Loading...
HomeMy WebLinkAboutBLD2021-00280 - 10 COMMUNICATIONGeoStructural ▪ P.O. Box 2621, Boise, ID 83701 ▪ Office: (530) 539-4787 Page 1 Professional Engineers | Tower Technicians | Climbers | sUAS Mapping 10092414 - Gen Post Install Letter_R0 210909 Generator -Post Install Review Letter Site Name::Anderson Lake Site Number:10092414 Project: Generator Upgrade Prepared For:AT&T Structure Description:Concrete Slab & Anchorage Diesel Backup Generator Site Location:413 Southport Lane Port Townsend,Washington 98368 Jefferson County 48.02417°,-122.82295° Review Result:Adequate per Plan Revision 0 September 9, 2021 Date Signed: 9/9/2021 Received by DCD 09/09/2021 AT&T | 10092414 | Anderson Lake - Post Install Review Letter Page 2 GeoStructural, LLC | PO Box 2621 | Boise, ID 83701 | p:530.539.4787 1.0 Introduction A review of the provided generator upgrade project documentation has been performed on AT&T’s recently installed backup diesel generator located at the 10092414 communications site in Jefferson County, Washington. The purpose of the review is to provide an engineering opinion on the installation of the generator support concrete slab and generator anchorage, and to investigate compliance with the approved Construction Drawings. 2.0 Building Code and Installation Criteria The approved Construction Drawings have appropriately utilized the following design criteria based on the site’s location: IBC 2018 – International Building Code. ASCE 7-16 – Minimum Design Loads and Associated Criteria for Buildings and Other Structures. ANSI/TIA-222-H – Structural Standard for Antenna Supporting Structures and Antennas. AISC – Steel Construction Manual. ACI 318 – Building Code Requirements for Structural Concrete. The following documents were provided: Construction Drawings – Generator Upgrade Project GeoStructural LLC, Rev-0, 08/06/20. Construction Photos – Before Concrete Placement Site Photos – After Concrete Placement and Generator Anchorage According to the approved Construction Drawings, AT&T’s proposed backup diesel standby generator project at the above site consists of the following: Installation of a new 4’-0” x 10’-0” x 0’-8” thick reinforced concrete pad. o Preparation of subgrade/base as specified in Construction Drawings (e.g. undisturbed natural subgrade or compacted granular fill material). o #5 horizontal reinforcing bars at a spacing of 12” o.c. each way. o Concrete “block-out” for supply conduit stub-up as per manufacturer. Installation of, at a minimum, four (4) Hilti Kwik Bolt TZ SS expansion anchors from generator diesel fuel tank frame to concrete. o 5/8” Ø w/ 60 ft-lb installation torque. Received by DCD 09/09/2021 AT&T | 10092414 | Anderson Lake - Post Install Review Letter Page 3 GeoStructural, LLC | PO Box 2621 | Boise, ID 83701 | p:530.539.4787 3.0 Conclusion Based upon review of the provided documents, it appears the installation of the outdoor generator with belly-mounted diesel fuel tank, generator reinforced concrete pad and post-installed anchorage is in general conformance with the approved Construction Drawings. All data required to complete our post installation review has been furnished by our client. GeoStructural has not conducted a site visit or independent study to verify existing conditions and the results of this letter are based solely on the information provided. This review only encompasses the outdoor generator and the apparent installation of its anchorage and supporting concrete slab. The anchor bolt installation torque, concrete mixture/strength, pad structural capacity, soil bearing capacity and subgrade preparation methods, electrical and grounding system design/installation, etc. are beyond the scope of this review. If any of the existing or proposed conditions reported in this review are not properly represented, please contact our office immediately to request an amended report. Prepared by:Reviewed and Approved by: Jesse Drennen, PE, MLE Don George, PE, SE, MLSE 208.761.7986 208.602.6569 jesse.drennen@geostructural.com don.george@geostructural.com Received by DCD 09/09/2021 AT&T | 10092414 | Anderson Lake - Post Install Review Letter Page 4 GeoStructural, LLC | PO Box 2621 | Boise, ID 83701 | p:530.539.4787 Received by DCD 09/09/2021 AT&T | 10092414 | Anderson Lake - Post Install Review Letter Page 5 GeoStructural, LLC | PO Box 2621 | Boise, ID 83701 | p:530.539.4787 Received by DCD 09/09/2021