Loading...
HomeMy WebLinkAboutBLD2022-00391-07A- Structural CalculationstnxTower Report - version 8.1.1.0 Date: May 04, 2022 B+T Group 1717 S. Boulder, Suite 300 Tulsa, OK 74119 (918) 587-4630 Subject: Structural Analysis Report Carrier Designation: AT&T Mobility Co-Locate Site Number: RN12 Site Name: Anderson Lake FA Number: 10092414 Crown Castle Designation: BU Number: 846384 Site Name: Anderson Lake JDE Job Number: 691641 Work Order Number: 2103639 Order Number: 591705 Rev. 0 Engineering Firm Designation: B+T Group Project Number: 163554.001.01 Site Data: 413 Southport Lane, Port Townsend, Jefferson County, WA Latitude 48° 1' 26.4'', Longitude -122° 49' 21.4'' 150 Foot - Monopole Tower B+T Group is pleased to submit this “Structural Analysis Report” to determine the structural integrity of the above-mentioned tower. The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we have determined the tower stress level for the structure and foundation, under the following load case, to be: LC5: Proposed Equipment Configuration Sufficient Capacity This analysis has been performed in accordance with the 2018 International Building Code based upon an ultimate 3-second gust wind speed of 97 mph. Applicable Standard references and design criteria are listed in Section 2 - Analysis Criteria. Structural analysis prepared by: Clint Coody Respectfully submitted by: B+T Engineering, Inc. COA: 3425; Expires: 12/31/2022 John W. Kelly, P.E., S.E. RECEIVED BY DCD 7/5/22 May 04, 2022 150 Ft Monopole Tower Structural Analysis CCI BU No 846384 Project Number 163554.001.01, Order 591705, Revision 0 Page 2 tnxTower Report - version 8.1.1.0 TABLE OF CONTENTS 1) INTRODUCTION 2) ANALYSIS CRITERIA Table 1 - Proposed Equipment Configuration Table 2 - Other Considered Equipment 3) ANALYSIS PROCEDURE Table 3 - Documents Provided 3.1) Analysis Method 3.2) Assumptions 4) ANALYSIS RESULTS Table 4 - Section Capacity (Summary) Table 5 – Tower Component Stresses vs. Capacity – LC5 4.1) Recommendations 5) APPENDIX A tnxTower Output 6) APPENDIX B Base Level Drawing 7) APPENDIX C Additional Calculations RECEIVED BY DCD 7/5/22 May 04, 2022 150 Ft Monopole Tower Structural Analysis CCI BU No 846384 Project Number 163554.001.01, Order 591705, Revision 0 Page 3 tnxTower Report - version 8.1.1.0 1) INTRODUCTION This tower is a 150 ft. Monopole tower designed by Valmont. 2) ANALYSIS CRITERIA TIA-222 Revision: TIA-222-H Risk Category: II Wind Speed: 97 mph Exposure Category: D Topographic Factor: 5 Wind Speed with Ice: 30 mph Seismic Ss: 1.322 Seismic S1: 0.482 Service Wind Speed: 60 mph Table 1 - Proposed Equipment Configuration Mounting Level (ft) Center Line Elevation (ft) Number of Antennas Antenna Manufacturer Antenna Model Number of Feed Lines Feed Line Size (in) 146.0 151.0 6 Cellmax Tech.CMA- UBTULBULBHH/6517/17/21/21_CCIV2 15 2 1 1 1-5/8 5/8 3/8 13/64 3 Kathrein 800 10121 3 Nokia AHCA_CCIV3 3 Nokia AHFIB_CCIV2 3 Nokia AHLBBA_CCIV2 3 Nokia AHNA_CCIV2 1 Raycap DC6-48-60-18-8F_CCIV2 1 Raycap DC9-48-60-24-8C-EV_CCIV2 150.0 3 Powerwave TT19-08BP111-001 146.0 1 --Platform Mount [LP 713-1] Table 2 - Other Considered Equipment Mounting Level (ft) Center Line Elevation (ft) Number of Antennas Antenna Manufacturer Antenna Model Number of Feed Lines Feed Line Size (in) 121.0 124.0 3 KMW Comm. ET-X-WM-18-65-8P 1 3 1 1-7/16 1-1/4 1/4 3 KMW Comm.ETCR-654L12H6 1 Samsung Telecomm. 2.5G 8T8R RADAR FILTER 3 Samsung Telecomm. 2.5GHz RRH-V3 3 Samsung Telecomm. Optic Fiber Junction Cylinder 3 Samsung Telecomm. Power Junction Cylinder 6 Samsung Telecomm.RRH-C2A W/ EXT FILTER_CCIV2 3 Samsung Telecomm.RRH-P4 121.0 1 Andrew VHLP2-18 1 Dragonwave Horizon Quantum 1 --Sector Mount [SM 411-3] 119.0 120.0 2 Kathrein 800-10080 2 1/2 RECEIVED BY DCD 7/5/22 May 04, 2022 150 Ft Monopole Tower Structural Analysis CCI BU No 846384 Project Number 163554.001.01, Order 591705, Revision 0 Page 4 tnxTower Report - version 8.1.1.0 3) ANALYSIS PROCEDURE Table 3 - Documents Provided Document Reference Source Tower Manufacturer Drawing 5183129 CCI Sites Foundation Mapping 5298964 CCI Sites Geotech Report 4302286 CCI Sites Crown CAD Package Date: 04/14/2022 CCI Sites 3.1) Analysis Method tnxTower (version 8.1.1.0), a commercially available analysis software package, was used to create a three-dimensional model of the tower and calculate member stresses for various loading cases. Selected output from the analysis is included in Appendix A. When applicable, Crown Castle has calculated and provided the effective area for panel antennas using approved methods following the intent of the TIA-222 standard. 3.2) Assumptions 1) The tower and structures were maintained in accordance with the - TIA-222 standard. 2) The configuration of antennas, transmission cables, mounts and other appurtenances are as specified in Tables 1 and 2 and the referenced drawings. This analysis may be affected if any assumptions are not valid or have been made in error. B+T Group should be notified to determine the effect on the structural integrity of the tower. 4) ANALYSIS RESULTS Table 4 - Section Capacity (Summary) Section No. Elevation (ft) Component Type Size Critical Element P (K) SF*P_allow (K) % Capacity Pass / Fail L1 150 - 95.917 Pole TP34.29x21.313x0.281 1 -12.355 1823.997 50.7 Pass L2 95.917 - 46.583 Pole TP45.571x32.508x0.375 2 -23.441 3237.958 56.1 Pass L3 46.583 - 0 Pole TP56x43.281x0.469 3 -42.811 5148.486 53.8 Pass Summary Pole (L2) 56.1 Pass Rating = 56.1 Pass RECEIVED BY DCD 7/5/22 May 04, 2022 150 Ft Monopole Tower Structural Analysis CCI BU No 846384 Project Number 163554.001.01, Order 591705, Revision 0 Page 5 tnxTower Report - version 8.1.1.0 Table 5 - Tower Component Stresses vs. Capacity – LC5 Notes Component Elevation (ft) % Capacity Pass / Fail 1,2 Anchor Rods Base 60.8 Pass 1,2 Base Plate Base 33.4 Pass 1,2 Base Foundation (Structure)Base 47.9 Pass 1,2 Base Foundation (Soil Interaction)Base 28.2 Pass Structure Rating (max from all components) = 60.8% Notes: 1) See additional documentation in “Appendix C – Additional Calculations” for calculations supporting the % capacity consumed. 