HomeMy WebLinkAboutBLD2020-00225-07- BUILDING PLANS- FINAL APPROVEDReceived 04/22/2022 This plan has significant deficiencies and omissions. Approval of these plans shall not be presumed to be approval
of the deficiencies and/or components not in compliance with the International Residential Code, as adopted by
Jefferson County. Approval of these plans is conditioned that the project is subject to field corrections as identified
and as required by the Jefferson County Building Inspectors. Construction is at the risk of the applicant, and the
applicant shall make any required or identified corrections in order for the project to be in compliance with the
adopted building codes.
If this condition is not accepted by the applicant, the "Approved Plans" shall be considered VOID, and the building
permit suspended until a full set of corrected plans is prepared by a licensed architect or other state registered
design professional, and fully reviewed by the Jefferson County Department of Community Development.
This space is NOT approved
to be "unheated." See Notes
on Plan Sheets. This space
shall be included within the
conditioned area, and be
bound by wall, floor and ceiling
assemblies that satisfy the
Energy envelope requirements
of the WSEC.
If an alternative is desired,
then the applicant shall
obtain the services of a
registered architect or other
competent design
professional to prepare
plans that can satisfy all
minimum building,
plumbing, mechanical and
energy code requirements.
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
WSEC R402.1. If the building's Energy
envelope is not extended to, and complete to,
the exterior walls, it is provisionally
acceptable to use this wall between heated
and unheated, provided it is framed with 2x6
studs and plates, and provided with full R-21
insulation, air-sealing, and fully
weatherstripped exterior door assemblies.
Otherwise the entire area is considered
indirectly heated space and shall fully satisfy
all thermal energy envelope requirements of
the WSEC.
If these conditions are not acceptable to the
applicant, approval of the plans will be
withdrawn, and the applicant shall hire a
licensed architect or other design
professional to prepare plans.
This wall line is NOT
approved to be the thermal
envelope between heated
and unconditioned space
R-21
(unless thermal envelope is
fully complete to all exterior
walls, floors and roofs.)
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
See insulation notes at Floor
above. From this wall line, and
continuing across the entire
floor area below the dwelling
area, shall be minimum R-38
floor insulation in accordance
with WSEC requirements.
R-21
This plan has significant deficiencies and omissions. Approval of these plans shall not be presumed to be approval
of the deficiencies and/or components not in compliance with the International Residential Code, as adopted by
Jefferson County. Approval of these plans is conditioned that the project is subject to field corrections as identified
and as required by the Jefferson County Building Inspectors. Construction is at the risk of the applicant, and the
applicant shall make any required or identified corrections in order for the project to be in compliance with the
adopted building codes.
If this condition is not accepted by the applicant, the "Approved Plans" shall be considered VOID, and the building
permit suspended until a full set of corrected plans is prepared by a licensed architect or other state registered
design professional, and fully reviewed by the Jefferson County Department of Community Development.
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
The AWC assembly may be used as a recognized fire-resistive
assembly. The details of the assembly must be strictly followed;
such documentation shall be available on-site at the time of
inspection(s). If there is no documentation available on-site, then
the assembly shall include minimum fasteners satisfying IRC
Section R702.3.5.1, spaced no more than 6-inches on center as
required by IRC Sections R302.6, R702.3.5 and Table R702.3.5.
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
This plan has significant deficiencies and omissions. Approval of these plans shall not be presumed to be approval
of the deficiencies and/or components not in compliance with the International Residential Code, as adopted by
Jefferson County. Approval of these plans is conditioned that the project is subject to field corrections as identified
and as required by the Jefferson County Building Inspectors. Construction is at the risk of the applicant, and the
applicant shall make any required or identified corrections in order for the project to be in compliance with the
adopted building codes.
If this condition is not accepted by the applicant, the "Approved Plans" shall be considered VOID, and the building
permit suspended until a full set of corrected plans is prepared by a licensed architect or other state registered
design professional, and fully reviewed by the Jefferson County Department of Community Development.
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
This plan has significant deficiencies and omissions. Approval of these plans shall not be presumed to be approval
of the deficiencies and/or components not in compliance with the International Residential Code, as adopted by
Jefferson County. Approval of these plans is conditioned that the project is subject to field corrections as identified
and as required by the Jefferson County Building Inspectors. Construction is at the risk of the applicant, and the
applicant shall make any required or identified corrections in order for the project to be in compliance with the
adopted building codes.
If this condition is not accepted by the applicant, the "Approved Plans" shall be considered VOID, and the building
permit suspended until a full set of corrected plans is prepared by a licensed architect or other state registered
design professional, and fully reviewed by the Jefferson County Department of Community Development.
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
R-21 By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
"Interior" Doors are suitable only within the
dwelling area, within walls that do not form
part of the separation between heated and
unheated areas. Any door assemblies within
walls between heated and unheated areas
shall be fully weatherstripped, insulated,
exterior door assemblies satisfying the
requirements of the WSEC.
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
This building plan is reviewed as a single-family
residential building, to be in compliance with the
International Residential Code as adopted by
the State of Washington and Jefferson County.
Any use of the building for anything other than a
single-family residence with an attached garage
will be a violation of adopted building and zoning
codes, and will be a cause for a Code
Enforcement action against the owner.
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
This plan has significant deficiencies and omissions. Approval of these plans shall not be presumed to be approval
of the deficiencies and/or components not in compliance with the International Residential Code, as adopted by
Jefferson County. Approval of these plans is conditioned that the project is subject to field corrections as identified
and as required by the Jefferson County Building Inspectors. Construction is at the risk of the applicant, and the
applicant shall make any required or identified corrections in order for the project to be in compliance with the
adopted building codes.
If this condition is not accepted by the applicant, the "Approved Plans" shall be considered VOID, and the building
permit suspended until a full set of corrected plans is prepared by a licensed architect or other state registered
design professional, and fully reviewed by the Jefferson County Department of Community Development.
R-38
R-38
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
This plan has significant deficiencies and omissions. Approval of these plans shall not be presumed to be approval
of the deficiencies and/or components not in compliance with the International Residential Code, as adopted by
Jefferson County. Approval of these plans is conditioned that the project is subject to field corrections as identified
and as required by the Jefferson County Building Inspectors. Construction is at the risk of the applicant, and the
applicant shall make any required or identified corrections in order for the project to be in compliance with the
adopted building codes.
If this condition is not accepted by the applicant, the "Approved Plans" shall be considered VOID, and the building
permit suspended until a full set of corrected plans is prepared by a licensed architect or other state registered
design professional, and fully reviewed by the Jefferson County Department of Community Development.
This 1-hour fire-resistive assembly is
acceptable provided all of the
components fully match and satisfy
the requirements of the AWC
assembly WIJ 1.1.
Otherwise, in accordance with IRC
Table 702.3.5, fasteners spacing
shall not exceed 6" o.c. on all
members throughout.
2x6 wood stud wall required for interior walls that
separate heated/conditioned space from un-
conditioned space, with minimum R-21 insulation.
(Unless the exterior walls, roof and floor fully satisfy all
WSEC requirements as a complete thermal envelope.)
Closed-Cell spray foam is
required for this un-vented
assembly. No substitutions
will be allowed.
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
Received 04/22/2022
By Michael J. Barth, M.C.P. at 7:20 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:24 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
By Michael J. Barth, M.C.P. at 7:21 pm, Jul 05, 2022
CodePros, LLC, Western Washington, Custom Project Checklist
Custom Project Checklist
Permit Number: BLD20-00225, 552 McMinn Rd.
