUBCONTRACTOR'S EXPENSE.
GENERAL PROJECT NOTES:
1. THIS PROPOSAL IS FOR THE ADDITION OF A NEW GENERATOR ON A NEW CONCRETE PAD TO AN
EXISTING UNMANNED TELECOMMUNICATIONS FACILITY CONSISTING OF AN EQUIPMENT
SHELTER/PLATFORM AND TOWER.
2. THE PROPOSED FACILITY WILL BE UNMANNED AND DOES NOT REQUIRE POTABLE WATER OR
SEWER SERVICE.
3. THE PROPOSED FACILITY IS UNMANNED AND IS NOT FOR HUMAN HABITAT. (NO HANDICAP
ACCESS IS REQUIRED)
4. OCCUPANCY IS LIMITED TO PERIODIC MAINTENANCE AND INSPECTION, APPROXIMATELY 2
TIMES PER MONTH BY AT&T TECHNICIANS.
5. OUTDOOR STORAGE AND SOLID WASTE CONTAINERS ARE NOT PROPOSED.
6. ALL MATERIAL SHALL BE FURNISHED AND WORK SHALL BE PERFORMED IN ACCORDANCE WITH
THE PROJECT SPECIFICATIONS.
7. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING ANY DAMAGE CAUSED BY THE
CONSTRUCTION OPERATION.
8. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS AND INSPECTION
REQUIRED FOR CONSTRUCTION.
9. SUBCONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE SITE ON A DAILY BASIS.
ELECTRICAL NOTES:
A. GENERAL
1. COORDINATE LOCATION AND POWER REQUIREMENTS OF ALL EQUIPMENT WITH AT&T AND
EQUIPMENT SUPPLIER PRIOR TO INSTALLATION.
2. COORDINATE LOCATION AND REQUIREMENTS FOR ELECTRICAL AND TELEPHONE SERVICES
WITH THE PROPERTY REPRESENTATIVE, AT&T AND UTILITY COMPANIES. ROUTING OF
CONDUITS MAY BE MODIFIED TO MEET SITE REQUIREMENTS. EXACT CONDUIT ROUTING TO
BE DETERMINED IN THE FIELD.
3. ALL WIRING AND EQUIPMENT SHOWN ON ELECTRICAL SHEETS SHALL BE FURNISHED AND
INSTALLED UNDER ELECTRICAL PORTION OF CONTRACT UNLESS OTHERWISE NOTED
4. UNINTERRUPTED ELECTRICAL SERVICE FOR EXISTING EQUIPMENT SHALL BE MAINTAINED
DURING THE INSTALLATION OF THE WORK DESCRIBED UNDER THESE DOCUMENTS.
TEMPORARY EQUIPMENT, CABLES AND WHATEVER ELSE IS NECESSARY SHALL BE PROVIDED
AS REQUIRED TO MAINTAIN ELECTRICAL SERVICE. TEMPORARY SERVICE FACILITIES, IF
REQUIRED AT ANY TIME, SHALL NOT BE DISCONNECTED OR REMOVED UNTIL NEW SERVICE
EQUIPMENT IS IN PROPER OPERATION. IF ANY SERVICE OR SYSTEM MUST BE INTERRUPTED,
THE CONTRACTOR SHALL REQUEST PERMISSION IN WRITING STATING THE DATE, TIME, ETC.
THE SERVICE WILL BE INTERRUPTED AND THE AREAS AFFECTED. THIS REQUEST SHALL BE
MADE IN SUFFICIENT TIME FOR PROPER ARRANGEMENTS TO BE MADE. WRITTEN
PERMISSION SHALL BE OBTAINED FROM THE OWNER BEFORE INTERRUPTING ELECTRICAL
SERVICE.
5. COORDINATE NEW WORK WITH OTHER TRADES AND VERIFY EXISTING CONDITIONS TO AVOID
INTERFERENCE. IN CASE OF INTERFERENCE, AT&T'S REPRESENTATIVE WILL DECIDE WHICH
WORK IS TO BE RELOCATED, REGARDLESS OF WHICH WAS FIRST INSTALLED.
6. THE INSTALLATION MUST COMPLY WITH NEC AND ALL FEDERAL, STATE AND LOCAL RULES
AND REGULATIONS.
7. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF
SYSTEMS AND EQUIPMENT UNLESS OTHERWISE DEFINED BY DIMENSIONS OR DETAILS.
EXACT EQUIPMENT LOCATIONS AND RACEWAY ROUTING SHALL BE GOVERNED BY ACTUAL
FIELD CONDITIONS AND/OR DIRECTIONS FROM AT&T'S REPRESENTATIVE.
8. CONTRACTOR SHALL PAY ALL PERMITS AND FEES REQUIRED.
9. ALL MATERIALS SHALL BE FURNISHED AND WORK SHALL BE PERFORMED IN ACCORDANCE
WITH THE APPLICABLE SECTIONS OF THE STANDARDS REFERENCED BELOW:
a. ANSI (AMERICAN NATIONAL STANDARDS INSTITUTE)
b. ASTIM (AMERICAN SOCIETY FOR TESTING MATERIALS)
c. ETL (ELECTRICAL TESTING LABORATORY)
d. ICEA (INSULATED CABLE ENGINEERS ASSOCIATION)
e. IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS)
f. MBFU (NATIONAL BOARD OF FIRE UNDERWRITERS)
g. NESC (NATIONAL ELECTRICAL SAFETY CODE)
h. NEMA (NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION)
i. NFPA (NATIONAL FIRE PROTECTION ASSOCIATION)
j. UL (UNDERWRITER'S LABORATORY)
k. NEC (NATIONAL ELECTRICAL CODE)
10. CONTRACTOR SHALL REVIEW PLANS, DETAILS AND SPECIFICATIONS IN DETAIL AND ADJUST
WORK TO CONFORM WITH ACTUAL SITE CONDITIONS SO THAT ELECTRICAL DEVICES AND
EQUIPMENT WILL BE LOCATED AND READILY ACCESSIBLE. QUANTITIES LISTED IN MATERIAL
LISTS ON THE DRAWINGS ARE FOR INFORMATION ONLY. THE CONTRACTOR SHALL PROVIDE
HIS OWN TAKEOFF FOR MATERIAL QUANTITY AND TYPES BASED ON ACTUAL SITE
CONDITIONS, IN ADDITION, CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS TO
INSTALL EQUIPMENT FURNISHED BY AT&T OR ITS SUPPLIERS. ALL ITEMS NOT SPECIFICALLY
MENTIONED HEREIN OR SHOWN ON THE DRAWINGS, BUT WHICH ARE OBVIOUSLY
NECESSARY TO MAKE A COMPLETE WORKING INSTALLATION, SHALL BE INCLUDED.
11. THE CONTRACTOR OR BIDDER SHALL BEAR THE RESPONSIBILITY OF NOTIFYING (IN WRITING)
AT&T'S REPRESENTATIVE OF ANY CONFLICTS PRIOR TO THE SUBMISSION OF CONTRACTOR'S
PROPOSAL OR PERFORMANCE OF WORK, IN THE EVENT OF DISCREPANCIES THE
CONTRACTOR SHALL PRICE THE MORE COSTLY OR EXTENSIVE WORK, UNLESS DIRECTED IN
WRITING OTHERWISE.
ELECTRICAL NOTES:
12. ALL FLOORS WHERE PENETRATIONS ARE REQUIRED IN BUILDING ARE TO BE CORE DRILLED
AND THEN FIREPROOFED.
B. WIRING/CONDUIT
1. PROVIDE PULL BOXES AND JUNCTION BOXES WHERE SHOWN OR AS REQUIRED BY CODE
SUCH THAT NO MORE THAN THE EQUIVALENT OF FOUR QUARTER BENDS (360 DEGREES
TOTAL) EXIST IN A CONDUIT RUN.
2. ALL POWER AND CONTROL/INDICATION WIRING SHALL BE TYPE THHN/THWN 600V RATED 75
DEGREES CELSIUS, UNLESS NOTED OTHERWISE.
3. CONDUIT BENDS SHALL BE MADE IN ACCORDANCE WITH NEC TABLE 346-10. NO RIGHT
ANGLE DEVICE OTHER THAN STANDARD CONDUIT ELBOWS WITH 12" MINIMUM INSIDE
SWEEPS FOR ALL CONDUITS 2" OR LARGER.
4. POWER WIRING SIZE SHALL NOT BE SMALLER THAN #12 AWG.
5. ALL WIRING SHALL BE COPPER. ALUMINUM WILL NOT BE ACCEPTABLE ALL POWER CIRCUITS
SHALL CONTAIN A GROUND WIRE.
6. PHASE MARKINGS TO BE USED AT POWER CONDUCTOR TERMINATIONS.
7. CONTRACTOR SHALL ENSURE INTEGRITY IS MAINTAINED WHEN INSTALLING CONDUIT AND
WIRING.
8. INSTALL PULL STRING IN ALL CONDUIT.
9. FOR ROOFTOP INSTALLS AND BUILD-OUTS, CONDUITS INSIDE BUILDING AND ON ROOF
SHALL BE RGS, UNLESS OTHERWISE NOTED. FOR RAW LAND SITES AND CO-LOCATES, PVC
SCHEDULE 80 SHALL BE UTILIZED UNLESS NOTED OTHERWISE.
10. MAINTAIN MINIMUM 1'-0" VERTICAL AND 1'-0" HORIZONTAL SEPARATIONS FROM ANY
MECHANICAL GAS PIPING.