2) Rating per TIA-222-H Section 15.5. 4.1) Recommendations The tower and its foundations have sufficient capacity to carry the proposed load configuration. No modifications are required at this time. RECEIVED BY DCD 7/5/22 APPENDIX A TNXTOWER OUTPUT RECEIVED BY DCD 7/5/22 B+T Group 1717 S. Boulder, Suite 300 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Job: 163554.001.01 - ANDERSON LAKE, WA (BU# 846384 Project: Client: Crown Castle Drawn by: R AITHAL App'd: Code: TIA-222-H Date: 05/03/22 Scale: NTS Path: G:\SA jobs\03-05-2022--\163554_846384_Anderson lake----Ranjith-----Akshaykumar--\Tnx_001_01\163554_001_01_ANDERSON LAKE_WA.eri Dwg No. E-1 150.0 ft 95.9 ft 46.6 ft 0.0 ft REACTIONS - 97 mph WIND TORQUE 1 kip-ft 35 K SHEAR 3380 kip-ft MOMENT 43 K AXIAL ARE FACTORED ALL REACTIONS S e c t i o n 1 2 3 L e n g t h ( f t ) 54 . 0 8 3 54 . 4 1 7 53 . 0 0 0 N u m b e r o f S i d e s 12 12 12 T h i c k n e s s ( i n ) 0. 2 8 1 0. 3 7 5 0. 4 6 9 S o c k e t L e n g t h ( f t ) 5. 0 8 3 6. 4 1 7 T o p D i a ( i n ) 21 . 3 1 3 32 . 5 0 8 43 . 2 8 1 B o t D i a ( i n ) 34 . 2 9 0 45 . 5 7 1 56 . 0 0 0 G r a d e A5 7 2 - 6 5 W e i g h t ( K ) 4. 6 8. 6 13 . 4 26 . 6 MATERIAL STRENGTH GRADE GRADEFy FyFu Fu A572-65 65 ksi 80 ksi TOWER DESIGN NOTES 1. Tower is located in Jefferson County, Washington. 2. Tower designed for Exposure D to the TIA-222-H Standard. 3. Tower designed for a 97 mph basic wind in accordance with the TIA-222-H Standard. 4. Deflections are based upon a 60 mph wind. 5. Tower Risk Category II. 6. Topographic Category 5 with Crest Height of 324.000 ft 7. TIA-222-H Annex S 8. TOWER RATING: 56.1% RECEIVED BY DCD 7/5/22 B+T Group 1717 S. Boulder, Suite 300 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Job: 163554.001.01 - ANDERSON LAKE, WA (BU# 846384 Project: Client: Crown Castle Drawn by: R AITHAL App'd: Code: TIA-222-H Date: 05/03/22 Scale: NTS Path: G:\SA jobs\03-05-2022--\163554_846384_Anderson lake----Ranjith-----Akshaykumar--\Tnx_001_01\163554_001_01_ANDERSON LAKE_WA.eri Dwg No. E-4 0 0 50 50 Global Mast Shear (K) 150.000 95.917 46.583 0.000 El e v a t i o n ( f t ) 0 0 5000 5000 Global Mast Moment (kip-ft) 150.000 95.917 46.583 0.000 TIA-222-H - 97 mph Exposure D Maximum Values Vx Vz Mx MzRECEIVED BY DCD 7/5/22 B+T Group 1717 S. Boulder, Suite 300 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Job: 163554.001.01 - ANDERSON LAKE, WA (BU# 846384 Project: Client: Crown Castle Drawn by: R AITHAL App'd: Code: TIA-222-H Date: 05/03/22 Scale: NTS Path: G:\SA jobs\03-05-2022--\163554_846384_Anderson lake----Ranjith-----Akshaykumar--\Tnx_001_01\163554_001_01_ANDERSON LAKE_WA.eri Dwg No. E-5 TIA-222-H - Service - 60 mph Maximum Values 0 0 50 50 Deflection (in) 150.000 95.917 46.583 0.000 El e v a t i o n ( f t ) 0 0 0.5 0.5 1 1 1.5 1.5 2 2 Tilt (deg) 0 0 0.05 0.05 0.1 0.1 Twist (deg) 150.000 95.917 46.583 0.000 RECEIVED BY DCD 7/5/22 B+T Group 1717 S. Boulder, Suite 300 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Job: 163554.001.01 - ANDERSON LAKE, WA (BU# 846384 Project: Client: Crown Castle Drawn by: R AITHAL App'd: Code: TIA-222-H Date: 05/03/22 Scale: NTS Path: G:\SA jobs\03-05-2022--\163554_846384_Anderson lake----Ranjith-----Akshaykumar--\Tnx_001_01\163554_001_01_ANDERSON LAKE_WA.eri Dwg No. E-7 Feed Line Distribution Chart 0' - 150' Round Flat App In Face App Out Face Truss Leg Face A 95.917 46.583 0.000 150.000 El e v a t i o n ( f t ) (3 ) L D F 7 - 5 0 A ( 1 - 5 / 8 ) Face B 146.000146.000146.000146.000146.000146.000 121.000121.000121.000 119.000 78.000 (3 ) T Y P E 1 ( 1 - 1 / 4 ) TY P E 2 ( 1 - 7 / 1 6 ) CA T 5 E ( 1 / 4 ) Face C 95.917 46.583 0.000 150.000 146.000146.000146.000146.000146.000146.000 121.000121.000121.000 119.000 78.000 (1 2 ) L D F 7 - 5 0 A ( 1 - 5 / 8 ) CA T E G O R Y 5 E ( 1 3 / 6 4 ) (2 ) 9 7 7 6 ( 5 / 8 ) LD F 2 - 5 0 ( 3 / 8 ) 2- 1 / 2 " R i g i d C o n d u i t (2 ) L D F 4 - 5 0 A ( 1 / 2 ) Sa f e t y L i n e 3 / 8 LD F 2 - 5 0 ( 3 / 8 ) LD F 2 - 5 0 ( 3 / 8 ) RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 1 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL  Tower Input Data The tower is a monopole. This tower is designed using the TIA-222-H standard. The following design criteria apply: Tower is located in Jefferson County, Washington. Tower base elevation above sea level: 319.000 ft. Basic wind speed of 97 mph. Risk Category II. Exposure Category D. Crest Height: 324.000 ft. Rigorous Topographic Factor Procedure for wind speed-up calculations is used. Topographic Feature: Flat Topped Hill. Slope Distance L: 2244.000 ft. Distance from Crest x: 139.000 ft. Horizontal Distance Downwind: No. Deflections calculated using a wind speed of 60 mph. TIA-222-H Annex S. A non-linear (P-delta) analysis was used. Pressures are calculated at each section. Stress ratio used in pole design is 1. Tower analysis based on target reliabilities in accordance with Annex S. Load Modification Factors used: Kes(Fw) = 0.95. Maximum demand-capacity ratio is: 1.05. Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered. Options Consider Moments - Legs Distribute Leg Loads As Uniform Use ASCE 10 X-Brace Ly Rules Consider Moments - Horizontals Assume Legs Pinned Calculate Redundant Bracing Forces Consider Moments - Diagonals √ Assume Rigid Index Plate Ignore Redundant Members in FEA Use Moment Magnification √ Use Clear Spans For Wind Area SR Leg Bolts Resist Compression √ Use Code Stress Ratios Use Clear Spans For KL/r All Leg Panels Have Same Allowable √ Use Code Safety Factors - Guys Retension Guys To Initial Tension Offset Girt At Foundation Escalate Ice √ Bypass Mast Stability Checks √ Consider Feed Line Torque Always Use Max Kz √ Use Azimuth Dish Coefficients Include Angle Block Shear Check Use Special Wind Profile √ Project Wind Area of Appurt. Use TIA-222-H Bracing Resist. Exemption Include Bolts In Member Capacity Autocalc Torque Arm Areas Use TIA-222-H Tension Splice Exemption Leg Bolts Are At Top Of Section Add IBC .6D+W