2015 International Residential Code, WAC 51-51
2015 International Mechanical Code, WAC 51-52
2015 International Fuel Gas Code, WAC 51-52
2015 Uniform Plumbing Code, WAC 51-56
2015 Washington State Energy Code (WSEC), WAC 51-11R
The numbered items on the following pages are common items associated with the
above referenced codes as adopted and amended by the State of Washington.
This checklist is intended to provide basic, helpful information only, to assist in
understanding code requirements, and shall not be construed as an all-inclusive list
of code requirements.
IBC 105.4 / IRC R105.4 Validity of permit.
The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of this code or of any other ordinance of the jurisdiction.
Permits presuming to give authority to violate or cancel the provisions of this code or other
ordinances of the jurisdiction shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the building official from requiring the correction of
errors in the construction documents and other data. The building official is also authorized to
prevent occupancy or use of a structure where in violation of this code or of any other ordinances
of this jurisdiction.
IBC 105.5 / IRC R105.5 Expiration.
Every permit issued shall become invalid unless the work on the site authorized by such permit is
commenced within 180 days after its issuance, or if the work authorized on the site by such permit
is suspended or abandoned for a period of 180 days after the time the work is commenced. The
building official is authorized to grant, in writing, one or more extensions of time, for periods not
more than 180 days each. The extension shall be requested in writing and justifiable cause
demonstrated.
Minimum Required Inspections for Your Project Include:
Setbacks/Footings
Foundation Wall
Underground Plumbing
Water & Sewer Service
Ext. Sheathing/Shear
Rough Mechanical
Rough Plumbing
Framing
Insulation
Drywall
Final Mechanical
Final Plumbing
Final Building
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
2
FLOOR PLAN
1. CONSTRUCTION DOCUMENTS: IRC Section
R105.3(4) & R106.1.1. Construction documents
shall be drawn upon suitable material, or provided
on electronic media and shall be of sufficient clarity
to indicate the location, nature and extent of work
proposed, and show in detail that it will conform to
the provisions of the adopted code and all relevant
laws, ordinances, rules and regulations. All braced
wall lines, (or engineered shear walls) shall be
clearly identified on the construction documents as
well as all bracing methods, location, length and
type of braced wall panels, foundation
requirements and similar structural details.
Construction plans shall also clearly show each
room and its intended use.
2. EGRESS WINDOWS: IRC Section R310.1.
Basements, habitable attics, and every sleeping
room shall have at least one operable emergency
escape and rescue opening. Windows shall have a
minimum net clear openable area of 5.7 square
feet, or, may be a minimum of 5.0 square feet if
within 44 inches of exterior grade. The minimum
net clear openable height dimension shall be 24".
The minimum net clear openable width dimension
shall be 20". The window shall have a finished sill
height not more than 44" above the floor.
Emergency escape and rescue openings shall be
operational from the inside of the room without the
use of keys, tools, or special knowledge.
Additional provisions may apply. See IRC R310 for
additional information.
3. SMOKE ALARMS: IRC Section R314.1 A smoke
alarm listed in accordance with UL217 shall be
installed in each sleeping room, which includes
each bedroom, bonus room, and other habitable
room that could potentially be utilized as a sleeping
room that contain an intervening door that can be
closed to separate the room from areas otherwise
provided with smoke alarms. In addition, a smoke
alarm shall be installed outside each separate
sleeping area in the immediate vicinity of the
bedrooms as well as at least one on each
additional story of the dwelling including basements
and habitable attics (but excluding crawl spaces
and uninhabitable attics). All smoke alarms within
an individual dwelling unit shall be hardwired from
the building wiring, have a battery back-up, and be
interconnected in such a manner that the actuation
of one alarm will activate all of the alarms in the
individual unit. When alterations or repairs are
made that require a permit, (other than plumbing
and mechanical system alterations or repairs)
smoke alarms must be installed in accordance with
IRC R314.3.1 Note: Habitable rooms such as
dens, libraries and offices that are provided with
built in features that establish the specific use of
the room as something other than for sleeping, and
do not contain clothes closets, typically would not
be considered a sleeping room. Some additional
provisions may apply, see IRC R314.
3. CARBON MONOXIDE ALARMS: IRC R315. An
approved carbon monoxide alarm, compliant with
UL 2034, shall be installed in accordance with the
manufacturer’s recommendations, outside each
separate sleeping area in the immediate vicinity of
the bedrooms in dwelling units, and on each floor
level. See WA-IRC R315 for additional information.
4. SAFETY GLAZING: IRC Section R308.4. All
glass located in an area considered “hazardous”
must be safety glazed. These include:
1. Glazing within fixed, sliding, bi-fold, and
swinging door assemblies, including
storm doors (except glazing less than 3
inches and decorative glass).
2. Glazing in any opening adjacent to a
door within 24" where the bottom is less
than 60" above the walking surface.
3. Glazing that meet all of the following
conditions:
A. Exposed area of an individual pane
is greater than 9 square feet. and
B. The bottom edge of the glazing is
less than 18" above the floor. and
C. The top edge of the glazing is
greater than 36" above the floor.
and
D. One or more walking surfaces is
within 36" horizontally of the plane
of the glazing.
4. Glazing in railing systems and guards.
5. Glazing in walls, enclosures or fences
containing or facing tubs, showers, hot
tubs, spas, whirlpools, saunas, steam
rooms and indoor or outdoor swimming
pools where the bottom of the glazing is
less than 60" above a walking surface
and within 60 inches horizontally from
the edge of a tub, shower, pool, etc.
6. Glazing adjacent to stairways, mid-flight
landings and ramps within 36 inches
horizontally of a walking surface when
the bottom of the glazing is less than 36
inches above the floor or walking
surface.
7. Glazing adjacent to the bottom landing
of stairways within 60 inches
horizontally of the bottom tread in any
direction, when the bottom of the glazing
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
3
is less than 36 inches above the
landing.
Some exceptions may apply, See IRC R308.4
for additional details.
5. NATURAL LIGHT. IRC Section R303.1. All
habitable rooms shall be provided with (aggregate)
glazing areas of not less than eight percent (8%) of
the floor area of such rooms. An exception
provides that the glazed area need not be provided
in habitable rooms that are provided with artificial
light capable of producing an average illumination
of 6 footcandles over the area of the room at a
height 30” above the floor.
6. EXHAUST FANS: IRC Sections R303.4, M1501,
M1507.1, IMC 501.2, 501.2.1 Dwelling units shall be
equipped with local exhaust and whole house
ventilation systems as specified in Section M1507.
Local exhaust fans are required in each kitchen,
bathroom, water closet room, laundry facility, indoor
swimming pool, spa and other rooms where water
vapor or cooking odor is produced. The air removed
by every mechanical exhaust system shall be
discharged outdoors at a point where it will not cause
a nuisance and from which it cannot again be readily
drawn in by a ventilating system. Typically a
minimum of 3 feet of separation is required from
exhaust terminations and operable windows and
property lines; a minimum of 10 feet is required to any
mechanical air intake. Air shall not be exhausted into
an attic or crawl space or any other area inside the
building. See the energy code section of this checklist
for additional requirements.
7. CLOTHES DRYERS: IRC Sections M1502, G2439.3
& G2439.5. Clothes dryer exhaust ducts shall
terminate outside the building at lease three feet
away from any openings, and shall be equipped with
a backdraft damper. Screens shall not be installed at
the duct termination. Nominal 4-inch diameter
exhaust ducts shall be constructed of minimum
0.0157-inch-thick (28 gage) rigid metal ducts, having
smooth interior surfaces with joints running in the
direction of air flow. Duct joints shall be mechanically
fastened with fasteners that do not protrude into the
inside of the duct more than 1/8 of an inch and shall
be sealed in accordance with IRC Section M1601.4.1
with mastic. Duct length shall not exceed a length
approved by the dryer manufacturer’s listing or a total
combined vertical and horizontal length of 35’, with
the maximum length of the duct being reduced 2.5
feet for each 45 degree bend and 5 feet for each 90
degree bend. Other fitting reduction factors may be
obtained from IRC Table M1502.4.4.1. Approved
flexible duct connectors of not more than 8’ in length
may only be used within the dwelling to connect the
dryer to the exhaust duct, and shall not be concealed
within construction.