11. ALL WIRING ROUTED IN PLENUM TO BE RATED OR IN METALLIC FLEX (LIQUIDTITE) CONDUIT.
C. EQUIPMENT
1. EQUIPMENT/PARTS CONNECTED TO EXISTING PANELS, DUCTS, ETC. SHALL MATCH THE
CHARACTERISTICS (A/C, V, A) OF THAT EQUIPMENT.
2. ALL ELECTRICAL EQUIPMENT OUTSIDE SHALL BE NEMA 3R RATED.
D. GROUNDING
1. ALL GROUND CONNECTIONS TO BUILDING SHALL BE MADE USING TWO-HOLE CONNECTORS.
PROVIDE STAINLESS STEEL BOLTS AND LOCK WASHERS ON ALL MECHANICAL GROUND
CONNECTIONS.
2. ALL EQUIPMENT SURFACES TO BE BONDED TO GROUNDING SYSTEM SHALL BE STRIPPED OF
ALL PAINT AND DIRT AT ANY POINT OF CONNECTION. CONNECTIONS TO VARIOUS METALS SHALL
BE OF A TYPE AS TO PREVENT A GALVANIC OR CORROSIVE REACTION. AREA SHALL BE
REPAINTED FOLLOWING BONDING.
3. ANY METALLIC ITEM WITHIN 6' OF ANY EQUIPMENT OR METALLIC INFRASTRUCTURE (RACKS,
CABLE TRAY.. ETC.) OR GROUND CONDUCTORS MUST BE CONNECTED TO THE
GROUNDING SYSTEM PER AT&T STANDARDS.
4. EXTERIOR, ABOVE GRADE GROUND CONNECTIONS SHALL BE FURNISHED WITH A LIBERAL
PROTECTIVE COATING OF ANTI-OXIDATION COMPOUND.
5. ALL MATERIALS AND LABOR REQUIRED FOR THE GROUNDING SYSTEM AS INDICATED ON THE
PLANS AND DETAILS, AND AS DESCRIBED HEREIN SHALL BE FURNISHED BY THE CONTRACTOR
UNLESS OTHERWISE NOTED.
6. EXACT LOCATION OF GROUND CONNECTION POINTS SHALL BE DETERMINED IN FIELD.
ADJUST LOCATIONS INDICATED ON PLANS ACCORDING TO ACTUAL EQUIPMENT LOCATIONS
TO KEEP THE GROUND CONNECTION CABLES AS SHORT AND STRAIGHT AS PRACTICAL.
7. PROVIDE ALL ELECTRICAL SYSTEM AND EQUIPMENT GROUNDS AS REQUIRED BY THE CURRENT
EDITION OF THE NATIONAL ELECTRIC CODE, THE CURRENT EDITION OF THE NATIONAL
ELECTRICAL SAFETY CODE AND AT&T STANDARDS. BONDING JUMPERS WITH APPROVED GROUND
FITTINGS SHALL BE INSTALLED AT ALL RACEWAYS, EQUIPMENT ENCLOSURES, PULL BOXES, ETC.
TO MAINTAIN GROUND CONTINUITY WHERE REQUIRED BY CODE.
8. ALL BURIED EQUIPMENT GROUND CONDUCTORS SHALL BE #2 AWG BARE, TINNED, SOLID
COPPER UNLESS NOTED OTHERWISE ON THE DRAWINGS.
E. INSPECTION/DOCUMENTATION
1. THE CONTRACTOR, UPON COMPLETION OF HIS WORK, SHALL PROVIDE AS-BUILT DRAWINGS.
INFORMATION SHOULD BE GIVEN TO THE GENERAL CONTRACTOR FOR INCLUSION IN FINAL
AS-BUILT SURVEY DOCUMENTS TO BE GIVEN TO THE OWNER.
2. CONTRACTOR SHALL SUPPLY DOCUMENTATION ATTESTING TO THE COMPLETE GROUND
SYSTEM'S RESISTANCE TO GROUND (MAX. 5 OHMS).
3. AN ELECTRICAL INSPECTION SHALL BE MADE BY AN INSPECTING AGENCY APPROVED BY AT&T'S
REPRESENTATIVE. CONTRACTOR SHALL COORDINATE ALL INSPECTIONS AND OBTAIN
POWER COMPANY APPROVAL.
4. CONTRACTOR SHALL HAVE ATS AND GENERATOR RELAY INSTALLATION AND CONNECTIONS
INSPECTED BY OTHERS TO ENSURE THAT UL LISTING FOR THAT EQUIPMENT IS NOT VOIDED.
200730
GENERAL NOTES
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
N-1 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
N-1
Apr 03 2021
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OH
W
OH
W
OH
W
OH
W
OH
W
OH
W
OH
W
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
BATTERY B
O
X
L
I
F
T
-
O
F
F
S
E
R
V
I
C
E
P
A
N
E
L
B
R
E
A
K
E
R
/
C
O
N
T
R
O
L
AL
T
E
R
N
A
T
O
R
PA
N
E
L
/
I
N
T
A
K
E
E
N
D
R
A
D
I
A
T
O
R
/
E
X
H
A
U
S
T
/
F
U
E
L
E
N
D
1
0
'
-
0
"
10'-0"
4
'
-
0
"
4'-
0
"
5
'
V
E
N
T
R
A
D
I
U
S
5
'
V
E
N
T
R
A
D
I
U
S
X
X
OVERALL
SITE PLAN
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
A-1
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
OVERALL SITE PLAN
N
1SCALE: 1" = 10'-0" (11x17)
PROPOSED GENERATOR
LOCATION, SEE SHEET A-2
FOR ENLARGED SITE PLAN
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
TAX ID#: 901081022
NOTE:
EVERYTHING SHOWN IS EXISTING
UNLESS MARKED PROPOSED
EXISTING CONDITIONS:
THESE DRAWINGS WERE PRODUCED WITH INFORMATION PROVIDED BY THE
CLIENT. LINES, EASEMENTS, AND SETBACKS SHALL BE VERIFIED PRIOR TO
START OF CONSTRUCTION, GEOSTRUCTURAL DOES NOT GUARANTEE THE
ACCURACY OF SAID PROPERTY LINE, EASEMENTS AND SETBACKS.
SO
U
T
H
P
O
R
T
L
A
N
E
MONOPOLE TOWER
GRAVEL
ACCESS DRIVE
AT&T PREFAB CONCRETE
EQUIPMENT SHELTER
EQUIPMENT SHELTER
(OTHER CARRIER)
OVERHEAD
UTILITY LINES
PAD MOUNTED
TRANSFORMER
CHAIN-LINK SECURITY
FENCE
UTILITY
PEDESTAL
UTILITY VAULT
UTILITY BOX ON
WOODEN POST DENSE TREE
COVER
DENSE TREE
COVER
DENSE TREE
COVER
CHAIN-LINK
DOUBLE SWING
ACCESS GATE
APPROX. TREE LINE
Apr 03 2021
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
BATTERY BOX
L
I
F
T
-
O
F
F
S
E
R
V
I
C
E
P
A
N
E
L
B
R
E
A
K
E
R
/
C
O
N
T
R
O
L
AL
T
E
R
N
A
T
O
R
PA
N
E
L
/
I
N
T
A
K
E
E
N
D
R
A
D
I
A
T
O
R
/
E
X
H
A
U
S
T
/
F
U
E
L
E
N
D
1
0
'
-
0
"
10'-0"
4
'
-
0
"
4'
-
0
"
5
'
V
E
N
T
R
A
D
I
U
S
5
'
V
E
N
T
R
A
D
I
U
S
X
X
ENLARGED
SITE PLAN
1ENLARGED SITE PLAN
N
SCALE: 1" = 5'-0" (11x17)
UTILITY NOTE:
THE UTILITIES AS SHOWN ON THIS SET OF DRAWINGS WERE DEVELOPED
FROM RECORD INFORMATION. THE INFORMATION PROVIDED IS IMPLIED NOT
INTENDED TO BE A COMPLETE INVENTORY OF THE UTILITIES IN THIS AREA. IT
IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE LOCATION OF ALL
UTILITIES (WHETHER SHOWN OR NOT) AND PROTECT SAID UTILITIES FROM
ANY DAMAGE CAUSED BY CONTRACTOR'S ACTIVITIES.
EXISTING CONDITIONS:
THESE DRAWINGS WERE PRODUCED WITH INFORMATION PROVIDED BY THE
CLIENT. LINES, EASEMENTS, AND SETBACKS SHALL BE VERIFIED PRIOR TO
START OF CONSTRUCTION, GEOSTRUCTURAL DOES NOT GUARANTEE THE
ACCURACY OF SAID PROPERTY LINE, EASEMENTS AND SETBACKS.
SCOPE OF WORK DETAILS:
GENERAL:
· NEW KOHLER DIESEL GENERATOR PROVIDED BY GENERAL DYNAMICS &
INSTALLED BY GENERAL CONTRACTOR. SEE SHEETS E-4.0, E-4.1, E-4.2.
· NEW CONCRETE PAD PROVIDED & INSTALLED BY GENERAL CONTRACTOR.
SEE SHEET S-1.
· NEW KOHLER AUTOMATIC TRANSFER SWITCH PROVIDED BY GENERAL
DYNAMICS & INSTALLED BY CONTRACTOR. SEE SHEETS S-2, E-5.0, E-5.1.
· NEW COMPOUND FENCE & COMPOUND EXPANSION PROVIDED & INSTALLED
BY GENERAL CONTRACTOR. SEE SHEETS S-3, S-4.
· CONTRACTOR TO VERIFY ALL EXISTING UTILITIES PRIOR TO CONSTRUCTION.