Combination Poles Secondary Horizontal Braces Leg Sort Capacity Reports By Component √ Include Shear-Torsion Interaction Use Diamond Inner Bracing (4 Sided) Triangulate Diamond Inner Bracing Always Use Sub-Critical Flow SR Members Have Cut Ends Treat Feed Line Bundles As Cylinder Use Top Mounted Sockets SR Members Are Concentric Ignore KL/ry For 60 Deg. Angle Legs Pole Without Linear Attachments Pole With Shroud Or No Appurtenances Outside and Inside Corner Radii Are Known Tapered Pole Section Geometry RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 2 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Section Elevation ft Section Length ft Splice Length ft Number of Sides Top Diameter in Bottom Diameter in Wall Thickness in Bend Radius in Pole Grade L1 150.000-95.917 54.083 5.083 12 21.313 34.290 0.281 1.125 A572-65 (65 ksi) L2 95.917-46.583 54.417 6.417 12 32.508 45.571 0.375 1.500 A572-65 (65 ksi) L3 46.583-0.000 53.000 12 43.281 56.000 0.469 1.875 A572-65 (65 ksi) Tapered Pole Properties Section Tip Dia. in Area in2 I in4 r in C in I/C in3 J in4 It/Q in2 w in w/t L1 21.966 19.047 1075.377 7.529 11.040 97.406 2179.005 9.374 4.958 17.629 35.400 30.799 4546.805 12.175 17.762 255.982 9213.060 15.158 8.436 29.995 L2 34.786 38.800 5113.532 11.504 16.839 303.671 10361.403 19.096 7.707 20.552 47.046 54.574 14228.958 16.180 23.606 602.774 28831.726 26.860 11.208 29.888 L3 46.236 64.619 15117.285 15.327 22.419 674.297 30631.719 31.804 10.343 22.065 57.810 83.817 32990.998 19.880 29.008 1137.307 66848.706 41.252 13.752 29.337 Tower Elevation ft Gusset Area (per face) ft2 Gusset Thickness in Gusset Grade Adjust. Factor Af Adjust. Factor Ar Weight Mult. Double Angle Stitch Bolt Spacing Diagonals in Double Angle Stitch Bolt Spacing Horizontals in Double Angle Stitch Bolt Spacing Redundants in L1 150.000-95.91 7 1 1 1 L2 95.917-46.583 1 1 1 L3 46.583-0.000 1 1 1 Feed Line/Linear Appurtenances - Entered As Round Or Flat Description Face or Leg Allow Shield Exclude From Torque Calculation Component Type Placement ft Total Number Number Per Row Clear Spacing in Width or Diameter in Perimeter in Weight klf * Feed Line/Linear Appurtenances - Entered As Area Description Face or Leg Allow Shield Exclude From Torque Calculation Component Type Placement ft Total Number CAAA ft2/ft Weight klf * LDF7-50A(1-5/8) C No No Inside Pole 146.000 - 0.000 12 No Ice 0.000 0.001 LDF7-50A(1-5/8) A No No Inside Pole 146.000 - 0.000 3 No Ice 0.000 0.001 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 3 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Description Face or Leg Allow Shield Exclude From Torque Calculation Component Type Placement ft Total Number CAAA ft2/ft Weight klf CATEGORY 5E(13/64) C No No Inside Pole 146.000 - 0.000 1 No Ice 0.000 0.000 9776(5/8) C No No Inside Pole 146.000 - 0.000 2 No Ice 0.000 0.000 LDF2-50(3/8) C No No Inside Pole 146.000 - 0.000 1 No Ice 0.000 0.000 2-1/2'' Rigid Conduit C No No Inside Pole 146.000 - 0.000 1 No Ice 0.000 0.003 * TYPE 1(1-1/4) B No No Inside Pole 121.000 - 0.000 3 No Ice 0.000 0.001 TYPE 2(1-7/16) B No No Inside Pole 121.000 - 0.000 1 No Ice 0.000 0.001 CAT5E(1/4) B No No Inside Pole 121.000 - 0.000 1 No Ice 0.000 0.000 * LDF4-50A(1/2) C No No Inside Pole 119.000 - 0.000 2 No Ice 0.000 0.000 * Safety Line 3/8 C No No CaAa (Out Of Face) 150.000 - 0.000 1 No Ice 0.037 0.000 * LDF2-50(3/8) C No No Inside Pole 78.000 - 0.000 1 No Ice 0.000 0.000 LDF2-50(3/8) C No No Inside Pole 150.000 - 0.000 1 No Ice 0.000 0.000 * Feed Line/Linear Appurtenances Section Areas Tower Section Tower Elevation ft Face AR ft2 AF ft2 CAAA In Face ft2 CAAA Out Face ft2 Weight K L1 150.000-95.917 A B C 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.028 0.123 0.055 0.699 L2 95.917-46.583 A B C 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.850 0.121 0.109 0.698 L3 46.583-0.000 A B C 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.747 0.115 0.102 0.660 Feed Line Center of Pressure Section Elevation ft CPX in CPZ in CPX Ice in CPZ Ice in L1 150.000-95.917 -0.196 0.113 -0.155 0.090 L2 95.917-46.583 -0.196 0.113 -0.156 0.090 L3 46.583-0.000 -0.197 0.114 -0.156 0.090 Note: For pole sections, center of pressure calculations do not consider feed line shielding. Discrete Tower Loads RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 4 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustment ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K Flash Beacon Lighting A From Leg 0.500 0.000 0.000 0.000 154.000 No Ice 2.700 2.700 0.050 5' x 2'' Pipe Mount A From Leg 0.500 0.000 2.500 0.000 149.500 No Ice 1.188 1.188 0.018 Side Lighting A From Leg 1.000 0.000 0.000 0.000 78.000 No Ice 0.108 0.108 0.005 Side Lighting B From Leg 1.000 0.000 0.000 0.000 78.000 No Ice 0.108 0.108 0.005 Side Lighting C From Leg 1.000 0.000 0.000 0.000 78.000 No Ice 0.108 0.108 0.005 Junction Box C From Leg 0.500 0.000 0.000 0.000 78.000 No Ice 1.000 0.600 0.010 * * 800 10121 w/ Mount Pipe A From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 3.600 2.950 0.072 800 10121 w/ Mount Pipe B From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 3.600 2.950 0.072 800 10121 w/ Mount Pipe C From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 3.600 2.950 0.072 TT19-08BP111-001 A From Leg 4.000 0.000 4.000 0.000 146.000 No Ice 0.545 0.442 0.016 TT19-08BP111-001 B From Leg 4.000 0.000 4.000 0.000 146.000 No Ice 0.545 0.442 0.016 TT19-08BP111-001 C From Leg 4.000 0.000 4.000 0.000 146.000 No Ice 0.545 0.442 0.016 (2) CMA-UBTULBULBHH/651 7/17/21/21_CCIV2 w/ Mount Pipe A From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 23.860 8.300 0.174 (2) CMA-UBTULBULBHH/651 7/17/21/21_CCIV2 w/ Mount Pipe B From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 23.860 8.300 0.174 (2) CMA-UBTULBULBHH/651 7/17/21/21_CCIV2 w/ Mount Pipe C From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 23.860 8.300 0.174 AHFIB_CCIV2 A From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 2.793 1.526 0.066 AHFIB_CCIV2 B From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 