Length Identification: Where the dryer exhaust duct
is concealed, the equivalent length of the duct shall
be identified on a permanent label or tag within 6 feet
of the dryer connection.
Nail Plates Required: Minimum 0.062-inch thick
protective shield plates, extending 2 inches above
sole plates, and 2 inches below top plates, shall be
placed on the finished face of framing members
where there is less than 1¼ inches from the duct to
the face of the framing.
8. RANGE HOOD: IRC Sections M1503 and M1901,
IMC 505. The vertical distance between the cooking
surface of a domestic range and unprotected
combustible material above shall not be less than 30”.
Reduced clearances may be permitted in accordance
with the listing and labeling of the range hoods or
appliances. Commercial cooking equipment shall not
be installed within a dwelling unit; cooking appliances
shall be listed and labeled as household-type
appliances for domestic use. Range hoods capable
of exhausting in excess of 400 cfm shall be provided
with an interlocked makeup air system. See the
energy code section of this checklist for additional
requirements.
9. WATER CLOSET CLEARANCES: IRC Figure 307.1.
Water closets shall be located in a clear space not
less than 30” in width, and not closer than 15” from
the center of the fixture to a wall or other side barrier
such as a tub or shower. The clear space in front of
the water closet shall be at least 21”.
10. SHOWER AREAS: IRC Figure 307.1, R305.
Showers shall be minimum 30”x 30” and have a
minimum 24” clearance in front of the opening, and at
least 6’ 8” clearance above the shower floor. A non-
absorbent wall finish shall be provided to a height of
not less than 6 feet above the shower floor. (Also
note #4 above, Safety Glazing.)
16. APPLIANCE LOCATIONS: IRC Section G2406.2.
Fuel burning appliances shall not be installed in a
sleeping room, bathroom, toilet room, or closets, nor
in any area that opens only into such rooms or
spaces. Exception: direct vent appliances (see IRC
Section G2406.2 for additional exceptions).
17. APPLIANCES LOCATED IN GARAGE: IRC Section
M1307.3, UPC 507.13. Appliances shall not be
located where subject to potential vehicle damage
unless protected by approved barriers. Within
garages or spaces that directly communicate with a
garage, appliances having a potential ignition source
(pilot light, flame, electric switching device or relay,
etc.) shall be elevated such that the source of ignition
is not less than 18 inches above the floor. (It should
be noted that this includes both gas and electric water
heaters, furnaces, pumps, etc.)
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
4
18. WATER HEATER: IRC Section M1307.2 & UPC
504.6, 505.2, 507, 608.3, 608.4, and 608.5. Water
heaters shall be anchored or strapped to resist
horizontal displacement due to earthquake motion.
Strapping shall be at points within the upper one-third
and lower one-third of the appliance and shall be at
least 4” away from the controls. Water heaters
installed in locations where leakage of the tank or
connections can cause damage, a watertight pan of
corrosion-resistant materials shall be installed
beneath the water heater with a minimum three-
quarter (3/4) inch diameter drain to an approved
location. Temperature and pressure relief valves shall
be drained to outside. Drain may not be trapped and
must terminate pointed downward, and be no more
than 2’ nor less than 6” from the ground and shall not
be threaded. IRC M1307.3, water heaters located in
a garage shall have any sources of ignition
(switches/relays, pilots, etc.) elevated at least 18
inches above the garage floor. A water system with a
check valve, backflow preventor, or any other device
which prevents building pressure back into the water
main shall be equipped with an approved, listed,
adequately sized expansion tank. WSEC Section
R403.4.3. All electric hot water heaters shall be
placed on an incompressible, R-10 pad when located
in an unheated space or on a concrete floor.
20. MANUFACTURER’S SPECS: IRC M1307.1.
Installation of appliances shall conform to the
conditions of their listing and label and the
manufacturer’s installation instructions. The
manufacturer’s operating and installation instructions
shall remain attached to the appliance until the final
inspection is approved.
21. BACKFLOW PREVENTORS: UPC Section 603,,
603.5.7. Potable water outlets with hose attachments
other than water heater drains and clothes washer
connections shall be protected by a listed non-
removable hose bibb type backflow preventor, or
atmospheric vacuum breaker. If exterior, they shall
be listed, self-draining frost-proof hose bibs with
integral backflow preventer or vacuum breakers. All
cross connections between potable water sources
and other systems, such as landscape irrigation
systems, hydronic-radiant heating systems, swimming
pools, etc. shall be equipped with backflow preventors
in accordance with UPC Section 603.
22. TRAP PRIMERS: UPC Section 1007. Floor drains
or similar traps connected to the drainage system and
subject to infrequent use shall be provided with an
approved automatic means of maintaining their water
seals.
23. GARAGE/DWELLING DOOR: IRC Section R302.5.
Openings from a private garage directly into a room
used for sleeping purposes shall not be permitted.
Other openings between the garage and residence
shall be equipped with solid wood doors not less that
1-3/8 inches in thickness, solid or honeycomb core
steel doors not less than 1-3/8 inches thick, or 20-
minute fire-rated doors, and shall be equipped with a
self-closing device.
24. GARAGE/DWELLING SEPARATION: IRC Section
R302.6 The garage shall be separated from the
residence and its attic area by not less than ½”
gypsum board applied to the garage side. Garages
beneath habitable rooms shall be separated from all
habitable rooms above by not less than 5/8” Type X
gypsum board. Structural members supporting the
horizontal separation shall be protected by minimum
½” gypsum (this includes all bearing walls, posts,
columns, etc.). Any duct penetrations shall be of
ducts a minimum of 26 gage sheet steel and shall not
have any openings into the garage,
25. GARAGE FLOOR SURFACE: IRC Section R309.1
The garage floor surface shall be of approved
noncombustible material, typically concrete. The area
of floor used for parking of automobiles or other
vehicles shall be sloped to facilitate the movement of
liquids to a drain or toward the main vehicle entry
doorway.
27. FLOOR AREA: IRC Section R304.1 & R304.2.
Dwelling units shall have at least one room with not
less than 120 square feet of floor area. Other
habitable rooms, except kitchens shall have an area
of not less than 70 square feet and shall not be less
than 7’ in any dimension.
28. MINIMUM CEILING HEIGHTS: IRC Section R305.1
Habitable spaces, hallways, bathrooms, toilet rooms,
laundry rooms, and portions of basements containing
these spaces shall have a ceiling height of not less
than 7 feet. For rooms with sloped ceilings, at least
50% of the required floor area of the room shall have
a minimum ceiling height of 7 feet, and no portion of
the required floor area may have a ceiling height of
less than 5 feet. Ceilings in basements without
habitable spaces may have a ceiling height of 6’-8”
with beams projecting to within 6’-4” of the finished
floor. Bathrooms shall have minimum ceiling height
of 6’-8” over the fixture and at the front clearance
areas of fixtures.
29. ATTIC ACCESS: IRC Section R807.1. Attics which
exceed 30 square feet and have a minimum vertical
height of 30” must be provided with an access
opening of not less than 22” wide x 30” high (or
positioned horizontally) and located in a hallway, or
other readily accessible location. Note: The attic
access shall not penetrate the garage/dwelling
fire resistive barrier unless it is a protected
assembly. Attics with mechanical equipment shall
have access openings large enough for removal of
the largest appliance within 20 feet of the equipment,
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
5
and shall have a passageway with solid flooring not
less than 24 inches wide between the access and the
equipment, as well as a level service space at least
30 inches wide along the extent of the equipment.