· CONTRACTOR SHALL RESTORE & REPAIR ANY DAMAGED AREAS CAUSED BY
CONSTRUCTION TO ORIGINAL OR BETTER CONDITION.
· INNER AND OUTER TANK TESTING DOCUMENTATION SHALL BE PROVIDED
ONCE TANK IS IN PLACE ON SITE IN ACCORDANCE WITH NFPA 30.
· A CALIBRATION CHART OF PERMANENT AND DURABLE CONSTRUCTION
SHALL BE LOCATED AT THE FILL BOX.
CONDUITS:
· INSTALL PULL STRING IN EACH CONDUIT.
· (1) NEW 2" AND (1) NEW 1" ELECTRICAL CONDUIT WITH CONDUCTORS TO BE
INSTALLED FROM NEW GENERATOR TO NEW ATS. CONDUIT PROVIDED AND
INSTALLED BY GENERAL CONTRACTOR. SEE SHEETS E-1, E-2.
· (2) NEW 1" ELECTRICAL CONDUITS WITH CONDUCTORS TO BE INSTALLED
FROM NEW GENERATOR TO AC PANEL. CONDUIT PROVIDED & INSTALLED BY
GENERAL CONTRACTOR. SEE SHEETS E-1, E-2.
· (1) NEW 1" ALARM CONDUIT & CABLING PROVIDED & INSTALLED BY GENERAL
CONTRACTOR. SEE SHEETS E-1, E-2.
GROUNDING:
· NEW EXOTHERMIC CONNECTION FROM EXISTING GROUND RING TO NEW
MECHANICAL CONNECTION AT GENERATOR CHASSIS. GENERAL
CONTRACTOR TO VERIFY LOCATION IN FIELD. LOCATE GROUND RODS NO
MORE THAN 8'-0" APART. SEE SHEET E-3.
H-FRAME:
· CONTRACTOR TO PROVIDE NEW H-FRAME FOR ATS INSTALLATION (IF
REQUIRED). MATCH EXISTING H-FRAME MATERIAL FOR CONSTRUCTION OF
NEW H-FRAME. SEE SHEET S-2.
R
PROPOSED 12'-0" WIDE DOUBLE
SWING GATE, SEE SHEET S-3
PROPOSED 6' TALL CHAIN-LINK
SECURITY EXPANSION FENCE, SEE
SHEET S-3. LOCATE EXISTING
UTILITIES PRIOR TO EXCAVATION.
CONTRACTOR TO REMOVE SECTION OF
EXISTING FENCE AND GATE AS SHOWN
AND ATTACH EXISTING FENCE FABRIC
TO NEW EXPANSION FENCE POSTS
ACCESS CLEARANCE, TYP.
36" BREAKERS/ALTERNATOR
24" INTAKE/EXHAUST
POWER ROUTING KEYED NOTES:
EXISTING AT&T METER
INTERCEPT EXISTING CONDUIT AND CONDUCTORS AT NEW
DISCONNECT BY METER AND RE-ROUTE THROUGH PROPOSED ATS.
COORDINATE PATH WITH CONSTRUCTION MANAGER
EXISTING AC LOAD CENTER (ABOVE MTS)
PROPOSED AT&T UNDERGROUND GENERATOR CONDUIT ROUTE.
CONTRACTOR TO LOCATE EXISTING UTILITIES PRIOR TO EXCAVATION.
SEE SHEETS E-1, E-2.
SEE SHEET E-1 FOR SINGLE LINE DIAGRAM.
MET
INT
AC
CON
MET
INT
AC
CON
GEN
1
2
3
ATS
NOTE:
EVERYTHING SHOWN IS EXISTING UNLESS MARKED PROPOSED
GRAVEL COMPOUND
EXPANSION, SEE SHEET S-4
ATS / EQUIPMENT KEYED NOTES:
PROPOSED ATS W/ CAMLOCK MOUNTED ON SHELTER WALL WITH 36"
FRONT CLEARANCE. SEE SHEET S-2.ATS
GENERATOR KEYED NOTES:
PROPOSED AT&T 30KW DIESEL GENERATOR W/ SOUND ATTENUATED
ENCLOSURE, NORMAL/EMERGENCY TANK VENTING AND BASE FUEL
TANK ON A CONCRETE PAD. SEE SHEETS S-1, S-2, E-3.
FUEL FILL SHALL BE PROVIDED WITH SPILL CONTROL, WITH A SOLID
FILL CONNECTION, AND WITH OVERFILL PREVENTION
FUEL TANK NORMAL AND EMERGENCY VENTS SHALL TERMINATE AT
LEAST 12'-0" ABOVE THE ADJACENT GRADE. SEE SHEET S-2.
NFPA 704 PLACARD AND OTHER SIGNAGE. SEE SHEET E-4.2.
GEN
1
2
3
GEN PLUG
GRAVEL
COMPOUND
HVAC UNIT
CO
N
C
R
E
T
E
ST
O
O
P
CONTRACTOR TO REMOVE ALL SITE
SIGNAGE FROM EXISTING FENCE
AND REINSTALL ON NEW FENCE
ICE BRIDGE
MONOPOLE TOWER
GRAVEL
ACCESS DRIVE
AT&T PREFAB CONCRETE
EQUIPMENT SHELTER
EQUIPMENT SHELTER
(OTHER CARRIER)
CHAIN-LINK SECURITY
FENCE
DENSE TREE
COVER
CHAIN-LINK
DOUBLE SWING
ACCESS GATE
APPROX. TREE LINE
DENSE TREE
COVER
HVAC UNIT
HVAC UNIT
HVAC UNIT
ICE BRIDGE
ICE BRIDGE
CO
N
C
R
E
T
E
ST
O
O
P
INSPECTION
WELL
1'
-
0
"
4'-0"
3'
-
0
"
17'-0"
8'
-
0
"
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
A-2
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
INT
2'
-
1
1
"
PROPOSED 4'x10'
LEASE AREA
Apr 03 2021
K0
4'
-
0
"
1'-0"
BLOCKOUT
1'
-
8
"
BL
O
C
K
O
U
T
112"
BA
S
E
E
X
T
E
N
T
S
P
E
R
MA
N
U
F
A
C
T
U
R
E
R
#4 U-BARS
CONDUIT STUB-UP AREA;
CONFIRM LOCATION & SIZE
WITH MANUFACTURER
(4) 5 8"Ø x 312" EMBED HILTI KWIK BOLT
TZ STAINLESS STEEL EXPANSION
ANCHOR (OR APPROVED EQUAL).
REFERENCE ICC-ES ESR-1917 REPORT.
INSTALLATION TORQUE
= 60 FT-LB
#4 U-BARS
CONDUIT
STUB-UP AREA
FLEXIBLE STUB CONDUITS.
SEE SHEET E-2.
7" MIN. BOLT
℄ TO EDGE
A
AB
LONGITUDINAL
TR
A
N
S
V
E
R
S
E
10'-0"
1'
-
2
"
BASE EXTENTS PER MANUFACTURER 93 8"
OUTLINE OF GENERATOR
FOOTPRINT
SLAB REINF.,
SEE SECTION A-A
GENERATOR ANCHOR
FRAME
4 3
4 "
3 1 2 "
EM
B
E
D
M
E
N
T
3 3
4 "
HO
L
E
D
E
P
T
H
1116"Ø HOLE (5 8"Ø BIT)
CONCRETE PAD
B
CONCRETE NOTES:
1.PRIOR TO EXCAVATION, CHECK THE AREA FOR UNDERGROUND FACILITIES.
2.ALL CONCRETE SHALL BE IN ACCORDANCE WITH CHAPTER 19 OF THE IBC & ACI 318, "BUILDING CODE REQUIREMENTS FOR
REINFORCED CONCRETE", LATEST EDITION & HAVE THE FOLLOWING PROPERTIES:
A MINIMUM 28-DAY COMPRESSIVE STRENGTH (f'c) OF 4,000 PSI.
B CEMENT SHALL BE "LOW-ALKALI" TYPE IIA (MODERATE SULFATE RESISTANCE, AIR
ENTRAINING) CONFORMING TO ASTM C150.
C MAXIMUM WATER/CEMENT RATIO OF 0.45 AND AIR-ENTRAINED 4% TO 7%.
D CONCRETE PROPORTIONING SHALL BE DESIGNED BY AN APPROVED LABORATORY.
TOLERANCES IN ACCORDANCE WITH ACI 117. COPIES OF CONCRETE MIX SHALL
BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO PLACEMENT.
E ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. USE ONLY
AGGREGATES KNOWN NOT TO CAUSE EXCESSIVE SHRINKAGE. MAXIMUM
AGGREGATE SIZE TO BE 3 4".
F MAXIMUM SLUMP: REFER TO GEOTECHNICAL REPORT WHEN APPLICABLE.
3.FORMWORK FOR CONCRETE SHALL CONFORM TO ACI 347. TOLERANCES FOR FINISHED CONCRETE SURFACES SHALL MEET CLASS-C
REQUIREMENTS. IN NO CASE SHALL FINISHED CONCRETE SURFACES EXCEED THE FOLLOWING VALUES AS MEASURED FROM NEAT
PLAN LINES AND FINISHED GRADES: ± 14" VERTICAL, ± 1" HORIZONTAL.
4.CHAMFER ALL EXPOSED CORNERS AND FILLET ENTRANT ANGLES 3 4" U.N.O.
5.CONCRETE FINISHING: CONCRETE SURFACES SHALL BE FINISHED IN ACCORDANCE WITH ACI. PROVIDE ROUGH FINISH FOR ALL
SURFACES NOT EXPOSED TO VIEW AND SMOOTH FINISH FOR ALL OTHERS, U.N.O.