2.793 1.526 0.066 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 5 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustment ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K AHFIB_CCIV2 C From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 2.793 1.526 0.066 AHNA_CCIV2 A From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 1.331 0.608 0.034 AHNA_CCIV2 B From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 1.331 0.608 0.034 AHNA_CCIV2 C From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 1.331 0.608 0.034 DC6-48-60-18-8F_CCIV2 A From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 2.901 4.818 0.033 AHLBBA_CCIV2 A From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 3.057 1.023 0.101 AHLBBA_CCIV2 B From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 3.057 1.023 0.101 AHLBBA_CCIV2 C From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 3.057 1.023 0.101 AHCA_CCIV3 A From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 1.533 0.823 0.037 AHCA_CCIV3 B From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 1.533 0.823 0.037 AHCA_CCIV3 C From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 1.533 0.823 0.037 DC9-48-60-24-8C-EV_CCIV 2 B From Leg 4.000 0.000 5.000 0.000 146.000 No Ice 2.736 2.736 0.016 8' x 2'' Mount Pipe A From Leg 4.000 0.000 0.000 0.000 146.000 No Ice 1.900 1.900 0.029 8' x 2'' Mount Pipe B From Leg 4.000 0.000 0.000 0.000 146.000 No Ice 1.900 1.900 0.029 8' x 2'' Mount Pipe C From Leg 4.000 0.000 0.000 0.000 146.000 No Ice 1.900 1.900 0.029 5' x 2'' Pipe Mount A From Leg 4.000 0.000 0.000 0.000 146.000 No Ice 1.188 1.188 0.018 5' x 2'' Pipe Mount B From Leg 4.000 0.000 0.000 0.000 146.000 No Ice 1.188 1.188 0.018 5' x 2'' Pipe Mount C From Leg 4.000 0.000 0.000 0.000 146.000 No Ice 1.188 1.188 0.018 Platform Mount [LP 713-1] C None 0.000 146.000 No Ice 32.890 32.890 1.510 * ET-X-WM-18-65-8P w/ A From Leg 4.000 0.000 121.000 No Ice 4.000 2.300 0.059 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 6 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustment ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K Mount Pipe 0.000 3.000 ET-X-WM-18-65-8P w/ Mount Pipe B From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 4.000 2.300 0.059 ET-X-WM-18-65-8P w/ Mount Pipe C From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 4.000 2.300 0.059 ETCR-654L12H6 w/ Mount Pipe A From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 10.900 4.610 0.105 ETCR-654L12H6 w/ Mount Pipe B From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 10.900 4.610 0.105 ETCR-654L12H6 w/ Mount Pipe C From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 10.900 4.610 0.105 POWER JUNCTION CYLINDER A From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 0.369 0.369 0.003 POWER JUNCTION CYLINDER B From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 0.369 0.369 0.003 POWER JUNCTION CYLINDER C From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 0.369 0.369 0.003 OPTIC FIBER JUNCTION CYLINDER A From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 0.389 0.389 0.002 OPTIC FIBER JUNCTION CYLINDER B From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 0.389 0.389 0.002 OPTIC FIBER JUNCTION CYLINDER C From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 0.389 0.389 0.002 2.5GHz RRH-V3 A From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 2.402 1.221 0.060 2.5GHz RRH-V3 B From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 2.402 1.221 0.060 2.5GHz RRH-V3 C From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 2.402 1.221 0.060 2.5G 8T8R RADAR FILTER A From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 0.807 0.320 0.022 RRH-P4 A From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 2.735 1.789 0.060 RRH-P4 B From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 2.735 1.789 0.060 RRH-P4 C From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 2.735 1.789 0.060 (2) RRH-C2A W/ EXT A From Leg 4.000 0.000 121.000 No Ice 3.075 1.361 0.064 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 7 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustment ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K FILTER_CCIV2 0.000 3.000 (2) RRH-C2A W/ EXT FILTER_CCIV2 B From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 3.075 1.361 0.064 (2) RRH-C2A W/ EXT FILTER_CCIV2 C From Leg 4.000 0.000 3.000 0.000 121.000 No Ice 3.075 1.361 0.064 HORIZON QUANTUM C From Leg 4.000 0.000 0.000 0.000 121.000 No Ice 0.507 0.234 0.007 (2) 8' x 2'' Mount Pipe A From Leg 4.000 0.000 0.000 0.000 121.000 No Ice 1.900 1.900 0.029 (2) 8' x 2'' Mount Pipe B From Leg 4.000 0.000 0.000 0.000 121.000 No Ice 1.900 1.900 0.029 (2) 8' x 2'' Mount Pipe C From Leg 4.000 0.000 0.000 0.000 121.000 No Ice 1.900 1.900 0.029 Sector Mount [SM 411-3] C None 0.000 121.000 No Ice 20.530 20.530 1.069 * 800-10080 w/ Mount Pipe A From Leg 1.000 0.000 1.000 0.000 119.000 No Ice 0.798 1.143 0.014 800-10080 w/ Mount Pipe C From Leg 1.000 0.000 1.000 0.000 119.000 No Ice 0.798 1.143 0.014 * * Dishes Description Face or Leg Dish Type Offset Type Offsets: Horz Lateral Vert ft Azimuth Adjustment ° 3 dB Beam Width ° Elevation ft Outside Diameter ft Aperture Area ft2 Weight K * Andrew VHLP2-18 C Paraboloid w/Shroud (HP) From Leg 4.000 0.000 0.000 23.000 121.000 2.175 No Ice 3.715 0.031 * Load Combinations Comb. No. Description RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 8 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Comb. No. Description 1 Dead Only 2 1.2 Dead+1.0 Wind 0 deg - No Ice 3 0.9 Dead+1.0 Wind 0 deg - No Ice 4 1.2 Dead+1.0 Wind 30 deg - No Ice 5 0.9 Dead+1.0 Wind 30 deg - No Ice 6 1.2 Dead+1.0 Wind 60 deg - No Ice 7 0.9 Dead+1.0 Wind 60 deg - No Ice 8 1.2 Dead+1.0 Wind 90 deg - No Ice 9 0.9 Dead+1.0 Wind 90 deg - No Ice 10 1.2 Dead+1.0 Wind 120 deg - No Ice 11 0.9 Dead+1.0 Wind 120 deg - No Ice 12 1.2 Dead+1.0 Wind 150 deg - No Ice 13 0.9 Dead+1.0 Wind 150 deg - No Ice 14 1.2 Dead+1.0 Wind 180 deg - No Ice 15 0.9 