Additional provisions and exceptions may apply. See
IRC R807 and IRC M1305.1.3 for additional
information.
30. DOORS & EXITS: IRC Section R311.2. In every
dwelling (and accessory building) at least 1 doorway
shall be of a size as to permit the installation of a door
with a minimum clear width of at least 32” (typically a
3’ wide door) and not less than 6’-8” in height, that
can be opened from the inside without the use of a
key, tool or special knowledge or effort.
31. LANDINGS: IRC Section R311.3. There shall be a
floor or landing on each side of exterior doors with
dimensions of at least 36 inches measured in the
direction of travel, and at least the width of the door
served. The floor or landing shall be not more than
1.5” lower than the top of the threshold of the
doorway, except that landings for other than the main
egress door, may be up to 7¾” below the level of the
threshold provided the door does not swing over the
landing (except that screen and storm doors may).
An interior door may open at the top of a flight of
stairs provided the door does not swing over the top
step. In addition, for doors other than the main
egress door, that have two or fewer risers, a landing
is not required at the door. However, please note that
landings are required at the bottom of the two riser
stairway. Exterior landings may have a slope not to
exceed 2% (1” in 48”).
32. GUARDS: IRC Section R312. Porches, balconies or
raised floor surfaces located more than 30” above the
floor or grade below (within 36” horizontally) shall
have guards not less than 36” in height, including
areas enclosed with insect screening. Where guards
are required at the open side of stairs, the height may
be reduced to 34” above the stair nosings. Guardrails
shall be designed such that a sphere 4” in diameter
cannot pass through, except the triangular opening
between a riser, tread and the bottom rail of the guard
may be of such size that a sphere 6” cannot pass
through.
***Window Fall Protection: Operable windows
located more than 72 inches above the exterior grade
below, where the bottom of the window is less than
24 inches above the inside floor, shall have protective
devices or maximum opening dimensions that will
reject the passage of a 4 inch sphere.
Additional provisions or exceptions may apply; see
IRC R312 for additional information.
33. HANDRAILS: IRC Section R311.7.8. All stairways
with 4 or more risers shall have at least one handrail.
Such handrails shall be placed not less than 34” nor
more than 38” above the nosing of the treads. The
handgrip portion of the handrail shall not be less than
1-1/4” or more than 2-1/4” (maximum 2” if circular) in
cross-sectional dimension, and shall provide
“graspability” in accordance with IRC R311.7.8.3.
(see separate handrails handout) There shall be a
space of not less than 1-1/2” between a wall and a
handrail, however, the handrail shall not project more
than 4-1/2” into the required stair width.
34. STAIRWAYS: IRC Section R311.7. Private dwelling
stairways shall not be less than 36” in width and shall
have a headroom clearance of not less than 6 feet 8
inches measured vertically from the sloped plane
adjoining the tread nosings, or landing surfaces.
Additional exceptions for projections and for spiral
stairways may apply; see IRC R311.7 for additional
information.
35. STAIR RISE & RUN: IRC Section R311.7.5.
Maximum riser height shall be 7-¾ inches and the
minimum tread depth shall be 10 inches. The
greatest riser height may not exceed the smallest by
more than 3/8 inch. The radius curvature at the
leading edge of the tread shall be no greater than
9/16 inch. A nosing not less than ¾ inch but not more
than 1-¼ inches shall be provided on stairways with
solid risers. The greatest nosing projection shall not
exceed the smallest nosing projection by more than
3/8 inch between two stories, including the nosing at
the level of floors and landings. Exception: A nosing is
not required where the tread depth is a minimum of
11 inches. Open risers are permitted, provided that
the opening between treads does not permit the
passage of a 4-inch diameter sphere.
36. STAIRWAY ILLUMINATION R303.7 All interior and
exterior stairways shall be provided with a means to
illuminate the stairs, including the landings and
treads. Interior stairways shall be provided with a light
located in the immediate vicinity of each landing of
the stairway that provides at least 1 foot candle of
illumination measured at the center of treads and
landings. A wall switch shall be provided at each floor
level where the stairway has six or more risers.
Exterior stairways shall be provided with an artificial
light source located in the immediate vicinity of the
top landing of the stairway. Exterior stairways
providing access to a basement from the outside
grade level shall be provided with an artificial light
source located in the immediate vicinity of the bottom
landing of the stairway. The illumination of exterior
stairways shall be controlled from inside the dwelling.
37. USABLE SPACE UNDER STAIRS: IRC Section
R302.7. The walls and soffits of enclosed usable
space under stairs shall be protected on the enclosed
side by not less than 1 layer of ½” gypsum board.
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
6
STRUCTURAL
(Note: All buildings in Seismic Design Category D0,
D1 and D2 must be provided with minimum 3000 psi
concrete in accordance with IRC R404.1.3.3.1.)
40. MIN. CONCRETE FOOTING SIZE; See attached
engineer’s design.
41. MIN. CONCRETE FOOTING REINFORCEMENT:
See attached engineer’s design. IRC Section 403.1.3.
42. MIN. CONCRETE FOUNDATION WALL SIZE: See
attached engineer’s design. IRC Section 404.1.3 and
Tables R404.1.2(1) through R404.1.2(8).
43. MIN. CONC. FOUNDATION REINFORCEMENT: See
attached engineer’s design. IRC Section R404. At
least one horizontal #4 bar shall be located within 12
inches of the top of the wall and one #4 bar near mid-
height (at least two horizontal #4 bars within the top
12 inches if there is more than 4 feet of unbalanced
backfill (and permanent lateral support)). Where a
construction joint is located between the footing and
the foundation wall, vertical #4 bars, hooked into the
footing, shall be provided at least every 48 inches on
center. If only minimum prescriptive reinforcement is
utilized, reinforcement steel shall be minimum Grade
60 in accordance with IRC R404.1.3.3.7.1.
Additional provisions apply; see IRC R404.1.3 for
additional information
44. MINIMUM FOOTING DEPTH: See attached
engineer’s design. IRC Section R403.1.4. All exterior
footings shall be placed at least 12” below the
undisturbed ground. Interior footings supporting
bearing or bracing walls and cast monolithically with a
slab on grade shall extend to a depth of not less than
12” below the top of slab.
45. SLAB ON GRADE FLOOR: See attached engineer’s
design. IRC R506 & IRC R403.1.3.2. Foundations
must extend at least 6” above finish grade. Monolithic
slab/foundations shall have footings at least 12 inches
wide, be at least 12 inches below grade, extend at
least 6 inches above finish grade, and shall have at
least 1 #4 bars at the bottom of the footing and 1 #4
bar located within 7 inches of the top of the slab. IRC
R309.3: Garage or carport floor surfaces shall be
sloped to a drain or toward the main vehicle entry
doorway. IRC R506.2 A 4 inch thick base course of
clean sand, gravel or crushed stone shall be placed
on the prepared subgrade when the slab is below
grade. IRC R506.2.3 A 6 mil vapor retarder with
joints lapped at least 6 inches shall be placed
between the floor slab and the base course or
prepared subgrade. Some exceptions apply. IRC
506.2.4: Reinforcement must be supported to remain
in place from the center to upper one-third of the slab
during concrete placement. As a minimum standard,
see the handout: Prescriptive Foundation
Requirements.