6.STEEL REINFORCEMENT AND CONCRETE SHOULD BE PLACED IMMEDIATELY UPON COMPLETION OF THE FOUNDATION EXCAVATION.
CONTRACTOR SHALL NOT ALLOW A COLD JOINT TO FORM IN THE CONCRETE. PORTION AT GRADE SHOULD BE FORMED.
TEMPORARY CASING MAY BE REQUIRED TO PREVENT CAVING PRIOR TO CONCRETE PLACEMENT.
REINFORCING STEEL NOTES:
1.ALL REINFORCING STEEL SHALL CONFORM TO ASTM A615. VERTICAL/HORIZONTAL BARS SHALL BE GRADE 60; TIES OR STIRRUPS
SHALL BE A MINIMUM OF GRADE 40. ALL REINFORCING STEEL SHALL HAVE 3" (± 3 8") OF CONCRETE COVER, U.N.O.
2.ALL BAR BENDS, HOOKS, SPLICES AND OTHER REINFORCING STEEL SHALL CONFORM TO THE REQUIREMENTS OF ACI 315.
3.ALL BARS SHALL BE SPLICED WITH A MINIMUM LAP OF 48 BAR DIAMETERS. LAP SPLICES OF DEFORMED BARS IN TENSION ZONES
SHALL BE CLASS-B SPLICES. WELDING OF BARS IS NOT PERMITTED.
4.AT ALL CORNERS AND WALL INTERSECTIONS, PROVIDE BENT HORIZONTAL BARS TO MATCH THE HORIZONTAL REINFORCING STEEL.
5.PROVIDE VERTICAL DOWELS IN FOOTINGS AND AT CONSTRUCTION JOINTS TO MATCH VERTICAL REINFORCING BAR SIZE AND
SPACING.
6.ACI-APPROVED PLASTIC-COATED BAR CHAIRS OR PRECAST CONCRETE BLOCKS SHALL BE PROVIDED FOR SUPPORT OF ALL
GRADE-CAST REINFORCING STEEL & SHALL BE SUFFICIENT IN NUMBER TO PREVENT SAGGING. METAL CLIPS OR SUPPORTS SHALL
NOT BE PLACED IN CONTACT WITH THE FORMS OR THE SUB-GRADE.
7.DOWELS AND ANCHOR BOLTS SHALL BE WIRED OR OTHERWISE HELD IN CORRECT POSITION PRIOR TO PLACING CONCRETE. IN NO
CASE SHALL DOWELS OR ANCHOR BOLTS BE "STABBED" INTO FRESHLY-POURED CONCRETE.
FOUNDATION NOTES:
1.THE CONTRACTOR SHALL READ THE GEOTECHNICAL REPORT AND SHALL CONSULT THE GEOTECHNICAL ENGINEER AS NECESSARY
PRIOR TO CONSTRUCTION.
2.THE GEOTECHNICAL ENGINEER (OR INSPECTOR) SHALL INSPECT THE EXCAVATION PRIOR TO THE PLACEMENT OF CONCRETE AND
SHALL PROVIDE A NOTICE OF INSPECTION FOR THE BUILDING INSPECTOR FOR REVIEW AND RECORDS PURPOSES.
3.THE CONTRACTOR SHALL DETERMINE THE MEANS AND METHODS NECESSARY TO SUPPORT THE EXCAVATION DURING
CONSTRUCTION.
4.REBAR AT BOTTOM OF FOUNDATIONS SHALL BE BONDED TO SITE GROUNDING SYSTEM (WHEN APPLICABLE). SEE ADDITIONAL
DETAILS ON APPROVED A&E CONSTRUCTION DRAWINGS.
5.ALL FOOTINGS TO BE PLACED ON FIRM, UNDISTURBED, INORGANIC MATERIAL. PROOF ROLL SUB-GRADE PRIOR TO PLACING
CONCRETE WHERE THE MATERIAL HAS BEEN DISTURBED BY EQUIPMENT. UNACCEPTABLE/DISTURBED MATERIAL SHALL BE
OVER-EXCAVATED AND REPLACED WITH "LEAN CONCRETE FILL". THE GEOTECHNICAL REPORT SHALL BE REVIEWED AND ADHERED
TO FOR SPECIFIC RECOMMENDATIONS.
6.STRUCTURAL BACKFILL SHALL BE GRANULAR FREE-DRAINING MATERIAL FREE OF DEBRIS, ORGANICS, REFUSE AND OTHERWISE
DELETERIOUS MATERIALS. MATERIAL SHALL BE PLACED IN LIFTS NO GREATER THAN 6" IN DEPTH AND COMPACTED TO 95% OF
MAXIMUM DENSITY AS DETERMINED PER ASTM D1557 (MODIFIED PROCTOR). THE GEOTECHNICAL REPORT SHALL BE REVIEWED AND
ADHERED TO FOR SPECIFIC RECOMMENDATIONS.
MECHANICAL ANCHOR NOTES:
1.HILTI PRODUCTS MUST BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, AS
INCLUDED IN THE ADHESIVE PACKAGING.
2.CONTRACTOR SHALL AVOID DRILLING HOLES IN VERTICAL/HORIZONTAL REINFORCING BARS.
3.HOLES MUST BE WIRE BRUSHED AND BLASTED WITH COMPRESSED AIR PRIOR TO INSTALLATION.
TEMPERATURES/METHODS/WORKING TIME/ETC. ARE TO BE IN ACCORDANCE WITH MANUFACTURER SPECIFICATIONS.
SOIL NOTES:
1.FOUNDATION DESIGN BASED ON THE PRESUMPTIVE MINIMUM SOIL PARAMETERS IN ACCORDANCE WITH THE IBC AND TIA. WHEN A
SITE SPECIFIC GEOTECHNICAL REPORT IS AVAILABLE, THE CONTRACTOR SHALL ADHERE TO ALL RECOMMENDATIONS PROVIDED
THEREIN.
2.ALL FOUNDATIONS TO BE PLACED ON FIRM, UNDISTURBED, INORGANIC MATERIAL. PROOF ROLL SUB-GRADE PRIOR TO PLACING
CONCRETE WHERE THE MATERIAL HAS BEEN DISTURBED BY EQUIPMENT. UNACCEPTABLE/DISTURBED MATERIAL SHALL BE
OVER-EXCAVATED AND REPLACED WITH STRUCTURAL BACKFILL.
3.STRUCTURAL BACKFILL SHALL BE GRANULAR FREE-DRAINING MATERIAL FREE OF DEBRIS, ORGANICS, REFUSE AND OTHERWISE
DELETERIOUS MATERIALS. MATERIAL SHALL BE PLACED IN LIFTS NO GREATER THAN 6" IN DEPTH AND COMPACTED TO 95% OF
MAXIMUM DENSITY AS DETERMINED PER ASTM D1557 (MODIFIED PROCTOR). THE GEOTECHNICAL REPORT SHALL BE REVIEWED AND
ADHERED TO FOR SPECIFIC RECOMMENDATIONS.
13 4"
CLR.
TYP.
ANCHOR FRAME
3"3"
(2) #5 TRANSVERSE
REBAR (THIS LOCATION)
GENERATOR PAD - SECTION B-B
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
GENERATOR PAD - SECTION A-A TYPICAL ANCHOR
SCALE: 1/2" = 1'-0"
GENERATOR PAD DETAIL
(10) #5 TRANSVERSE
REBAR
4"±
33 4" CLR.3" TYP.
8" CONCRETE MIN.
(5) #5 LONGITUDINAL REBAR
OUTLINE OF GENERATOR
3 4" CHAMFER, TYP.
CONTRACTOR TO RESTORE
EXISTING CONDITIONS ON SITE,
SLOPE AWAY AS REQUIRED
6" COMPACTED GRANULAR BASE
COMPACTED SUBGRADE
GENERATOR PAD
DETAILS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
S-1 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
STRUCTURAL DESIGN NOTES:
ALL LOADS DERIVED FROM REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE, ASCE 7 & ANSI TIA-222.
BUILDING & COMMUNICATION STRUCTURES: (48.02417° / -122.82295°)
1.WIND LOADS: IBC 2018 & ASCE 7-16
V = 97 MPH ULTIMATE WIND SPEED
STRUCTURE CLASS = II; EXPOSURE CATEGORY = C; TOPOGRAPHIC CATEGORY = 1.
IMPORTANCE FACTOR = 1.0.
2.SEISMIC LOADS: IBC 2018 & ASCE 7-16
STRUCTURE CLASS = II; SITE CLASS = D.
SS = 1.322 ; S1 = 0.482 ; SDS = 1.057
S-1
Apr 03 2021
ATS MOUNTING DETAIL (IF REQUIRED)
PE
R
M
A
N
U
F
A
C
T
U
R
E
R
PE
R
M
A
N
U
F
A
C
T
U
R
E
R
SECTION A-A
3 8"Ø U-BOLT. FOLLOW
MANUFACTURER RECOMMENDATIONS
FOR BOLT TORQUE.