Dead+1.0 Wind 180 deg - No Ice 16 1.2 Dead+1.0 Wind 210 deg - No Ice 17 0.9 Dead+1.0 Wind 210 deg - No Ice 18 1.2 Dead+1.0 Wind 240 deg - No Ice 19 0.9 Dead+1.0 Wind 240 deg - No Ice 20 1.2 Dead+1.0 Wind 270 deg - No Ice 21 0.9 Dead+1.0 Wind 270 deg - No Ice 22 1.2 Dead+1.0 Wind 300 deg - No Ice 23 0.9 Dead+1.0 Wind 300 deg - No Ice 24 1.2 Dead+1.0 Wind 330 deg - No Ice 25 0.9 Dead+1.0 Wind 330 deg - No Ice 26 Dead+Wind 0 deg - Service 27 Dead+Wind 30 deg - Service 28 Dead+Wind 60 deg - Service 29 Dead+Wind 90 deg - Service 30 Dead+Wind 120 deg - Service 31 Dead+Wind 150 deg - Service 32 Dead+Wind 180 deg - Service 33 Dead+Wind 210 deg - Service 34 Dead+Wind 240 deg - Service 35 Dead+Wind 270 deg - Service 36 Dead+Wind 300 deg - Service 37 Dead+Wind 330 deg - Service Maximum Member Forces Section No. Elevation ft Component Type Condition Gov. Load Comb. Axial K Major Axis Moment kip-ft Minor Axis Moment kip-ft L1 150 - 95.917 Pole Max Tension 14 0.000 0.000 0.000 Max. Compression 2 -12.378 -0.105 664.047 Max. Mx 8 -12.355 -670.730 0.558 Max. My 2 -12.378 -0.105 664.047 Max. Vy 8 19.159 -670.730 0.558 Max. Vx 14 18.950 0.876 -663.558 Max. Torque 23 -1.234 L2 95.917 - 46.583 Pole Max Tension 1 0.000 0.000 0.000 Max. Compression 2 -23.453 -0.862 1740.725 Max. Mx 8 -23.441 -1757.876 1.365 Max. My 2 -23.453 -0.862 1740.725 Max. Vy 8 26.319 -1757.876 1.365 Max. Vx 14 26.103 2.730 -1740.518 Max. Torque 20 -0.713 L3 46.583 - 0 Pole Max Tension 1 0.000 0.000 0.000 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 9 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Section No. Elevation ft Component Type Condition Gov. Load Comb. Axial K Major Axis Moment kip-ft Minor Axis Moment kip-ft Max. Compression 2 -42.811 -1.877 3351.438 Max. Mx 8 -42.811 -3380.182 2.406 Max. My 14 -42.811 4.896 -3351.525 Max. Vy 8 34.805 -3380.182 2.406 Max. Vx 14 34.595 4.896 -3351.525 Max. Torque 18 -0.627 Maximum Reactions Location Condition Gov. Load Comb. Vertical K Horizontal, X K Horizontal, Z K Pole Max. Vert 8 42.833 -34.778 0.020 Max. Hx 20 42.833 34.731 -0.014 Max. Hz 2 42.833 -0.019 34.563 Max. Mx 2 3351.438 -0.019 34.563 Max. Mz 8 3380.182 -34.778 0.020 Max. Torsion 6 0.526 -30.142 17.292 Min. Vert 13 32.124 -17.417 -29.898 Min. Hx 8 42.833 -34.778 0.020 Min. Hz 14 42.833 0.040 -34.568 Min. Mx 14 -3351.525 0.040 -34.568 Min. Mz 20 -3374.848 34.731 -0.014 Min. Torsion 18 -0.627 30.094 -17.279 Tower Mast Reaction Summary Load Combination Vertical K Shearx K Shearz K Overturning Moment, Mx kip-ft Overturning Moment, Mz kip-ft Torque kip-ft Dead Only 35.694 0.000 0.000 -0.212 0.193 0.000 1.2 Dead+1.0 Wind 0 deg - No Ice 42.833 0.019 -34.563 -3351.438 -1.877 -0.460 0.9 Dead+1.0 Wind 0 deg - No Ice 32.124 0.019 -34.563 -3328.664 -1.926 -0.459 1.2 Dead+1.0 Wind 30 deg - No Ice 42.833 17.459 -29.920 -2900.746 -1698.440 -0.353 0.9 Dead+1.0 Wind 30 deg - No Ice 32.124 17.459 -29.920 -2881.025 -1686.981 -0.351 1.2 Dead+1.0 Wind 60 deg - No Ice 42.833 30.142 -17.292 -1676.857 -2929.973 -0.526 0.9 Dead+1.0 Wind 60 deg - No Ice 32.124 30.142 -17.292 -1665.429 -2910.162 -0.525 1.2 Dead+1.0 Wind 90 deg - No Ice 42.833 34.778 -0.020 -2.406 -3380.182 -0.459 0.9 Dead+1.0 Wind 90 deg - No Ice 32.124 34.778 -0.020 -2.323 -3357.320 -0.458 1.2 Dead+1.0 Wind 120 deg - No Ice 42.833 30.136 17.245 1670.999 -2929.573 -0.213 0.9 Dead+1.0 Wind 120 deg - No Ice 32.124 30.136 17.245 1659.745 -2909.764 -0.212 1.2 Dead+1.0 Wind 150 deg - No Ice 42.833 17.417 29.898 2897.767 -1693.711 0.157 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 10 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Load Combination Vertical K Shearx K Shearz K Overturning Moment, Mx kip-ft Overturning Moment, Mz kip-ft Torque kip-ft 0.9 Dead+1.0 Wind 150 deg - No Ice 32.124 17.417 29.898 2878.201 -1682.283 0.156 1.2 Dead+1.0 Wind 180 deg - No Ice 42.833 -0.040 34.568 3351.525 4.896 0.442 0.9 Dead+1.0 Wind 180 deg - No Ice 32.124 -0.040 34.568 3328.886 4.803 0.441 1.2 Dead+1.0 Wind 210 deg - No Ice 42.833 -17.417 29.920 2900.181 1693.717 0.503 0.9 Dead+1.0 Wind 210 deg - No Ice 32.124 -17.417 29.920 2880.599 1682.170 0.502 1.2 Dead+1.0 Wind 240 deg - No Ice 42.833 -30.094 17.279 1674.762 2924.501 0.627 0.9 Dead+1.0 Wind 240 deg - No Ice 32.124 -30.094 17.279 1663.484 2904.607 0.626 1.2 Dead+1.0 Wind 270 deg - No Ice 42.833 -34.731 0.014 1.160 3374.848 0.540 0.9 Dead+1.0 Wind 270 deg - No Ice 32.124 -34.731 0.014 1.221 3351.902 0.539 1.2 Dead+1.0 Wind 300 deg - No Ice 42.833 -30.093 -17.241 -1670.982 2924.714 0.299 0.9 Dead+1.0 Wind 300 deg - No Ice 32.124 -30.093 -17.241 -1659.593 2904.817 0.299 1.2 Dead+1.0 Wind 330 deg - No Ice 42.833 -17.389 -29.912 -2900.083 1690.696 -0.184 0.9 Dead+1.0 Wind 330 deg - No Ice 32.124 -17.389 -29.912 -2880.364 1679.167 -0.183 Dead+Wind 0 deg - Service 35.694 0.007 -12.455 -1203.325 -0.560 -0.166 Dead+Wind 30 deg - Service 35.694 6.292 -10.782 -1041.527 -609.643 -0.127 Dead+Wind 60 deg - Service 35.694 10.862 -6.231 -602.142 -1051.784 -0.190 Dead+Wind 90 deg - Service 35.694 12.533 -0.007 -0.991 -1213.419 -0.167 Dead+Wind 120 deg - Service 35.694 10.860 6.214 599.785 -1051.639 -0.079 Dead+Wind 150 deg - Service 35.694 6.276 10.774 1040.202 -607.944 0.055 Dead+Wind 180 deg - Service 35.694 -0.014 12.457 1203.104 1.871 0.159 Dead+Wind 210 deg - Service 35.694 -6.277 10.782 1041.070 608.174 0.183 Dead+Wind 240 deg - Service 35.694 -10.845 6.227 601.135 1050.044 0.228 Dead+Wind 270 deg - Service 35.694 -12.516 0.005 0.290 1211.729 0.196 Dead+Wind 300 deg - Service 35.694 -10.844 -6.213 -600.031 1050.119 0.109 Dead+Wind 330 deg - Service 35.694 -6.266 -10.779 -1041.286 607.088 -0.066 Solution Summary Load Comb. Sum of Applied Forces Sum of Reactions % Error PX K PY K PZ K PX K PY K PZ K 1 0.000 -35.694 0.000 0.000 35.694 0.000 0.000% 2 0.019 -42.833 -34.563 -0.019 42.833 34.563 0.000% 3 0.019 -32.124 -34.563 -0.019 32.124 34.563 0.000% 4 17.459 -42.833 -29.920 -17.459 42.833 29.920 0.000% 5 17.459 -32.124 -29.920 -17.459 32.124 29.920 0.000% 6 30.142 -42.833 -17.292 -30.142 42.833 