HomeMy WebLinkAboutBLD2022-00221_03Simple Heating System Size: Washington State
Project Information Contact Information
Heating System Type:
To see detailed instructions for each section, place your cursor on the word "Instructions"
Design Temperature
Instructions Design Temperature Difference (∆T)45
∆T = Indoor (70 degrees) - Outdoor Design Temp
Area of Building
Conditioned Floor Area
Instructions Conditioned Floor Area (sq ft)818
Average Ceiling Height Conditioned Volume
Instructions Average Ceiling Height (ft)8.0 6,544
Glazing and Doors U-Factor X Area = UA
Instructions 0.300 180 53.91
Skylights U-Factor X Area = UA
Instructions 0.50 ---
Insulation
Attic U-Factor X Area = UA
Instructions 0.026 818 21.27
Single Rafter or Joist Vaulted Ceilings U-Factor X Area UA
Instructions ---0 ________
Above Grade Walls (see Figure 1)U-Factor X Area UA
Instructions 0.056 929 52.02
Floors U-Factor X Area UA
Instructions 0.029 818 23.72
Below Grade Walls (see Figure 1)U-Factor X Area UA
Instructions 0.028 0 ________
Slab Below Grade (see Figure 1)F-Factor X Length UA
Instructions 0.303 0 ---
Slab on Grade (see Figure 1)F-Factor X Length UA
Instructions ---0 ________
Location of Ducts
Instructions Duct Leakage Coefficient
1.00
Sum of UA 150.92
Envelope Heat Load 6,792 Btu / Hour
Sum of UA x ∆T
Air Leakage Heat Load 3,180 Btu / Hour
Volume x 0.6 x ∆T x 0.018
Building Design Heat Load 9,972 Btu / Hour
Air leakage + envelope heat loss
Building and Duct Heat Load 9,972 Btu / Hour
Ducts in unconditioned space: sum of building heat loss x 1.10
Ducts in conditioned space: sum of building heat loss x 1
Maximum Heat Equipment Output 12,465 Btu / Hour
Building and duct heat loss x 1.40 for forced air furnace
Building and duct heat loss x 1.25 for heat pump
This heating system sizing calculator is based on the Prescriptive Requirements of the 2018 Washington State Energy Code (WSEC) and ACCA
Manuals J and S. This tool will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine cooling loads.
Please complete the green drop-downs and boxes that are applicable to your project. As you make selections in the drop-downs for each section, some
values will be calculated for you. If you do not see the selection you need in the drop-down options, please contact the WSU Energy Program at
energycode@energy.wsu.edu or (360) 956-2042 for assistance.
Kasperzak Addition
266 Moondance Lane
Port Ludlow, WA 98365
Dean Burgess, AIA
dburgess@proofarch.com
(406) 570-3235
Above Grade
Below Grade
Figure 1.
All Other Systems Heat Pump
(07/01/13)
RECEIVED BY DCD 4/28/2022
RECEIVED BY DCD 4/26/2022
RECEIVED BY DCD 4/26/2022
RECEIVED BY DCD 4/26/2022