GALVANIZED
H-FRAME POST
GRADE
UNISTRUT WALL ATTACHMENT:
WALL CONSTRUCTION
TYPE FASTENER
HOLLOW 3/8" DIA. TOGGLE BOLT
HOLLOW, AT STUD 3/8" DIA. LAG SCREW
CONCRETE BLOCK
(HOLLOW)
7/16" DIA. HILTI HY-270 WITH SCREEN,
MINIMUM EMBEDMENT 2-1/2"
CONCRETE
(SOLID)
7/16" DIA. HILTI HY-200, MINIMUM
EMBEDMENT 2-1/2"
NOTES:
1. USE GALVANIZED OR STAINLESS STEEL HARDWARE FOR
WALL MOUNT AND CONNECTION OF CHANNELS
2. GC SHALL USE NON-SHRINKING CAULK TO WEATHER SEAL
ALL PENETRATIONS INTO OR THROUGH SHELTER WALL
K
PROPOSED GENERATOR
W/ DIESEL FUEL TANK ON
CONCRETE PAD
VENT PIPE, TYP. OF (2)
12
'
M
I
N
.
DOUBLE WALL FUEL TANK BASE SPECIFICATION:
REF: AT&T 30KW GENERATOR PACKAGE
UL REGISTRATION NUMBER: MH 18459
UL 142 DOUBLE WALL FUEL TANK BASE SPECIFICATION
FUEL TANK BASE CONSTRUCTION:
+BE CONSTRUCTED IN ACCORDANCE WITH UNDERWRITERS LABORATORIES
STANDARD UL-142. BE CONSTRUCTED IN ACCORDANCE WITH FLAMMABLE
COMBUSTIBLE LIQUIDS CODE, NFPA 30; THE STANDARD FOR INSTALLATION USE OF
STATIONARY COMBUSTIBLE ENGINE GAS TURBINES, NFPA 37; AND THE STANDARD
FOR EMERGENCY STANDBY POWER SYSTEMS, NFPA 110.
+ANCHORS MINIMUM (4) 5/8" FOR GEN-SET MOUNTING
SUB BASE TANK TESTING:
+PRIMARY TANK & SECONDARY CONTAINMENT BASIN SECTIONS SHALL BE
PRESSURIZED AT 3-5 PSI AND LEAK-CHECKED TO ENSURE INTEGRITY OF SUB BASE
WELD SEAMS PER UL-142 STANDARDS
FUEL FILL: 5 GALLON SPILL CONTAINMENT WITH ALARM
+40% REMAINING FOR ALARM
+20% REMAINING FOR SHUT-DOWN
FACTORY PRE-SET AT 95% FULL FOR ALARM
FUEL CONTAINMENT BASIN:
+SUB BASE TANK SHALL INCLUDE A WELDED STEEL CONTAINMENT BASIN, SIZED AT A
MINIMUM OF 110% OF THE TANK. CAPACITY TO PREVENT ESCAPE OF FUEL INTO THE
ENVIRONMENT IN THE EVENT OF A TANK RUPTURE. A FUEL CONTAINMENT BASIN
LEAK DETECTOR SWITCH SHALL BE PROVIDED.
GENERATOR VENTING DETAIL
VENT BRACING TO
ENCLOSURE PER
MANUFACTURER
MOUNTING HOLES, TYP. OF (4)
NEW AUTOMATIC TRANSFER
SWITCH MOUNTED TO NEW
UNISTRUT. SEE SHEETS E-5.0, 5.1
(CAM-LOCK NOT SHOWN FOR
CLARITY)
1-5/8" P1000T UNISTRUT
MOUNTED TO WALL OR TO NEW
H-FRAME POSTS W/ FASTENER
AT EACH END, SEE H-FRAME
DETAIL, TYP. OF (2)
NEW MECHANICAL CONNECTION
WITH #2 AWG TO EXISTING
GROUND RING, SEE SHEET E-3
3' MIN.
(4'-6" MIN. IF SUB-PANEL REQ'D)
6'
-
0
"
PIPE CAP, TYP.
H-FRAME DETAIL
A A
6" MAX.
15 8" P1000T UNISTRUT MEMBER
INSTALLED TO H-FRAME POSTS.
APPLY TWO COATS OF
COLD-GALV COMPOUND TO
"CUT" ENDS. INSTALL VINYL END
CAPS. (TO BE FIELD LOCATED AS
REQUIRED)
3-
0
"
(
M
I
N
.
)
O
R
P
E
R
LO
C
A
L
F
R
O
S
T
D
E
P
T
H
4"
37
.
6
"
(
V
E
R
I
F
Y
W
/
AT
S
M
A
N
U
F
.
)
NEW PIPE2.5STD (2.875"OD
SCHEDULE 40) H-FRAME POST,
TYP.
(ALTERNATE INSTALLATION:
CONTRACTOR MAY ELECT TO
USE EXISTING H-FRAME POST
IF AVAILABLE)
2"
SUB-PANEL
IF REQ'D
AUTOMATIC
TRANSFER
SWITCH
CA
M
-
L
O
C
K
BO
X
12"Ø CONCRETE
FOOTING
1" CROWN
OR FOOTPAD
⅊3 4x7x7
(4) 12"Ø x 3.5" EMBED HILTI
KWIK BOLT TZ STAINLESS
STEEL EXPANSION ANCHOR
(OR APPROVED EQUAL).
REFERENCE ICC-ES ESR-1917
REPORT.
3.5"
3/16
POST
FOOT PAD FOR SLAB-TOP INSTALLATION
(IF APPLICABLE)
1" DRY PACK, IF REQ'D
5"3"(MIN.) TO EDGE
OF SLAB
#2 SOLID, TINNED BARE
COPPER WIRE CADWELD
POSTS TO GROUND RING
GROUND RING
ATS LOCATION NOTE:
ATS LOCATION SHOWN IN PLANS IS THE BEST AVAILABLE BASED ON THE INFORMATION
PROVIDED. ALTERNATIVE LOCATION MAY BE REQUIRED AND SHALL BE APPROVED BY
CONSTRUCTION MANAGER AND/OR LANDLORD. THIS DETAIL PROVIDES ALTERNATIVE
METHODS OF INSTALLATION (NOT ALL DETAILS MAY BE USED).
GENERAL
STRUCTURAL DETAILS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
S-2 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
S-2
Apr 03 2021
TOP RAIL
LINE POST
CHAIN-LINK
FABRIC MESH
WEATHERTIGHT POST CAP, TYP.
TENSION BAR, USE (1) FOR EACH END OR GATE
POST, (2) FOR EACH CORNER POST
END, GATE, CORNER OR PULL POST
TENSION BAND, (1) PER FOOT OF FENCE
HEIGHT
DIAGONAL ROD WITH STEEL TURNBUCKLE
ON GATE & ALL CORNERS WITH
HORIZONTAL BRACE
SEE LINE POST
SPACING SCHEDULE
SEE LINE POST
SPACING SCHEDULE
1" CROWN
TYP.
3"
C
L
R
12"Ø (MIN)
3'
-
6
"
M
I
N
0'-0"FINISH GRADE
LINE POST
BOTTOM
TENSION WIRE
CONC.
PIER, TYP.
BRACE RAIL
BRACE RAIL,
EA. CORNER,
EA. WAY
6'
T
O
8
'
C
H
A
I
N
-
L
I
N
K
F
A
B
R
I
C
9"Ø (MIN)
3'
-
0
"
M
I
N
3"
C
L
R
3'
-
0
"
M
I
N
3"
C
L
R
9"Ø (MIN)
2"
M
A
X
CL
E
A
R
A
N
C
E
F
R
O
M
GR
A
D
E
,
T
Y
P
.
X X X X X X X X X X X X X X
X X X X X X X X X X X X X X
X X X X X X X X X X X X X X (3) ROWS
GALVANIZED
BARBED WIRE
BARB ARMS WITH INTEGRAL
A0
CHAIN-LINK ACCESS GATE DETAIL (IF REQUIRED)
CHAIN-LINK GATE/FENCE SPECIFICATIONS:
(INSTALL FENCING PER ASTM F567 / SWING GATES PER ASTM F900)NOTES:
GATE POST
4.500" O.D. SCHEDULE 40 PIPE FOR GATE WIDTHS UP T0 6
FEET, PER ASTM F1083.
POST & FENCE PIPE SIZES ARE FENCE
INDUSTRY STANDARD. ALL PIPE TO BE
HOT-DIP GALV. CROSS BRACE ALL POSTS
EXCEPT INTERMEDIATES.
LINE POST 6' TALL = 2.375" O.D. SCHEDULE 40 PIPE PER ASTM F1083.
8' TALL = 2.875" O.D. SCHEDULE 40 PIPE PER ASTM F1083.
CORNER POST 3.500" O.D. SCHEDULE 40 PIPE PER ASTM F1083.
TOP RAIL/BRACE RAIL 1.875" O.D. SCHEDULE 40 PIPE, PER ASTM F1083.
GATE FRAME 1.875" O.D. SCHEDULED 40 PIPE, PER ASTM F1083.
GATE LATCH 1.375" O.D. PLUNGER ROD W/ MUSHROOM TYPE CATCH AND
LOCK.
CONTRACTOR TO INSTALL (2) GATE
HOLDBACKS TO HOLD GATE OPEN DURING
USE.
FABRIC 9 GA. CORE WIRE SIZE 2" MESH, CONFORMING TO ASTM
A392.
-
TIE WIRE
MINIMUM 11 GA. GALVANIZED STEEL AT POSTS AND RAILS
A SINGLE WRAP OF FABRIC TIE AND AT TENSION WIRE BY
HOG RINGS SPACED MAX. 24" INTERVALS.
-
TENSION WIRE 7 GA. GALVANIZED STEEL.-
BARBED WIRE
DOUBLE STRAND 12-1/2" O.D. TWISTED WIRE TO MATCH
WITH FABRIC 14 GA. 4 PT. BARBS SPACED ON
APPROXIMATELY 5" CENTERS.