46. FOUNDATION ANCHORAGE : See attached
engineer’s design. There shall be a minimum of 2
bolts per piece (sill plate), with a bolt located within
12” of each end of each piece. Holes shall not be
over-drilled, and 3” x 3” x ¼” thick hot dipped
galvanized plate washers and nuts shall be tightened
on each bolt to the plate.
47. DAMP-PROOF FOUNDATION WALLS / FOOTING
DRAINS: IRC Section R406 Exterior foundation
walls that retain earth and enclose habitable or usable
spaces located below grade shall be dampproofed in
accordance with IRC R406.1 or waterproofed in
accordance with IRC 406.2, from the top of the
footing to the finished grade by approved methods
and materials. All buildings that include basements,
cellars, crawl spaces or floors below grade shall be
provided with 3-inch minimum diameter perforated
footing drains laid in river rock, gravel or other free
draining material, protected with filter media, in
accordance with UPC 1101.6.
48. PIER PADS & COLUMNS: See attached engineer’s
design. IRC Section R407.3. Concrete pier footings
shall have a depth to width ratio not to exceed 2:1, or,
shall have #4 bars located each direction spaced not
more than 12” on center. (Rebar must be in place
upon inspection.) Positive connections shall be
provided to prevent lateral displacement at both the
top and bottom of columns.
51. FOUNDATION VENTILATION: IRC Section R408.2.
The minimum net area of ventilation openings shall
not be less than 1 square foot for each 300 square
feet of under-floor space area. One such ventilating
opening shall be within 3 feet of each corner of the
building. WA amendments allow one side of a
building to not have vents provided all other
provisions are satisfied. Ventilation openings shall
have grates or grills of materials identified in IRC
R408.2 such that the openings are not larger than ¼
inch. In addition, a minimum six mil black
polyethylene ground cover is required.
52. PROTECTION AGAINST DECAY: IRC Section
R317. All wood in contact with the ground and that
supports permanent structures intended for human
occupancy shall be approved pressure preservative
treated wood suitable for ground contact use. All
wood framing members that rest directly on concrete
or masonry foundation walls, or joists within 18 inches
of the ground, or beams within 12 inches of the
ground, or any structural members supporting a
pervious floor or roof shall be treated wood or decay-
resistant heartwood of redwood, black locust, or
cedars. (Note: All fasteners used in pressure treated
lumber [sills, joists to sill, rim joist to sill, etc.] shall be hot
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
7
dipped galvanized, stainless steel, silicon bronze or
copper. IRC R317.3.1)
53. POSTS, POLES AND COLUMNS: IRC Section
R317.1.4. Columns and posts that are embedded in
concrete or in direct contact with the ground, that
support permanent structures, shall be approved
pressure treated wood suitable for ground contact
use. Posts or columns which are exposed to the
weather, or are located in basements or cellars, shall
be supported by piers or metal pedestals projecting 1
inch above the floor (6” above exposed earth) and
shall be separated by an approved impervious
moisture barrier, or must be of pressure treated wood,
or wood of natural resistance to decay. Posts or
columns in enclosed crawl spaces located within the
periphery of the building, supported by concrete piers
or metal pedestals shall be greater than 8 inches from
exposed ground and must be separated by a
moisture barrier or be of pressure treated wood.
54. GIRDERS ENTERING MASONRY OR CONCRETE
WALL: IRC Section R319.1 (4) The ends of wood
girders entering concrete or masonry walls must have
a minimum clearance of ½ inch on tops, sides and
ends, or shall be of an approved species and grade of
lumber pressure treated or decay resistant heartwood
of redwood, black locust, black walnut or cedars.
55. POST-BEAM CONNECTIONS/FASTENING: IRC
R301, R407.3, R502.9. Where posts and beam or
girder construction is used to support framing,
positive connections shall be provided to ensure
against uplift and lateral displacement. The
construction of buildings and structures shall result in
a system that provides a complete load path capable
of transferring all loads from their point of origin
through the load resisting elements to the foundation.
56. SPECIFY WOOD SPECIES & GRADES: IRC
Sections R502.1, R602.1 Load-bearing dimension
lumber for joists, beams, girders, studs, plates and
headers shall be identified by a grade mark of a
lumber grading or inspection agency that has been
approved by an accreditation body that complies with
DOC PS 20. In lieu of a grade mark, for wood locally
milled, a certificate of inspection issued by a lumber
grading or inspection agency meeting the
requirements of this section may be accepted.
57. FLOOR FRAMING: IRC Sections R502.3, R502.6,
R502.6.1, R502.7, R502.2.1 The ends of each joist,
beam or girder shall have not less than 1-1/2” of
bearing on wood or metal or not less than 3” on
masonry or concrete. Joists framing from opposite
sides over a bearing support shall lap a minimum of 3
inches and shall be nailed together with a minimum
three 10d face nails. Joists shall be supported
laterally at each end and at each intermediate support
by full-depth solid blocking not less than 2” nominal
thickness; or by attachment to a header, band, or rim
joist; or shall be otherwise provided with lateral
support to prevent rotation. See IRC Tables
R502.3.1(1) & (2) for floor joist spans, R502.5(1) & (2)
for girder spans, and R502.3.3 (1) & (2) for cantilever
spans. Note: A load path for lateral forces shall be
provided between floor framing and braced wall
panels located above or below a floor.
58. BEARING PARTITIONS: IRC Section 502.4. Joists
under parallel bearing partitions shall be of adequate
size (as a beam) to support the load. Double joists,
sized to adequately support the load, that are
separated to permit the installation of piping or vents
shall be full-depth, solid-blocked with lumber not less
than 2 inches in nominal thickness spaced not more
than 4 feet on center. Bearing partitions perpendicular
to joists shall not be offset from supporting girders,
walls or partitions more than the joist depth unless
such joists are of sufficient size to carry the additional
load(s).
59. UNDER-FLOOR CLEARANCE: IRC Section 319.1.
When floor joists or the bottom of a wood structural
floor are located within 18" or wood girders are
located within 12" of exposed ground in crawl spaces
or unexcavated areas located within the periphery of
the building foundation, all components of the floor
assembly shall be pressure treated wood or wood of
natural resistance to decay, including all posts,
beams or girders, joists and sub-floor. The under-
floor grade shall be cleaned of all vegetation and
organic material. All wood forms used for placing
concrete and construction materials shall be
removed.
61. WALL FRAMING: See attached engineer’s design.
IRC Sections 602.3.1, 602.3.2, 602.3.3, 602.3.4,
602.6 & 602.9. Utility grade studs shall not be spaced
more than 16" on center, support more than a roof
and ceiling, or exceed 8' in height for exterior and
load bearing walls. The size, height, and spacing of
all other wood-framing studs shall be in accordance
with the engineer’s calculated design. Studs shall be
placed with their wide dimension perpendicular to the
wall. Wood stud walls shall be capped with a double
top plate installed to provide overlapping at corners
and intersections with bearing partitions. End joints
shall be offset at least 24” or the minimum required by
the engineer’s design. Studs shall have full bearing
on a nominal 2” or larger plate or sill having a width at
least equal to the width of the studs. Where joists,
trusses, or rafters are spaced more than 16” o.c. and
the bearing studs are spaced 24” o.c. such members
shall bear within 5” of the studs beneath.
Bored or drilled holes: The diameter of the resulting
hole may not exceed 40% of the stud width, can be
no closer than 5/8” to the edge of the stud, and may
not be located in the same section as a cut or notch.
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
8
See IRC Section R602.6 for exceptions and IRC
Figures R602.6(1), R602.6.2(2), and R602.6 for
additional details.
Cutting and notching of studs: May not exceed 25%
of the stud width in bearing or exterior walls and may
not exceed 40% of a single stud width in non-bearing
partitions.
