HomeMy WebLinkAboutBLD2022-00002-03- Energy WorksheetSimple Heating System Size: Washington State
Project Information Contact Information
Heating System Type:
To see detailed instructions for each section, place your cursor on the word "Instructions".
Design Temperature
Instructions Design Temperature Difference (∆T)45
∆T = Indoor (70 degrees) - Outdoor Design Temp
Area of Building
Conditioned Floor Area
Instructions Conditioned Floor Area (sq ft)1,536
Average Ceiling Height Conditioned Volume
Instructions Average Ceiling Height (ft)9.0 13,824
Glazing and Doors U-Factor X Area = UA
Instructions 0.30 343 102.90
Skylights U-Factor X Area = UA
Instructions 0.50 0 ---
Insulation
Attic U-Factor X Area = UA
Instructions 0.026 1,536 39.94
Single Rafter or Joist Vaulted Ceilings U-Factor X Area UA
Instructions 0.027 0 ________
Above Grade Walls (see Figure 1)U-Factor X Area UA
Instructions 0.056 1,215 68.04
Floors U-Factor X Area UA
Instructions 0.025 1,536 38.40
Below Grade Walls (see Figure 1)U-Factor X Area UA
Instructions ---0 ---
Slab Below Grade (see Figure 1)F-Factor X Length UA
Instructions ---0 ________
Slab on Grade (see Figure 1)F-Factor X Length UA
Instructions ---0 ________
Location of Ducts
Instructions Duct Leakage Coefficient
1.00
Sum of UA 249.28
Envelope Heat Load 11,217 Btu / Hour
Sum of UA X ∆T
Air Leakage Heat Load 6,718 Btu / Hour
Volume X 0.6 X ∆T X .018
Building Design Heat Load 17,936 Btu / Hour
Air Leakage + Envelope Heat Loss
Building and Duct Heat Load 17,936 Btu / Hour
Ducts in unconditioned space: Sum of Building Heat Loss X 1.10
Ducts in conditioned space: Sum of Building Heat Loss X 1
Maximum Heat Equipment Output 22,420 Btu / Hour
Building and Duct Heat Loss X 1.40 for Forced Air Furnace
Building and Duct Heat Loss X 1.25 for Heat Pump
This heating system sizing calculator is based on the Prescriptive Requirements of the 2012 Washington State Energy Code (WSEC) and ACCA
Manuals J and S. This calculator will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine cooling
loads.
The glazing (window) and door portion of this calculator assumes the installed glazing and door products have an area weighted average U-factor of
0.30. The incorporated insulation requirements are the minimum prescriptive amounts specified by the 2012 WSEC.
Please fill out all of the green drop-downs and boxes that are applicable to your project. As you make selections in the drop-downs for each section,
some values will be calculated for you. If you do not see the selection you need in the drop-down options, please call the WSU Energy Extension
Program at (360) 956-2042 for assistance.
Lot 105 - Rose 2 Car Left
281 Puget Loop Road
Port Ludlow Associates LLC
Cliff Obrien
360-437-8242
Above Grade
Below Grade
Figure 1.
All Other Systems Heat Pump
(07/01/13)
RECEIVED BY DCD 12/29/21
RECEIVED BY DCD 12/29/21
RECEIVED BY DCD 12/29/21
RECEIVED BY DCD 12/29/21
RECEIVED BY DCD 12/29/21
RECEIVED BY DCD 12/29/21
RECEIVED BY DCD 12/29/21
RECEIVED BY DCD 12/29/21
RECEIVED BY DCD 12/29/21