LOCAL ORDINANCE OF BARBED WIRE
PERMIT REQUIREMENTS SHALL BE
COMPLIED WITH IF REQUIRED.
CHAIN-LINK FENCE DETAIL
(3) ROWS GALVANIZED
BARBED WIRE
GATE FRAME
TENSION BAR, USE (1) FOR EACH
GATE POST
"STYMIE LOCK" ASSEMBLY
PLUNGER BAR
DIAGONAL ROD WITH STEEL
TURNBUCKLE ON GATE & ALL CORNERS
WITH HORIZONTAL BRACE
GATE FRAME
"MUSHROOM" TYPE CENTER GATE
STOP EMBEDDED IN CONCRETE
CHAIN-LINK FABRIC MESH
12"Ø CONC. PIER, TYP.
SEE PLANS SHEET
3'
-
6
"
3"
C
L
R
1"
C
R
O
W
N
6'
-
0
"
C
H
A
I
N
-
L
I
N
K
F
A
B
R
I
C
1'
-
0
"
2"
0'-0"FINISH GRADE
14GA BRAIDED GROUND
(POST TO GATE FRAME), TYP.
#2 SOLID, TINNED BARE COPPER WIRE
CADWELD POST TO GROUND RING, TYP.
#2 SOLID, TINNED BARE
COPPER WIRE CADWELD
CORNER POSTS TO
GROUND RING
GROUND RING
GROUND RING
EXISTING CONDITIONS:
1 CONTRACTOR TO MATCH EXISTING HEIGHT AND SECURITY IMPLEMENTS.
A STANDARD 6' FENCE IS SHOWN AND MAY REQUIRE MODIFICATIONS TO
MATCH EXISTING.
2 CONTRACTOR TO MATCH EXISTING FENCE DESIGN AND FINISH BY ADDING
SLATS, MESH, PAINT, ETC..
LINE POST SPACING SCHEDULE:
DESCRIPTION MAXIMUM SPACING
6' TALL MESH ONLY 10'-0"
6' TALL MESH W/ PRIVACY SLATS 5'-0"
8' TALL MESH ONLY 8'-0"
8' TALL MESH W/ PRIVACY SLATS 4'-0"
⅊3 4x7x7
(4) 12"Ø x 3.5" EMBED HILTI
KWIK BOLT TZ STAINLESS
STEEL EXPANSION ANCHOR
(OR APPROVED EQUAL).
REFERENCE ICC-ES ESR-1917
REPORT.
3.5"
3/16
POST
LINE POST FOOTPAD FOR
SLAB-TOP INSTALLATION
(IF APPLICABLE)
1" DRY PACK, IF REQ'D
5"3"(MIN.) TO EDGE
OF SLAB
⅊3 4x9x9
(4) 12"Ø x 3.5" EMBED HILTI
KWIK BOLT TZ STAINLESS
STEEL EXPANSION ANCHOR
(OR APPROVED EQUAL).
REFERENCE ICC-ES ESR-1917
REPORT.
3.5"
3/16
POST
GATE/CORNER POST FOOTPAD FOR
SLAB-TOP INSTALLATION
(IF APPLICABLE)
1" DRY PACK, IF REQ'D
7"3"(MIN.) TO EDGE
OF SLAB
FENCE & GATE
DETAILS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
S-3
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
Apr 03 2021
AGGREGATE NOTES:
1 THE AGGREGATE MATERIAL TO BE USED WILL BE PRODUCED FROM SOUND, TOUGH, DURABLE ROCK AND SHALL BE
UNIFORM IN QUALITY AND GRADATION. THE CRUSHED MATERIAL WILL BE REASONABLY FREE FROM SOFT OR
DISINTEGRATED PIECES, ORGANIC MATERIALS, AND OTHER OBJECTIONABLE MATTER.
2 THE AGGREGATE MATERIAL WILL SHOW A LOSS LESS THAN 35% IN THE LOS ANGELES ABRASION TEST.
3 THE PERCENTAGE OF SOFT PARTICLES, AS DETERMINED BY THE CLAY LUMPS AND FRIABLE PARTICLES [AASHTO T
112], SHALL NOT BE MORE THAN 5%.
4 THE AGGREGATE MATERIAL USED WILL NOT HAVE A SAND EQUIVALENT LESS THAN 30 IF 5% OR MORE OF THE
MATERIAL PASSES THE NUMBER 200 SIEVE.
5 80% OF THE GRAVEL (BY WEIGHT) OF THE COMBINED COURSE AGGREGATE SHALL HAVE THREE OR MORE ROUGH
ANGULAR SURFACES AND PRODUCED BY CRUSHING OF THE ROCK.
6 THE PLASTICITY INDEX OF THE FINISHED AGGREGATE PRODUCT SHALL NOT EXCEED 6.
AGGREGATE GRADATION CHART:
(% BY WEIGHT PASSING SIEVES)
SIEVE SIZE 2"-MINUS 3 4"-MINUS
212"100 -
2"90-100 -
1"55-83 100
3 4"-90-100
No. 4 30-60 40-65
No. 8 -30-50
No. 30 10-25 -
No. 200 0-8 3-9
COMPACTION NOTE:
STRUCTURAL FILL SHALL BE GRANULAR FREE-DRAINING MATERIAL FREE OF DEBRIS, ORGANICS, REFUSE AND OTHERWISE
DELETERIOUS MATERIALS. MATERIAL SHALL BE PLACED IN LIFTS NO GREATER THAN 12" IN DEPTH AND COMPACTED TO 95%
OF MAXIMUM DENSITY AS DETERMINED PER ASTM D1557.
ELEVATE COMPOUND
(IF APPLICABLE)
4"
PROOF-ROLL SUBGRADE PRIOR TO
PLACEMENT OF FILL MATERIAL
2
1
UNDISTURBED SOIL
CLIENT APPROVED WEED
BARRIER
4" OF 3 4" CRUSHED ROCK
LEASE AREA
SEE PLAN
CLEAR & GRUB UPPER 4" (MIN.) OF
EXISTING GROUND SURFACE &
REPLACE W/ STRUCTURAL FILL
EXISTING GRADE
COMPACTED 2"-MINUS
STRUCTURAL FILL,
SEE GRADATION CHART
COMPOUND DETAIL
A2
COMPOUND DETAIL
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
S-4
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
Apr 03 2021
K0
M
2 7
5
6
3
120/240, 1 , 60Hz
20A
20A
G
20A
CONDUIT / WIRE SCHEDULE:
NO.FROM TO WIRES GROUND CONDUIT
SIZE FUNCTION
NORMAL POWER
SOURCE
AUTOMATIC
TRANSFER SWITCH (3) 3/O (1) #4 2"NORMAL POWER FEEDER TO ATS (CUT BACK
EXISTING)
AUTOMATIC
TRANSFER SWITCH LOAD CENTER (3) 3/O (1) #4 2"POWER FEEDER FROM ATS TO PANEL
GENERATOR AUTOMATIC
TRANSFER SWITCH (3) .(1) #4 2"EMERGENCY POWER FEEDER TO ATS
AUTOMATIC
TRANSFER SWITCH GENERATOR (2) #10 (1) #10 1"START CIRCUIT
LOAD CENTER
(DISTRIBUTION
CENTER)
GENERATOR, ATS
(2) #12
(2) #12
(2) #12
(1) #12
(1) #12
(1) #12
1"
1"
1"
CIRCUIT FOR GENERATOR BLOCK HEATER &
BATTERY HEATER, CIRCUIT FOR BATTERY CHARGER,
CIRCUIT FOR ATS CONTROLS
GENERATOR AUTOMATIC
TRANSFER SWITCH
12-PAIR 24
AWG OR 2EA
6-PAIR CAT5
N/A 1"
ALARM CABLES (1) 12 PAIR 24 AWG. PROVIDE 24" OF
SLACK CABLE. FINAL PUNCH DOWN IS BY AT&T TECH.
LABEL ALL WIRES
AUTOMATIC
TRANSFER SWITCH ALARM BLOCK
(2) 12-PAIR 24
AWG OR (2)
6-PAIR CAT5
(1) 1-PAIR
24AWG
N/A 1"
ALARM CABLES (1) 12 PAIR 24 AWG (RUN THRU
INTERIOR OF SHELTER OR GROUND EQUIPMENT &
INTO ALARM BOX). PROVIDE SINGLE PAIR FOR
COMMERCIAL POWER FAIL ALARM. PROVIDE 24" OF
SLACK CABLE. FINAL PUNCH DOWN IS BY AT&T TECH.
LABEL ALL WIRES
1
2
3
4
5
SINGLE LINE DIAGRAM
ALARM WIRE IDENTIFICATION CHART:
WIRE ALARM
BROWN
BROWN / WHITE GENERATOR RUNNING
GREEN
GREEN / WHITE CRITICAL FAULT
BLUE
BLUE / WHITE MINOR FAULT
ORANGE
ORANGE / WHITE LOW FUEL
BROWN *
BROWN / WHITE *FUEL LEAK
*CAT5 CABLE ONLY, FROM 2ND CAT5 CABLE
EXISTING DISTRIBUTION PANEL
PROPOSED 30KW GENERATOR
4
6
7
GENERATOR NEUTRAL SHALL NOT
BE BONDED TO GROUND AT THE
GENERATOR. IT SHALL BE SOLIDLY
CONNECTED THROUGH THE ATS TO
THE UTILITY SERVICE NEUTRAL.
(OPEN TRANSITION, FLOATING
NEUTRAL AT GENERATOR) THIS
GENERATOR IS NOT INTENDED TO
BE A SEPARATELY DERIVED
SYSTEM.