Cutting and notching of top plate: When piping or
ducts necessitate notching or drilling a top plate by
more than 50% of its width, a galvanized metal tie not
less than .054 inch thick (16 gage) by 1½” wide shall
be fastened across and to the plate at each side of
the opening with at least 8 10d nails. The metal tie
must extend at least 6 inches past each side of the
opening.
62. WALL BRACING: See attached engineer’s design.
(Any cripple walls must be designed by the engineer
to work with the designed shear-walls. If the plan
does not include cripple walls, and they are
necessary on-site, a plan addendum will be required
from the engineer.)
63. OPENINGS IN EXTERIOR & INTERIOR WALLS
(HEADERS): See attached engineer’s design. IRC
Section R602.7. Headers shall be provided over
each opening in interior and exterior bearing walls.
Headers shall be sized to support the load above in
accordance with IRC Tables R502.5(1) and
R502.5(2), or as designed to support the loads as
specified in IRC Table R301.5. Each end of all
headers shall have at least 1.5" of full-width bearing.
64. FIRE-BLOCKS & DRAFT-STOPS: IRC Sections
R302.11, R302.12, R602.8, R502.12. Firebocking &
Draftstopping shall be installed to cut off all concealed
vertical and horizontal draft openings and shall form
an effective fire barrier between stories and between
a top story and the roof space. Fireblocking shall be
provided in concealed spaces of wood stud walls and
partitions: vertically at the ceiling and floor levels;
horizontally at intervals not exceeding 10 feet; and at
all interconnections between concealed vertical and
horizontal spaces such as occur at soffits, drop
ceilings and cove ceilings, as well as stair stringers at
the top and bottom of the run and openings around
vents, pipes and ducts at ceiling and floor levels.
Fireblocking materials shall consist of material listed
in IRC Section R302.11.1. Loose-fill insulation
material shall not be used as a fireblock unless
specifically tested in the form and manner intended.
Fireblocking of chimneys and fireplaces shall be in
accordance with IRC Section R1001.12. When there
is usable space both above and below a concealed
space of a floor/ceiling assembly, draftstops shall be
installed so that the area of the concealed space does
not exceed 1000 square feet. Draftstopping materials
shall consist of materials listed in Section R302.12.1.
All fireblocking and draftstopping shall be in place
prior to requesting a framing inspection.
65. SIDING TYPE IRC Section R703.3, R703.4, R703.5,
R703.8, R703.9, and R703.10. Exterior wall
coverings shall be installed, attached and flashed in
accordance with the provisions of IRC Section R703
and the siding manufacturer’s installation instructions.
66. WEATHER RESISTIVE BARRIER & FLASHING:
IRC Sections R703.2, R703.4 R703.8, R703.9.1.
The exterior wall envelope shall be designed and
constructed to provide a water-resistant barrier
behind the exterior veneer. Asphalt-saturated felt or
other approved weather resistant material such as
housewrap, shall be applied over the sheathing of all
exterior walls except where panel siding with shiplap
joints or other approved weather resistive methods
are used. Such felt or housewrap material shall be
applied horizontally, with the upper layer lapped over
the lower layer not less than 2”.
Approved corrosion-resistive flashing shall be
provided in all exterior walls in such a manner as to
prevent entry of water into the wall or the building
structural framing components. Self-adhered
membranes used as flashing shall comply with AAMA
711. The flashing shall extend to the surface of the
exterior wall finish and shall be installed to prevent
water from reentering the exterior wall envelope. See
Section R703.8 for specific locations.
68. SIDING/EARTH SEPARATION: IRC Section R317.1
#5. Wood siding, sheathing and wall framing at the
exterior of the building within 6" of ground, or less
than 2 inches measured vertically from concrete
steps, porch slabs, patio slabs and similar horizontal
surfaces exposed to the weather, shall be
preservative treated wood or wood of natural
resistance to decay.
69. DECKS & EXTERIOR STAIRS: IRC Section R317.
Naturally durable wood, such as heartwood of cedar
or redwood, or preservative treated (pressure treated)
wood shall be used for those portions of exposed
wood members and members subject to wind driven
rain, such as within a covered porch, that form the
structural supports of buildings, balconies, porches,
decks or similar structures, including all joists, beams,
girders, decking and posts, poles and columns. All
field cut board ends, notches, etc. of pressure treated
wood shall be treated in the field in accordance with
AWPA M4. Deck or porch ledger boards fastened to a
wall shall be properly flashed and positively
connected. (See IRC 502.2.2)
70. STEEL STRUCTURE: Special Inspection in
accordance with IBC Chapter 17 is required for the
steel structure. All special inspection reports shall be
provided to the Department of Community
Development prior to requesting any structural
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
9
(engineered metal building) inspections. Steel
structure framing members shall not be cut, drilled or
altered in any manner without the explicit design and
consent of the metal building engineer. Alterations
resulting in the addition of load (e.g., HVAC
equipment, water heaters, etc.) that exceed the
design load shall not be permitted without specific
engineering justifying the design.
75. ROOF DRAINAGE & COVERING IRC Section
R801.3, R903, R904, R905. All structures shall have
a controlled method of water collection and disposal
from roofs (typically gutters). Water shall discharge to
an approved drainage system or, where a drainage
system is not provided, to splash blocks that will
disperse water to the ground surface at least 5 feet
from foundation walls. Roofs that do not drain over
edges shall have roof drains installed at the low point
of the roof as well as overflow drains. See IRC
R903.4. Roof slope shall be indicated on the plans
and selected roof covering must be appropriate for
the roof pitch. Roof coverings must be installed in
accordance with the manufacturer’s installation
instructions. Flashing shall be installed at wall & roof
intersections, at changes in roof slope or direction,
and around roof openings. Where flashing is metal,
the metal shall be corrosion- resistant with a minimum
thickness of 0.019 inch (No. 26 galvanized sheet).
Roof dead loads are limited to a maximum of 15
pounds per square foot unless the additional bracing
provisions of R301.2.2.2.1 are provided, or the
structural system is designed by a professional
engineer.
76. ATTIC VENTILATION (None): The roof system is
proposed as an unvented roof assembly, which
requires closed-cell spray-foam insulation as
described in the approved plans. No substitutions will
be permitted. (IRC R806).
GENERAL
78. PREMISES IDENTIFICATION: IRC Section R319.1
Approved numbers or addresses shall be provided in
such a position as to be plainly visible and legible
from the street or road fronting the property. These
numbers shall contrast with their background.
Address numbers shall be Arabic numbers or
alphabetical letters a minimum of 4 inches high with a
minimum stroke width of ½ inch. Property address
shall be posted prior to requesting any inspections.
79. APPROVED PLANS: IRC Sections R105.7,
R106.3.1, R106.4. When the building official issues a
permit, the construction documents are approved in
writing or by stamp. All work shall be done in
accordance with the approved construction
documents, any changes made during construction
shall be resubmitted for approval. The building permit,
inspection card, and the set of approved construction
documents must remain on the job site at all times
until the completion of the project.
80. HEATING: IRC R303.8. Every dwelling unit shall be
provided with heating facilities capable of maintaining
a room temperature of 68º F at a point 3’ above the
floor and 2’ from exterior walls in all habitable rooms.
81. SKYLIGHTS: IRC 308.6. Skylight glazing shall be:
1) Laminated glass with a minimum .015” polyvinyl
butyl interlayer for glass panes 16 sq. ft. or less in
area located such that the highest point of the glass is
not more than 12’ above a walking surface or other
accessible area; for higher or larger sizes, the
minimum interlayer thickness shall be .030”; or
2) Fully tempered glass; or
3) Heat-strengthened glass; or
4) Wired glass; or
5) Approved rigid plastics.