INTERCEPT EXISTING CONDUIT AND CONDUCTORS
PRIOR TO MAIN PANEL AND RE-ROUTE TO NEW ATS
1
(3) NEW 20A WITH
ADEQUATE KAIC RATING
FOR AFC AT PANEL
PROPOSED 120/240, 1 , 60 Hz
200A NEMA 3R ATS
SCCR OF 100kA SEE ATS
POLE NOTE
EXISTING
METER
EXISTING 200A
SERVICE FEED
PROPOSED CAM-LOCK BOX FOR
PORTABLE GENERATOR CONNECTION
(3) 3/O
(1) #4 GROUND
2" PVC SCH80
EXISTING 120/240, 1 200A
DISTRIBUTION PANEL PROPOSED 66 BLOCK FOR GENERATOR
ALARM CIRCUITS (ON EXISTING TELCO BOARD)
GENERATOR TO ATS:
CONTRACTOR TO CONFIRM GENERATOR CIRCUIT BREAKER SIZE
PRIOR TO INSTALLATION AND USE THE APPROPRIATE SIZE
CONDUCTORS FOR THE BREAKER TO ATS ACCORDINGLY PER
NEC REQUIREMENTS.
1
1
1
INTERLOCK
CONTRACTOR SHALL NOT SUBMIT BIDS
OR PERFORM CONSTRUCTION WORK ON
THIS PROJECT WITHOUT ACCESS TO THE
CURRENT COMPLETE SET OF DRAWINGS
LISTED IN THE TITLE-SHEET INDEX.
PROPOSED 200A SERVICE
DISCONNECT
PANEL NOTES:
1.CONTRACTOR TO LABEL WIRES WITH P-TOUCH OR SIMILAR LABELS ONLY. ABSOLUTELY NO HANDWRITTEN LABELS.
2.CONTRACTOR SHALL PERFORM A POWER STUDY ON EXISTING AC PANEL PRIOR TO INSTALLING, CHANGING,
ALTERING, OR REMOVING ANY BREAKER. NO WORK SHALL BE COMPLETED ON AC PANEL WITHOUT PROPER
INSPECTOR OR ENGINEER APPROVED DOCUMENTATION CONFIRMING CAPACITY ON SITE. ALL WORK SHALL
CONFORM TO NEC VERSION ENFORCED BY A.H.J. AT TIME OF INSTALLATION.
3.CONTRACTOR SHALL VERIFY THAT THE MAXIMUM DEMAND FOR ALL CONNECTED EQUIPMENT AT THIS SITE AS
CALCULATED PER NEC 220 DOES NOT EXCEED THE GENERATOR OUTPUT CIRCUIT BREAKER RATING. (SEE NOTE #4 ALSO.)
4.IF MAXIMUM DEMAND OF GENERATOR OUTPUT CIRCUIT BREAKER RATING AS CALCULATED PER NEC 220 IS
CONTINGENT ON THE TWO HVAC UNITS NOT OPERATING CONCURRENTLY, THEN CONTRACTOR SHALL VERIFY THAT
THE HVAC LEAD/LAG CONTROLLER IS CONFIGURED TO PREVENT CONCURRENT OPERATION. IF NOT, THEN
CONTRACTOR SHALL RECONFIGURE IT AS NEEDED TO PREVENT TRIPPING THE CIRCUIT BREAKER.
G N
NOTE: ALL
CONDUCTORS TO BE
COPPER UNLESS
NOTED OTHERWISE.
200A
120/240, 1
120/240, 1
120/240, 1
(3)
(3)
(3)
(3)
z
ATS POLE NOTE:
PROPOSED ATS/CAMLOCK ARE
CONFIGURABLE FOR SINGLE OR
THREE PHASE OPERATION. IN
SINGLE PHASE INSTALLATIONS,
3-POLE ATS TO BE INSTALLED
WITH ONE POLE NOT
CONNECTED (UNUSED) AND TO
BE CONFIGURED FOR
DUAL-POLE USE. NEUTRAL
SHALL NOT BE SWITCHED.
#2 AWG BARE SOLID TINNED
COPPER GROUND PROTECTED
IN RIGID OR INTERMEDIATE
METAL CONDUIT (RMC/IMC) OR
RIGID PVC CONDUIT, TYP.
BREAKERS POTENTIALLY AVAILABLE TO BE
REMOVED. CONTRACTOR TO CONFIRM.
(3) PROPOSED 20 AMP BREAKERS FOR
BLOCK HEATER, BATTERY HEATER, AND
BATTERY CHARGER ON NEW AT&T
GENERATOR (INSTALL FILLER PLATES ON
ANY OPEN SLOTS)
ELECTRICAL
DETAILS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
E-1 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
E-1
Apr 03 2021
K
CONDUIT COUPLING
SLIP JOINT
CONDUIT ELBOW
CONDUIT PLUG FOR
SPARE CONDUIT
PROPOSED
CONDUIT
U.L. SYSTEM NO. C-AJ-1150
CONDUIT THROUGH BEARING WALL SIMILAR TO U.L. DESIGN NO. U902
F RATING = 3 HR
T RATING = O HR
1.FLOOR OR WALL ASSEMBLY : MINIMUM 4-1/2" THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF
ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAMETER OF OPENING IS 4". (SEE
CONCRETE BLOCKS 9CATZ) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES
OF MANUFACTURERS.
2.THROUGH PENETRATIONS : ONE METALLIC PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED
ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE ANNULAR SPACE SHALL BE
MINIMUM 0". (POINT CONTACT) TO MAXIMUM 1-3/8". THE FOLLOWING TYPES AND SIZES
OF METALLIC PIPES OR CONDUITS MAY BE USED:
A. STEEL PIPE-NOMINAL 6" DIAMETER (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE
B. IRON PIPE-NOMINAL 6" DIAMETER (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT - NOMINAL 4" DIAMETER (OR SMALLER) STEEL ELECTRICAL METALLIC
TUBING OR NOMINAL 3-1/2" DIAMETER (OR SMALLER) STEEL CONDUIT.
3.PACKING MATERIAL: MINIMUM 6" THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATTING
INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING
MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES
OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL
MATERIAL.
4.FILL, VOID, OR CAVITY MATERIAL*: SEALANT: MINIMUM 1/4" THICKNESS OF FILL
MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR AND
WITH BOTH SURFACES OF WALL. AT THE POINT CONTACT LOCATION BETWEEN PIPE AND
CONCRETE, A MINIMUM 1/2" DIAMETER BEAD OF FILL MATERIAL SHALL BE APPLIED AT
THE CONCRETE/PIPE INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH
SURFACES OF WALL. W-RATING APPLIES ONLY WHEN CP601S OR CP604 SEALANT IS
USED.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC. : CP601S, CP604, CP606, OR FS-ONE
SEALANT.
* BEARING THE UL CLASSIFICATION MARK
A
A
4
2
3
2
4
4
NOTE:
1.IF EXISTING CONSTRUCTION VARIES
FROM THIS DETAIL, AN EQUAL 3-HR
U.L. PENETRATION APPROPRIATE FOR
THE EXISTING WALL TYPE SHALL BE
CONSTRUCTED
2.GC SHALL USE NON-SHRINKING CAULK
TO WEATHERSEAL ALL PENETRATIONS
INTO OR THRU SHELTER WALL.
OUTER WALL PENETRATION DETAIL (IF APPLICABLE)
UTILITY TRENCH SECTION (IF APPLICABLE)
SLIP JOINT DETAIL (IF APPLICABLE)
CONDUIT NOTES:
1.VERIFY WIRE AND CONDUIT QUANTITY & SIZES WITH GENERATOR MAKE &
MODEL # PRIOR TO INSTALLATION. VERIFY ELECTRICAL REQUIREMENTS WITH
LOCAL UTILITY PROVIDER.
2.ALL CONDUIT ABOVE GRADE OR IN AREAS OF HIGH TRAFFIC SHALL BE SCH 80
PVC
3.PROVIDE SCH 40 PVC CONDUIT BELOW GRADE EXCEPT AS NOTED BELOW.
4.PROVIDE RGS CONDUIT AND ELBOWS AT STUB UP LOCATIONS (I.E. SERVICE
POLE, BTS EQUIPMENT, ETC.)
5.INSTALL UTILITY PULLBOXES PER NEC.
BACKFILL MATERIAL COMPACTED TO
95% RELATIVE DENSITY PER
STANDARD PROCTOR
COMPACTED SAND TO 95% RELATIVE
DENSITY PER STANDARD PROCTOR
26
"
M
I
N
30
"
M
A
X
1'
-
0
"
1'
-
0
"
1'-6"
8"
UNDISTURBED SOIL
ELECTRICAL CONDUIT(S)
CONDUIT NOTES:
1.VERIFY WIRE AND CONDUIT QUANTITY & SIZES WITH GENERATOR MAKE &
MODEL # PRIOR TO INSTALLATION. VERIFY ELECTRICAL REQUIREMENTS WITH
LOCAL UTILITY PROVIDER.
2.ALL CONDUIT ABOVE GRADE OR IN AREAS OF HIGH TRAFFIC SHALL BE SCH 80
PVC
3.PROVIDE SCH 40 PVC CONDUIT BELOW GRADE EXCEPT AS NOTED BELOW.
4.PROVIDE RGS CONDUIT AND ELBOWS AT STUB UP LOCATIONS (I.E. SERVICE
POLE, BTS EQUIPMENT, ETC.)
5.INSTALL UTILITY PULLBOXES PER NEC.