Skylights shall comply with Washington State Energy
Code requirements and be provided with flashing
appropriate for the skylight and the type of roofing.
82. GYPSUM WALLBOARD: IRC R702.3.8 & R702.4.2,
R702.3.8.1. When gypsum is used as a base for tile
or wall panels for tub/shower enclosures, water-
resistant gypsum shall be used. (Water resistant
gypsum wallboard may not be used over a vapor
retarder, or on ceilings where framing member
spacing exceeds 12” on center.) Cement, fiber-
cement, and glass mat gypsum backers in
compliance with ASTM C 1288, C 1325 or C 1178,
installed in accordance with the manufacturer’s
recommendations shall be used as backers for wall
tile or wall panels in tub & shower areas.
83. GYPSUM WALLBOARD FASTENING: IRC R702.3.6
& Table R702.3.5, IBC 2508.1.Screws for attaching
gypsum board to wood framing shall be type W or
Type S in accordance with ASTM C 1002 and shall
penetrate the wood not less than 5/8”; and be:
3/8" minimum from edge and ends for
nails or screws.
Nails: 7" o.c. ceiling, 8" o.c. walls; or
Screws: 12" o.c. ceiling, 16" o.c. walls
when wall framing is 16" o.c., 12" o.c.
when wall framing is 24" o.c.
Footnote e, Table R702.3.5: Type X gypsum
wallboard for garage ceilings beneath habitable
rooms shall be installed perpendicular to the ceiling
framing and shall be fastened at 6” o.c. by minimum
1-7/8” 6d coated nails or equivalent drywall screws.
84. NUMBER OF BUILDING STORIES: IRC Sections
R101.2, R202. A building story is that portion of a
building included between the upper surface of a floor
and the upper surface of the floor or roof next above.
The first “Story Above Grade” is the first story having
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
10
its finished floor surface entirely above grade, except
that a basement shall be considered as a story above
grade where the finished surface of the floor above
the basement is: 1) More than 6’ above grade plane;
2) More than 6’ above the finished ground level for
more than 50% of the total building perimeter; or, 3)
More than 12’ above the finished ground at any level.
The number of stories is the sum of the first story
above grade plane plus all of the stories above.
85. HEIGHT OF BUILDING / GRADE PLANE: IRC
Section 202. The building height is the vertical
distance from grade plane to the average height of
the highest roof surface. The grade plane is a
reference plane representing the average of the
finished ground level adjoining the building at all
exterior walls. Where the finished ground level slopes
away from the exterior walls, (which is required) then
the reference plane shall be established by the lowest
points within the area between the building and the lot
line, or, where the lot line is more than 6’ from the
building, the grade plane shall be established by the
lowest points between the building and points 6’ from
the building.
86. RETAINING WALLS: IBC 1806.1, IRC R105.2.
Retaining walls shall be designed to ensure stability
against overturning, sliding, excessive foundation
pressure and water uplift. Retaining walls shall be
designed for a safety factor of 1.5 against lateral
sliding and overturning. Retaining walls that do not
exceed 4’ in height, measured from the bottom of the
footing to the top of the wall, that do not support a
surcharge (load above) are exempt from permit
requirements, however, must still be constructed
properly and must conform with the adopted codes.
Typically, a separate permit is required for
construction of a retaining wall.
ENERGY CODE
100. FOUNDATION INSULATION: WSEC Sections
R402.2.9. Slab-on-grade insulation, (typically R-10)
installed inside the foundation wall, shall extend
downward from the top of the slab for a minimum
distance of 24” or downward from the top of the slab
and then horizontally beneath the slab for a minimum
combined distance of 24”. Insulation installed outside
the foundation shall extend downward to a minimum
of 24” or to the frostline. Above grade insulation shall
be protected. For monolithic slabs, the insulation
shall extend downward from the top of the slab to the
bottom of the footing.
101. UNDER-FLOOR INSULATION: WSEC. Floors over
unconditioned spaces, such as vented crawl spaces,
unconditioned basements and garages shall be
insulated to not less than the nominal R-value shown
for floors over unconditioned spaces on the energy
code application for the compliance option chosen
(typically R-30). Insulation supports shall hold
insulation in substantial contact with the subfloor and
shall be installed such that spacing does not exceed
24 inches on center.
102. WALL INSULATION: WSEC R402.1. (See
Approved Plans… wall assemblies include a layer of
closed-cell spray-foam insulation as well as fiberglass
batts.) Above grade exterior walls shall be insulated
to not less than the nominal R-value as specified on
the energy code application for the compliance option
chosen. (Typically R-21) Faced batts shall be face-
stapled (not inset-stapled), to avoid compression.
Headers shall be insulated to a minimum R-10.
Below grade walls shall be insulated either on the
exterior to a minimum level of R-10, or on the interior
to the same level as walls above grade.
103. ATTIC INSULATION / VAULTED CEILING
INSULATION: WSEC. Ceilings shall be insulated to
not less than the nominal R-value shown for ceilings
on the energy code application for the compliance
option chosen (Typically, minimum R-49 ceiling
insulation is required unless advanced roof framing
methods are utilized, which allows a reduction to R-
38.). See approved plan for closed-cell spray-foam
insulation requirements associated with the unvented
roof assembly.
105. HATCHES AND DOORS: WSEC. Access doors
from conditioned to unconditioned spaces (such as
attic and crawl space access doors) shall be weather-
stripped and insulated to a level equivalent to the
insulation on the surrounding surfaces.
106. DUCT SYSTEMS:
Duct Insulation: WSEC Sections. All heating ducts
within unconditioned spaces shall be insulated to a
minimum of R-8. Ducts installed under slabs shall be
insulated to a minimum of R-5.
Duct Location: Installation of ducts in walls, floors or
ceilings shall not displace required envelope
insulation. Building cavities shall not be used as
ducts.
Duct Sealing: All ducts located outside the
conditioned space shall be sealed in accordance with
IRC M1601.3 or IMC 603.9 using mastics, liquid
sealants, gasketing or tape systems consistent with
the manufacturers listed system. Note: duct tape is
not a duct sealant.
Duct Testing: Unless the air handler and all ducts
are located inside the conditioned space, duct
tightness testing is required in accordance with RS-
33, using the maximum leakage rates established in
WSEC (typically 6 cfm per 100 square feet of
consitioned floor area, at 0.1 inches w.g (25 Pascals)
with the air handler in place). Copies of all test
results shall be provided to the building department.
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
11
107. PIPE INSULATION: WSEC. Water pipes outside of
the conditioned space shall be insulated with pipe
insulation a minimum of 1 inch thick (conductivity
0.22-0.28).
108. VAPOR RETARDER: WSEC. Vapor retarders shall
be installed on the warm side (in winter) of insulation.
Vapor retarders are not required in roof/ceiling
assemblies where the ventilation space above the
insulation averages 12” or greater. Other exceptions
may apply.
109. WINDOWS: WSEC R402.1. The total glazing area
shall have an area weighted average U-factor not to
exceed that specified in Table R402.1.1 (typically
.30). The window brand, model and U-value must be
shown on the energy code application. Any change in
windows must be approved by the Building Division
before installation. NFRC compliance stickers shall
remain on the windows until the framing inspection
has been approved.
111. EXTERIOR DOORS: WSEC. Glazed doors are
considered to be windows. Exterior (opaque) doors
shall have an area weighted average U-factor not to
exceed that specified in Table R402.1.1 (.20). A
single ornamental door may be excepted. See
WSEC R402 for additional information.
112. EXHAUST FANS: Table M1507.4:
Table M1507.4 Minimum Source Specific Ventilation
Capacity Requirements
Laundry rooms
or Bathrooms Kitchens
Intermittently
Operating 50 cfm 100 cfm
Continuous
Operation 20 cfm 25 cfm
All fans shall provide the required flow when tested at
0.25 water gauge as determined per HVI 916 or
AMCA 210 in accordance with IRC M1507.4.1. Fans
larger than the above prescriptive sizes may be
necessary to attain the required flow.
113. WHOLE HOUSE FAN: IRC M1507. Each new
dwelling unit shall be equipped with a whole house
ventilation system in accordance with IRC Section
M1507.3.4 (exhaust fan), M1507.3.5 (integrated with
forced-air), M1507.3.6 (supply fan) or M1507.3.7
(HRV system), with ventilation capacities in
accordance with IRC M1507.3.3 and Table
M1507.3.3(1) for continuous systems, or M1507.3.3
and Table M1507.3.3(2) for intermittent systems.
Fans located 4 feet or less from the interior grill shall
have a sone rating of 1.0 or less measured at 0.1”
water gauge.
TABLE M1507.3.3(1) Minimum Ventilation Rates
(Continuously Operated System): Min. CFM (Qr)
Floor Number of Bedrooms
Area, ft2 0-1 2-3 4-5 6-7 >7
Min. Min. Min. Min. Min.
< 1500 30 45 60 75 90
1501-3000 45 60 75 90 105
3001-4500 60 75 90 105 120
4501-6000 75 90 105 120 135
6001-7500 90 105 120 135 150
> 7500 105 120 135 150 165
TABLE M1507.3.3(2)
Ventilation Effectiveness For Intermittant Fans.
Run-
TimePercentage
in each 4-Hour
Segment f 25% 33% 50% 66% 75% 100%
Factor 4 3 2 1.5 1.3 1.0
The minimum ventilation rate for intermittently
operating ventilation systems (Qf) shall be the
ventilation rate prescribed in Table M1507.3.3(1)
multiplied by the factor in Table M1507.3.3(2).
TABLE M1507.3.6.2:
Prescriptive Supply Fan Duct Sizing
Supply Fan Tested at 0.40” W.G.
Specified Volume from
Table 408.1
Minimum
Smooth Duct Diameter
Minimum
Flexible Duct Diameter
50 – 90 CFM 4 inch 5 inch
90 - 150 CFM 5 inch 6 inch
150 – 250 CFM 6 inch 7 inch
250 – 400 CFM 7 inch 8 inch
114. WHOLE HOUSE VENTILATION SYSTEM
CONTROLS: IRC M1507.3.2. Ventilation system
controls shall be readily accessible. Intermittently
operated systems, including exhaust system, supply
system, HRV system as well as those systems
integrated with a forced-air system shall have a
manual control, as well as an automatic control, such
as a clock timer. The automatic control timer shall be
set to operate the whole house fan system for at least
1 hour out of every four. A label shall be affixed to
the control that reads “Whole House Ventilation (See
Operating Instructions).” The installer shall provide
the whole house ventilation system manufacturer’s
operation description and operating instructions.
115. VENTILATION DUCTS: IRC M1508. All ventilation
supply ducts in the conditioned space shall be
insulated to a minimum of R-4. Exhaust ducts shall
be sized in accordance with the system
manufacturer’s instructions, shall terminate outside
the building, and be equipped with back draft
dampers. Exhaust ducts located outside the
conditioned space shall be insulated to a minimum of
R-4.
116. WINDOW OR WALL PORTS: WS-IRC M1507.3.4.4.
Individual room outdoor air inlets shall have a
screened, controllable and secure opening and be
capable of a total opening area of not less than 4
square inches. Outdoor air inlets shall be located so
CODEPROS, LLC
CUSTOM PROJECT CHECKLIST
12
as not to take air from within 10 feet of a plumbing
vent opening, or an appliance vent outlet, or where it
will pick up objectionable odors, fumes or flammable
vapors. Individual outdoor air inlets are not required
if the home is provided with a ducted forced-air
heating system that communicates with all habitable
rooms and is equipped with an outdoor air intake.
117. DISTRIBUTION: WS-IRC M1507.3.4.4. Where
outdoor air supplies (window or wall ports) are
separated from fan locations by doors, provisions
shall be made to ensure air flow by installation of
distribution ducts, undercutting of doors, installation of
grilles, transoms, or similar means. Doors shall be
undercut to a minimum of ½” above the surface of the
finished floor covering.
118. PRESCRIPTIVE HEATING SYSTEM SIZING:
IRC M1401.3. All equipment must be sized in
accordance with ACCA Manual S based on building
loads calculated in accordance with ACCA Manual J,
Residential Load Calculation, 8th Edition, or other
approved calculation methods.
Additional Energy Code Information may be obtained
from the WSU Energy Program at:
www.energy.wsu.edu/code .
119. WSEC Table R406.2 Energy Credits. The
Prescriptive Energy Code Compliance Form indicates
that Table R406.2 Options 1.4, 2.1, 3.6, and 7.1 will
be incorporated into the project in order to satisfy
WSEC R406.2 requirements. They are as follows:
1.4. EFFICIENT BUILDING ENVELOPE (1.0):
Prescriptive compliance is based on Table R402.1.1
with the following modifications: Vertical fenestration
U=0.25; Wood frame wall R-21 int plus R-4 ci; Floor
R-38; Basement wall R-21 int plus R-5 ci; Slab on
grade R-10 perimeter and under entire slab; Below
grade slab R-10 perimeter and under entire slab, OR,
Compliance based on Section R402.1.4: Reduce the
Total UA by 15%.
2.1. AIR LEAKAGE CONTROL AND EFFICIENT
VENTILATION (0.5): Compliance based on
R402.4.1.2:
Reduce the tested air leakage to 3.0 air changes
per hour maximum at 50 Pascals; and
All whole house ventilation requirements as
determined by Section M1507.3 of the International
Residential Code or Section 403.8 of the
International Mechanical Code shall be met with a
high efficiency fan(s) (maximum 0.35 watts/cfm),
not interlocked with the furnace fan (if present).
Ventilation systems using a furnace including an
ECM motor are allowed, provided that they are
controlled to operate at low speed in ventilation
only mode.
To qualify to claim this credit, the building permit
drawings shall specify the option being selected, the
maximum tested building air leakage, and shall show
the qualifying ventilation system and its control
sequence of operation.
3.6. HIGH EFFICIENCY HVAC EQUIPMENT (2.0):
Ductless split system heat pumps with no electric
resistance heating in the primary living areas. A ductless
heat pump system with a minimum HSPF of 10 shall be
sized and installed to provide heat to entire dwelling unit
at the design outdoor air temperature.
To qualify to claim this credit, the building permit drawings
shall specify the option being selected, the heated floor
area calculation, the heating equipment type(s), the
minimum equipment efficiency, and total installed heat
capacity (by equipment type). (Footnote a: An alternative heating source
sized at a maximum of 0.5 Watts/ft2 (equivalent) of heated floor area or 500 Watts,
whichever is bigger, may be installed in the dwelling unit.)
7.1. APPLIANCE PACKAGE OPTION (0.5):
All of the following appliances shall be new and installed
in the dwelling unit and shall meet the following
standards:
Dishwasher – Energy Star rated
Refrigerator (if provided) – Energy Star rated
Washing machine – Energy Star rated
Dryer – Energy Star rated, ventless dryer with a
minimum CEF rating of 5.2.
To qualify to claim this credit, the building permit drawings
shall specify the option being selected and shall show the
appliance type and provide documentation of Energy Star
compliance. At the time of inspection, all appliances shall
be installed and connected to utilities. Dryer ducts and
exterior dryer vent caps are not permitted to be installed in
the dwelling unit..