SECTION A-A
CONTRACTOR SHALL NOT SUBMIT BIDS
OR PERFORM CONSTRUCTION WORK ON
THIS PROJECT WITHOUT ACCESS TO THE
CURRENT COMPLETE SET OF DRAWINGS
LISTED IN THE TITLE-SHEET INDEX.
ELECTRICAL WARNING TAPE
CONTRACTOR TO MATCH EXISTING GRADE CONDITIONS
AFTER TRENCH PLACEMENT AND COMPACTION
(FOR PAVEMENT) CONTRACTOR TO SAW-CUT AND REMOVE
EXISTING PAVEMENT. UPON REPLACEMENT, CONTRACTOR
TO MATCH EXISTING PAVEMENT THICKNESS, PLACEMENT
DETAILS AND DRAINAGE CONDITIONS AFTER TRENCH
PLACEMENT AND COMPACTION
GALVANIZED CHANNEL
WITH PIPE CLAMP PER
MANUFACTURER
CONDUIT
COOPER B-LINE DURA-BLOK
SLEEPER (OR SIMILAR) AT
5'-0" O.C. MAXROOF DECK
ROOF CONDUIT MOUNTING DETAIL (IF APPLICABLE)
3
4
2
3
1
4
2
1
2
3
4
CONDUIT (TYP)
P1119 OR P2558 CLAMP
EXISTING WALL/CEILING
CONDUIT WALL MOUNT DETAIL (IF APPLICABLE)
VERTICAL "UNISTRUT" P1000T.
REQUIRED LENGTH BASED ON
QUANTITY OF CONDUIT TO BE
MOUNTED. INSTALL AT 5'-0" O.C. MAX.
W/ FASTENER AT EACH END.
UNISTRUT WALL ATTACHMENT:
WALL CONSTRUCTION
TYPE FASTENER
HOLLOW 3/8" DIA. TOGGLE BOLT
HOLLOW, AT STUD 3/8" DIA. LAG SCREW
CONCRETE BLOCK
(HOLLOW)
7/16" DIA. HILTI HY-270 WITH SCREEN,
MINIMUM EMBEDMENT 2-1/2"
CONCRETE
(SOLID)
7/16" DIA. HILTI HY-200, MINIMUM
EMBEDMENT 2-1/2"
NOTES:
1. USE GALVANIZED OR STAINLESS STEEL HARDWARE FOR
WALL MOUNT AND CONNECTION OF CHANNELS
2. GC SHALL USE NON-SHRINKING CAULK TO WEATHER SEAL
ALL PENETRATIONS INTO OR THROUGH SHELTER WALL
1
ELECTRICAL
DETAILS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
E-2 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
E-2
Apr 03 2021
K
TA VN NC SS
VV VS VB PT
GT GY GR GL
GROUNDING NOTES:
1.IF MORE THAN 20' FROM EXISTING GROUND RING, INSTALL GROUND ROD (5/8" x 10' SS). ROD SPACING: 8' MAX. TOP OF
ROD AND GROUND WIRE TO BE BELOW FROST LINE.
2.CONTRACTOR SHALL COORDINATE INCOMING SERVICES WITH LOCAL UTILITIES PRIOR TO TRENCHING.
3.ALL CONDUCTORS SHALL BE COPPER, 75 DEGREES C RATED, AND CONDUCTOR INSULATION BE THWN OR THHN.
4.ALL TERMINATION SHALL BE LISTED AND IDENTIFIED FOR USE WITH 75°C RATED CONDUCTORS OPERATING AT 75°C.
5.GROUND FAULT PROTECTION REQUIRED FOR UTILITY RECEPTACLES.
6.GENERATOR NEUTRAL SHALL NOT BE GROUNDED AT THE GENERATOR. REFER TO SINGLE LINE DETAIL, SHEET E-1.
7.EQUIPMENT LOCATED OUTSIDE OR EXPOSED TO MOISTURE SHALL BE NEMA 3R RATED.
8.CONTRACTOR SHALL USE SCHEDULE 80 PVC CONDUIT THROUGH CONCRETE AND ABOVE GROUND, UNLESS
OTHERWISE NOTED.
9.ALL NEWLY INSTALLED EQUIPMENT SHALL BE RATED "AT 10K AIC" MINIMUM. HIGHER RATINGS SHALL BE REQUIRED
WHERE AVAILABLE FAULT CURRENT EXCEEDS THIS VALUE. EXACT FAULT CURRENT AVAILABLE SHALL BE
COORDINATED WITH LOCAL UTILITY BASED ON EXACT CONDITIONS (XFMR SIZE, PERCENT IMPEDANCE, LENGTH OF
CONDUCTORS, ETC).
GROUND ROD DETAILS
CADWELD DETAILS
GROUND ROD NOTES:
1.GROUND RODS MAY BE:
- COPPER CLAD STEEL
- SOLID COPPER
2.GROUND RODS SHALL HAVE A
MAXIMUM SPACING TWICE THE
LENGTH OF ROD
3.SEE RESISTIVITY REPORT FOR
VERIFICATION AS AVAILABLE
4.A LARGER CONDUCTOR SHALL BE
REQUIRED IN AREAS HIGHLY PRONE
TO LIGHTNING AND/OR AREAS WITH
HIGHLY ACIDIC SOIL
5.GROUND RODS INSTALLED WITHIN
CLOSE PROXIMITY TO TOWER OR
WHEN SOIL IS AT OR BELOW 2,000
OHM-CM, SHALL BE GALVANIZED TO
PREVENT GALVANIC CORROSION OF
TOWER, (SEE ANSI/TIA-EIA-222)
6.PROVIDE (1) GROUND LEAD TO EACH
SIDE OF THE GENERATOR
CADWELD
GRADE
#2 AWG BCW
GROUND RING
GROUND ROD
5 8"Ø x 10'-0"
LONG MAX.
CONTRACTOR SHALL NOT SUBMIT BIDS
OR PERFORM CONSTRUCTION WORK ON
THIS PROJECT WITHOUT ACCESS TO THE
CURRENT COMPLETE SET OF DRAWINGS
LISTED IN THE TITLE-SHEET INDEX.
30" OR 6" BELOW FROST
LINE, WHICHEVER IS
DEEPER.
EXISTING EQUIPMENT
SHELTER OR PAD
TRANSFER SWITCH &
CAM-LOCK BOX
PROPOSED GENERATOR
#2 AWG BARE TINNED GROUND WIRE TO
EXISTING EQUIPMENT GROUND RING.
GROUND GENERATOR PER
MANUFACTURER'S RECOMMENDATIONS
EXISTING GROUND WIRE, TYP.
EXISTING BURIED EQUIPMENT
GROUND RING (FIELD LOCATE)
#2 AWG GROUNDED TO
FENCE IF LESS THAN 6FT
ELECTRICAL SYMBOLS LEGEND
EXOTHERMIC WELD TYPE CONNECTION
MECHANICAL TYPE CONNECTION
NEW GROUNDING
EXISTING GROUNDING
TYPICAL GROUNDING DIAGRAM
FENCE GROUNDING:
1.SEE FENCE & GATE DETAILS
SHEET FOR ADDITIONAL
GROUNDING (IF APPLICABLE)
#2 AWG BARE TINNED BOND TO
NEW GROUND ROD (IF NOT
ADJACENT TO COMPOUND OR
EQUIPMENT GROUND RING)
(TYP.OF TWO)
#2 AWG BARE TINNED BOND TO NEW
GROUND ROD (IF NOT ADJACENT TO
COMPOUND OR EQUIPMENT GROUND RING)
ELECTRICAL
DETAILS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
E-3 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
E-3
Apr 03 2021
KOHLER 30KW GENERATOR SPECIFICATIONS
K
NOTE: IT IS RECOMMENDED THAT
BATTERY BE WITHIN LEAK
CONTAINMENT BOX OR TRAY
GENERATOR
SPECIFICATIONS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
E-4.0 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
E-4.0
FOR
INFORMATION
ONLY
Apr 03 2021
KOHLER 30KW GENERATOR SPECIFICATIONS
K
GENERATOR
SPECIFICATIONS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
E-4.1 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
E-4.1
FOR
INFORMATION
ONLY
Apr 03 2021
KOHLER 30KW GENERATOR SPECIFICATIONS
K
GENERATOR
SPECIFICATIONS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
E-4.2 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
E-4.2
FOR
INFORMATION
ONLY
Apr 03 2021
KOHLER ATS SPECIFICATIONS
K
ATS
SPECIFICATIONS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
E-5.0 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
E-5.0
FOR
INFORMATION
ONLY
Apr 03 2021
KOHLER CAM-LOCK BOX SPECIFICATIONS
K
CAM-LOCK BOX
SPECIFICATIONS
PO BOX 2621, BOISE, ID 83701
530.539.4787
CONTACT@GEOSTRUCTURAL.COM
WWW.GEOSTRUCTURAL.COM
0 08/06/20 ISSUED FOR CONSTRUCTION JCM
SHEET TITLE:
SHEET NUMBER:
E-5.1 (K)
REV DATE DESCRIPTION INT
REVISIONS
SITE INFORMATION:
413 SOUTHPORT LANE
PORT TOWNSEND, WA 98368
GENERATOR INSTALLATION
PROJECT
ANDERSON LAKE
10092414
CHECKED BY:GGD
THE INFORMATION CONTAINED IN THIS SET OF
DOCUMENTS IS PROPRIETARY BY NATURE. ANY
USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO THE CLIENT NAMES IS STRICTLY
PROHIBITED.
at t &
GENERAL DYNAMICS
Information Technology
JURISDICTION USE:
E-5.1
FOR
INFORMATION
ONLY
Apr 03 2021