17.292 0.000% 7 30.142 -32.124 -17.292 -30.142 32.124 17.292 0.000% 8 34.778 -42.833 -0.020 -34.778 42.833 0.020 0.000% 9 34.778 -32.124 -0.020 -34.778 32.124 0.020 0.000% 10 30.136 -42.833 17.245 -30.136 42.833 -17.245 0.000% 11 30.136 -32.124 17.245 -30.136 32.124 -17.245 0.000% 12 17.417 -42.833 29.898 -17.417 42.833 -29.898 0.000% 13 17.417 -32.124 29.898 -17.417 32.124 -29.898 0.000% 14 -0.040 -42.833 34.568 0.040 42.833 -34.568 0.000% RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 11 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Load Comb. Sum of Applied Forces Sum of Reactions % Error PX K PY K PZ K PX K PY K PZ K 15 -0.040 -32.124 34.568 0.040 32.124 -34.568 0.000% 16 -17.417 -42.833 29.920 17.417 42.833 -29.920 0.000% 17 -17.417 -32.124 29.920 17.417 32.124 -29.920 0.000% 18 -30.094 -42.833 17.279 30.094 42.833 -17.279 0.000% 19 -30.094 -32.124 17.279 30.094 32.124 -17.279 0.000% 20 -34.731 -42.833 0.014 34.731 42.833 -0.014 0.000% 21 -34.731 -32.124 0.014 34.731 32.124 -0.014 0.000% 22 -30.093 -42.833 -17.241 30.093 42.833 17.241 0.000% 23 -30.093 -32.124 -17.241 30.093 32.124 17.241 0.000% 24 -17.389 -42.833 -29.912 17.389 42.833 29.912 0.000% 25 -17.389 -32.124 -29.912 17.389 32.124 29.912 0.000% 26 0.007 -35.694 -12.455 -0.007 35.694 12.455 0.000% 27 6.292 -35.694 -10.782 -6.292 35.694 10.782 0.000% 28 10.862 -35.694 -6.231 -10.862 35.694 6.231 0.000% 29 12.533 -35.694 -0.007 -12.533 35.694 0.007 0.000% 30 10.860 -35.694 6.214 -10.860 35.694 -6.214 0.000% 31 6.276 -35.694 10.774 -6.276 35.694 -10.774 0.000% 32 -0.014 -35.694 12.457 0.014 35.694 -12.457 0.000% 33 -6.277 -35.694 10.782 6.277 35.694 -10.782 0.000% 34 -10.845 -35.694 6.227 10.845 35.694 -6.227 0.000% 35 -12.516 -35.694 0.005 12.516 35.694 -0.005 0.000% 36 -10.844 -35.694 -6.213 10.844 35.694 6.213 0.000% 37 -6.266 -35.694 -10.779 6.266 35.694 10.779 0.000% Non-Linear Convergence Results Load Combination Converged? Number of Cycles Displacement Tolerance Force Tolerance 1 Yes 4 0.00000001 0.00000001 2 Yes 4 0.00000001 0.00005310 3 Yes 4 0.00000001 0.00002444 4 Yes 5 0.00000001 0.00010994 5 Yes 5 0.00000001 0.00004699 6 Yes 5 0.00000001 0.00011190 7 Yes 5 0.00000001 0.00004787 8 Yes 4 0.00000001 0.00011213 9 Yes 4 0.00000001 0.00006545 10 Yes 5 0.00000001 0.00010875 11 Yes 5 0.00000001 0.00004645 12 Yes 5 0.00000001 0.00011056 13 Yes 5 0.00000001 0.00004733 14 Yes 4 0.00000001 0.00005982 15 Yes 4 0.00000001 0.00002969 16 Yes 5 0.00000001 0.00011105 17 Yes 5 0.00000001 0.00004754 18 Yes 5 0.00000001 0.00010847 19 Yes 5 0.00000001 0.00004632 20 Yes 4 0.00000001 0.00011364 21 Yes 4 0.00000001 0.00006654 22 Yes 5 0.00000001 0.00011155 23 Yes 5 0.00000001 0.00004776 24 Yes 5 0.00000001 0.00010965 25 Yes 5 0.00000001 0.00004689 26 Yes 4 0.00000001 0.00001271 27 Yes 4 0.00000001 0.00020220 28 Yes 4 0.00000001 0.00021098 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 12 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL 29 Yes 4 0.00000001 0.00001952 30 Yes 4 0.00000001 0.00019813 31 Yes 4 0.00000001 0.00020526 32 Yes 4 0.00000001 0.00001285 33 Yes 4 0.00000001 0.00020728 34 Yes 4 0.00000001 0.00019704 35 Yes 4 0.00000001 0.00002035 36 Yes 4 0.00000001 0.00021050 37 Yes 4 0.00000001 0.00020182 Maximum Tower Deflections - Service Wind Section No. Elevation ft Horz. Deflection in Gov. Load Comb. Tilt ° Twist ° L1 150 - 95.917 27.887 29 1.722 0.003 L2 101 - 46.583 12.204 29 1.202 0.001 L3 53 - 0 3.199 29 0.558 0.000 Critical Deflections and Radius of Curvature - Service Wind Elevation ft Appurtenance Gov. Load Comb. Deflection in Tilt ° Twist ° Radius of Curvature ft 154.000 Flash Beacon Lighting 29 27.887 1.722 0.003 35059 149.500 5' x 2'' Pipe Mount 29 27.713 1.717 0.003 35059 146.000 800 10121 w/ Mount Pipe 29 26.498 1.683 0.003 35059 121.000 Andrew VHLP2-18 29 18.088 1.432 0.002 6043 119.000 800-10080 w/ Mount Pipe 29 17.455 1.411 0.001 5653 78.000 Side Lighting 29 6.977 0.894 0.000 3777 Maximum Tower Deflections - Design Wind Section No. Elevation ft Horz. Deflection in Gov. Load Comb. Tilt ° Twist ° L1 150 - 95.917 77.720 8 4.801 0.009 L2 101 - 46.583 34.021 8 3.354 0.002 L3 53 - 0 8.916 8 1.556 0.000 Critical Deflections and Radius of Curvature - Design Wind Elevation ft Appurtenance Gov. Load Comb. Deflection in Tilt ° Twist ° Radius of Curvature ft 154.000 Flash Beacon Lighting 8 77.720 4.801 0.009 12702 149.500 5' x 2'' Pipe Mount 8 77.236 4.788 0.009 12702 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 13 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Elevation ft Appurtenance Gov. Load Comb. Deflection in Tilt ° Twist ° Radius of Curvature ft 146.000 800 10121 w/ Mount Pipe 8 73.849 4.693 0.009 12702 121.000 Andrew VHLP2-18 8 50.419 3.994 0.004 2187 119.000 800-10080 w/ Mount Pipe 8 48.654 3.935 0.004 2045 78.000 Side Lighting 8 19.450 2.494 0.001 1359 Compression Checks Pole Design Data Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K Pn K Ratio Pu Pn L1 150 - 95.917 (1) TP34.29x21.313x0.281 54.083 0.000 0.0 29.695 -12.355 1737.140 0.007 L2 95.917 - 46.583 (2) TP45.571x32.508x0.375 54.417 0.000 0.0 52.714 -23.441 3083.770 0.008 L3 46.583 - 0 (3) TP56x43.281x0.469 53.000 0.000 0.0 83.817 -42.811 4903.320 0.009 Pole Bending Design Data Section No. Elevation ft Size Mux kip-ft Mnx kip-ft Ratio Mux Mnx Muy kip-ft Mny kip-ft Ratio Muy Mny L1 150 - 95.917 (1) TP34.29x21.313x0.281 670.730 1281.100 0.524 0.000 1281.100 0.000 L2 95.917 - 46.583 (2) TP45.571x32.508x0.375 1757.875 3029.950 0.580 0.000 3029.950 0.000 L3 46.583 - 0 (3) TP56x43.281x0.469 3380.183 6078.058 0.556 0.000 6078.058 0.000 Pole Shear Design Data Section No. Elevation ft Size Actual Vu K Vn K Ratio Vu Vn Actual Tu kip-ft Tn kip-ft Ratio Tu Tn L1 150 - 95.917 (1) TP34.29x21.313x0.281 19.159 521.141 0.037 0.642 1503.092 0.000 L2 95.917 - 46.583 (2) TP45.571x32.508x0.375 26.319 925.132 0.028 0.549 3552.575 0.000 L3 46.583 - 0 (3) TP56x43.281x0.469 34.805 1471.000 0.024 0.463 7185.367 0.000 RECEIVED BY DCD 7/5/22 ttnnxxTToowweerr Job 163554.001.01 - ANDERSON LAKE, WA (BU# 846384) Page 14 of 14 B+T Group 1717 S. Boulder, Suite 300 Project Date 18:07:51 05/03/22 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Client Crown Castle Designed by R AITHAL Pole Interaction Design Data Section No. Elevation ft Ratio Pu Pn Ratio Mux Mnx Ratio Muy Mny Ratio Vu Vn Ratio Tu Tn Comb. Stress Ratio Allow. Stress Ratio Criteria L1 150 - 95.917 (1) 0.007 0.524 0.000 0.037 0.000 0.532 1.050 4.8.2 L2 95.917 - 46.583 (2) 0.008 0.580 0.000 0.028 0.000 0.589 1.050 4.8.2 L3 46.583 - 0 (3) 0.009 0.556 0.000 0.024 0.000 0.565 1.050 4.8.2 Section Capacity Table Section No. Elevation ft Component Type Size Critical Element P K øPallow K % Capacity Pass Fail L1 150 - 95.917 Pole TP34.29x21.313x0.281 1 -12.355 1823.997 50.7 Pass L2 95.917 - 46.583 Pole TP45.571x32.508x0.375 2 -23.441 3237.958 56.1 Pass L3 46.583 - 0 Pole TP56x43.281x0.469 3 -42.811 5148.486 53.8 Pass Summary Pole (L2) 56.1 Pass RATING = 56.1 Pass  Program Version 8.1.1.0 RECEIVED BY DCD 7/5/22 APPENDIX B BASE LEVEL DRAWING RECEIVED BY DCD 7/5/22 RECEIVED BY DCD 7/5/22 APPENDIX C ADDITIONAL CALCULATIONS RECEIVED BY DCD 7/5/22 Monopole Base Plate Connection *TIA-222-H Section 15.5 Applied #VALUE! Anchor Rod Data Anchor Rod Summary (units of kips, kip-in) (16) 2-1/4" ø bolts (A615-75 N; Fy=75 ksi, Fu=100 ksi) on 64" BC Pu_t = 155.69 φPn_t = 243.75 Stress Rating Vu = 2.18 φVn = 149.1 60.8% Base Plate Data Mu = n/a φMn = n/a Pass 70" OD x 2.75" Plate (S-128; Fy=60 ksi, Fu=80 ksi) Base Plate Summary Stiffener Data Max Stress (ksi):18.95 (Flexural) N/A Allowable Stress (ksi):54 Stress Rating:33.4%Pass Pole Data 56" x 0.46875" 12-sided pole (A572-65; Fy=65 ksi, Fu=80 ksi) Analysis ResultsConnection Properties Iar (in) 1.375 Moment (kip-ft) 3380.18 Axial Force (kips) 42.81 Shear Force (kips) 34.81 Moment (kip-ft) Axial Force (kips) Shear Force (kips) 0.00 BU # 846384 Applied Loads Site Name ANDERSON LAKE, WA Order # 591705, Rev# 0 Analysis Considerations Site Info TIA-222 Revision H Grout Considered:No 42.81 34.81 Adjusted Pole Reactions Analysis Date: 03-05-2022CCIplate - Version 4.1.2 RECEIVED BY DCD 7/5/22 Report File: TIA-222 Revison: Tower Type:Check Pier Capacity only at location of Max Moment?No Location: Soil Lateral Check Compression Uplift Comp.Uplift 8.61 - 3380.18 5.90 - 42.83 3602.35 - 34.78 21.5%- Soil Vertical Check Compression Uplift Go to Soil Calculations 684.74 - 3 ksi 430.74 - 60 ksi 287.07 - 40 ksi 1115.49 - 329.90 - 28.2%- 35.8 ft Reinforced Concrete Flexure Compression Uplift 0.3 ft 8.57 - 3602.34 - 7505.11 - 7.5 ft 45.7%- 27 36 Reinforced Concrete Shear Compression Uplift 10 23.72 - 5 in 282.21 - 4 560.92 - in 47.9%- in *Rating per TIA-222-H Section 15.5 N/A # of Layers 3 121 FALSE 1 0 3 3 110 150 0 0 0.000 0.000 0.00 0.00 FALSE 2 3 15 12 110 150 0 28 1.084 1.084 50 FALSE 3 15 35.8 20.8 110 150 2.25 0 1.238 1.238 13 Pier Diameter Rebar Quantity Rebar Cage Diameter Rebar Quantity Tie Spacing Drilled Pier Foundation BU # : Site Name: Order Number: Monopole Applied Loads Material Properties Pier Design Data H 846384 ANDERSON LAKE, WA 591705, Rev# 0 Moment (kip-ft) Axial Force (kips) Shear Force (kips) Concrete Strength, f'c: Rebar Strength, Fy: Tie Yield Strength, Fyt: Cohesive Cohesionless Ultimate Skin Friction Uplift Override (ksf) Critical Shear Capacity Rating* Skin Friction (kips) Weight of Concrete (kips) Rating* Critical Shear (kip) End Bearing (kips) Axial (kips) Critical Depth (ft from TOC) Calculated Ultimate Skin Friction Uplift (ksf) Calculated Ultimate Skin Friction Comp (ksf) Ultimate Skin Friction Comp Override (ksf) Soil Profile Soil TypeSPT Blow Count Ult. Gross Bearing Capacity (ksf) γsoil (pcf) γconcrete (pcf) Critical Depth (ft from TOC) 28.2%Soil Interaction Rating* Rebar 2, Fy Override (ksi) Rebar 3, Fy Override (ksi) Depth Cohesionless Layer Top (ft)Bottom (ft)Thickness (ft) Groundwater Depth Cohesion (ksf) Angle of Friction (degrees) Rebar Size Pier Section 1 Check Limitation Apply TIA-222-H Section 15.5: Additional Longitudinal Rebar Shear Design Options Check Shear along Depth of Pier: Utilize Shear-Friction Methodology: Override Critical Depth: Dv=0 (ft from TOC) Soil Safety Factor Max Moment (kip-ft) Rating* Ext. Above Grade Critical Moment (kip-ft) Critical Moment Capacity Rating* From 0.3' above grade to 35.8' below grade Rebar Size Clear Cover to Ties Tie Size Input Effective Depths (else Actual): G:\SA jobs\03-05-2022--\163554_846384_Anderson lake----Ranjith-----Akshaykumar--\Tnx_001_01\163554_001_01_ANDERSON LAKE_WA.eri.rtf 47.9%Structural Foundation Rating* Total Capacity (kips) N/A Analysis Results Rebar & Pier Options Embedded Pole Inputs Belled Pier Inputs Version 5.0.3 RECEIVED BY DCD 7/5/22 ASCE 7 Hazards Report Address: No Address at This Location Standard:ASCE/SEI 7-16 Risk Category:II Soil Class:D - Default (see Section 11.4.3) Elevation:318.96 ft (NAVD 88) Latitude: Longitude: 48.024 -122.822611 Wind Results: Wind Speed 97 Vmph 10-year MRI 67 Vmph 25-year MRI 73 Vmph 50-year MRI 78 Vmph 100-year MRI 83 Vmph Data Source: ASCE/SEI 7-16, Fig. 26.5-1B and Figs. CC.2-1–CC.2-4, and Section 26.5.2 Date Accessed: Mon May 02 2022 Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability = 0.00143, MRI = 700 years). Site is not in a hurricane-prone region as defined in ASCE/SEI 7-16 Section 26.2. Page 1 of 3https://asce7hazardtool.online/Mon May 02 2022 RECEIVED BY DCD 7/5/22 SS : 1.322 S1 : 0.482 F a : 1.2 F v : N/A SMS : 1.586 SM1 : N/A SDS : 1.057 SD1 : N/A T L : 16 PGA : 0.563 PGA M : 0.676 F PGA : 1.2 Ie : 1 C v : 1.364 Seismic Site Soil Class: Results: Data Accessed: Date Source: D - Default (see Section 11.4.3) USGS Seismic Design Maps Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8. Mon May 02 2022 Page 2 of 3https://asce7hazardtool.online/Mon May 02 2022 RECEIVED BY DCD 7/5/22 Ice Results: Data Source: Date Accessed: Ice Thickness: 0.50 in. Concurrent Temperature: 25 F Gust Speed 30 mph Standard ASCE/SEI 7-16, Figs. 10-2 through 10-8 Mon May 02 2022 Ice thicknesses on structures in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may exceed the mapped values. Values provided are equivalent radial ice thicknesses due to freezing rain with concurrent 3-second gust speeds, for a 500-year mean recurrence interval, and temperatures concurrent with ice thicknesses due to freezing rain. Thicknesses for ice accretions caused by other sources shall be obtained from local meteorological studies. Ice thicknesses in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may exceed the mapped values. The ASCE 7 Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE 7 standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE. ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE 7 standard. In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE 7 Hazard Tool. Page 3 of 3https://asce7hazardtool.online/Mon May 02 2022 RECEIVED BY DCD 7/5/22 BU:846384 Structure:A WO:2103639 Order:591705 Rev:0 Decimal Degrees Deg Min Sec ###Lat:48.024000 +48 1 26.40 ###Long:-122.822611 -122 49 21.40 Seismic Design Code:TIA-222-H-1 ###Site Soil:D (Default)Default Risk Category:II ###USGS Seismic Reference SS:1.3220 g ###S1:0.4820 g TL:16 s 1 Importance Factor, Ie:1 Acceleration-based site coefficient, Fa:1.2000 Velocity-based site coefficient, Fv:1.8180 Design spectral response acceleration short period, SDS:1.0576 g Design spectral response acceleration 1 s period, SD1:0.5842 g Ts:0.5524 Seismic Design Category Based on SDS:D Seismic Design Category Based on SD1:D Seismic Design Category Based on S1:N/A Controlling Seismic Design Category:D Location Code and Site Parameters Seismic Design Category Determination CCISeismic 3.3.9 Page 1 Analysis Date: 03-05-2022 RECEIVED BY DCD 7/5/22 BU:846384 Structure:A WO:2103639 Order:591705 Rev:0 Tower Type:Tapered Monopole Height, h:150 ft ###Effective Seismic Weight, W:35.66 kips Amplification Factor, As:1.0 2.7.8.1 ###Response Modification Factor, R:1.5 ###2.799643342 Discrete Appurtenance Weight in Top 1/3 of Structure, Wu:6.37004 kips WL:29.28562502 kips E:29000.0 ksi g:386.088 in/s2 Average Moment of Inertia, Iavg:11614.79876 in4 Fa:0.357188355 hz Approximate Fundamental Period Monopole, Ta:2.7996 s 2.7.7.1.3.3 Seismic Response Coefficient, Cs 0.2087 Table 2-12 Note 3 Seismic Response Coefficient Max 1, Csmax N/A Seismic Response Coefficient Max 2, Csmax N/A Seismic Response Coefficient Min 1, Csmin 0.0465 2.7.7.1.1 Seismic Response Coefficient Min 2, Csmin N/A 2.7.7.1.1 Controlling Seismic Response Coefficient, Csc 0.2087 Seismic Base Shear, V 7.440 kips 2.7.7.1.1 Period Related Exponent, k:2.000 Sum of wihi k 263985.96 ### Tower Details Seismic Base Shear Vertical Distribution Factors CCISeismic 3.3.9 Page 2 Analysis Date: 03-05-2022 RECEIVED BY DCD 7/5/22 Section Number Length Top Height Mid Height, hx Section Weight, wx wxhx k Cvx Fxh Fxv 1 - 1 4.08 150.00 147.96 0.2704 5919.62 0.0224 0.1668 0.0572 1 - 2 10.00 145.92 140.92 0.7143 14183.51 0.0537 0.3997 0.1511 1 - 3 10.00 135.92 130.92 0.7881 13507.42 0.0512 0.3807 0.1667 1 - 4 10.00 125.92 120.92 0.8619 12602.28 0.0477 0.3552 0.1823 1 - 5 10.00 115.92 110.92 0.9358 11512.41 0.0436 0.3245 0.1979 1 - 6 10.00 105.92 100.92 1.0096 10282.10 0.0389 0.2898 0.2136 2 - 1 4.42 101.00 98.79 0.5919 5777.25 0.0219 0.1628 0.1252 2 - 2 10.00 96.58 91.58 1.4112 11835.98 0.0448 0.3336 0.2985 2 - 3 10.00 86.58 81.58 1.5096 10047.90 0.0381 0.2832 0.3193 2 - 4 10.00 76.58 71.58 1.6081 8240.33 0.0312 0.2322 0.3402 2 - 5 10.00 66.58 61.58 1.7066 6472.36 0.0245 0.1824 0.3610 2 - 6 10.00 56.58 51.58 1.8051 4803.11 0.0182 0.1354 0.3818 3 - 1 3.00 53.00 51.50 0.6642 1761.75 0.0067 0.0497 0.1405 3 - 2 10.00 50.00 45.00 2.2942 4645.68 0.0176 0.1309 0.4853 3 - 3 10.00 40.00 35.00 2.4172 2961.13 0.0112 0.0835 0.5113 3 - 4 10.00 30.00 25.00 2.5403 1587.71 0.0060 0.0447 0.5373 3 - 5 10.00 20.00 15.00 2.6634 599.27 0.0023 0.0169 0.5634 3 - 6 10.00 10.00 5.00 2.7865 69.66 0.0003 0.0020 0.5894 Sum 26.5786 126809.46 Tower Section Loads CCISeismic 3.3.9 Page 3 Analysis Date: 03-05-2022 RECEIVED BY DCD 7/5/22 Name hx wx wxhx k Cvx Fxh Fxv miscl Flash Beacon Lighting 154.00 0.0500 1185.80 0.0045 0.0334 0.0106 tower mounts 5' x 2'' Pipe Mount 149.50 0.0180 402.30 0.0015 0.0113 0.0038 miscl Side Lighting 78.00 0.0050 30.42 0.0001 0.0009 0.0011 miscl Side Lighting 78.00 0.0050 30.42 0.0001 0.0009 0.0011 miscl Side Lighting 78.00 0.0050 30.42 0.0001 0.0009 0.0011 Junction Box 78.00 0.0100 60.84 0.0002 0.0017 0.0021 kathrein 800 10121 w/ Mount Pipe 146.00 0.0716 1525.80 0.0058 0.0430 0.0151 kathrein 800 10121 w/ Mount Pipe 146.00 0.0716 1525.80 0.0058 0.0430 0.0151 kathrein 800 10121 w/ Mount Pipe 146.00 0.0716 1525.80 0.0058 0.0430 0.0151 powerwave technologies TT19-08BP111-001 146.00 0.0160 341.06 0.0013 0.0096 0.0034 powerwave technologies TT19-08BP111-001 146.00 0.0160 341.06 0.0013 0.0096 0.0034 powerwave technologies TT19-08BP111-001 146.00 0.0160 341.06 0.0013 0.0096 0.0034 (2) cellmax technologies CMA-UBTULBULBHH/6517/17/21/21_CCIV2 w/ Mount Pipe146.00 0.3481 7420.53 0.0281 0.2091 0.0736 (2) cellmax technologies CMA-UBTULBULBHH/6517/17/21/21_CCIV2 w/ Mount Pipe146.00 0.3481 7420.53 0.0281 0.2091 0.0736 (2) cellmax technologies CMA-UBTULBULBHH/6517/17/21/21_CCIV2 w/ Mount Pipe146.00 0.3481 7420.53 0.0281 0.2091 0.0736 nokia AHFIB_CCIV2 146.00 0.0660 1406.86 0.0053 0.0397 0.0140 nokia AHFIB_CCIV2 146.00 0.0660 1406.86 0.0053 0.0397 0.0140 nokia AHFIB_CCIV2 146.00 0.0660 1406.86 0.0053 0.0397 0.0140 nokia AHNA_CCIV2 146.00 0.0340 724.74 0.0027 0.0204 0.0072 nokia AHNA_CCIV2 146.00 0.0340 724.74 0.0027 0.0204 0.0072 nokia AHNA_CCIV2 146.00 0.0340 724.74 0.0027 0.0204 0.0072 raycap DC6-48-60-18-8F_CCIV2 146.00 0.0330 703.43 0.0027 0.0198 0.0070 nokia AHLBBA_CCIV2 146.00 0.1010 2152.92 0.0082 0.0607 0.0214 nokia AHLBBA_CCIV2 146.00 0.1010 2152.92 0.0082 0.0607 0.0214 nokia AHLBBA_CCIV2 146.00 0.1010 2152.92 0.0082 0.0607 0.0214 nokia AHCA_CCIV3 146.00 0.0370 788.69 0.0030 0.0222 0.0078 nokia AHCA_CCIV3 146.00 0.0370 788.69 0.0030 0.0222 0.0078 nokia AHCA_CCIV3 146.00 0.0370 788.69 0.0030 0.0222 0.0078 raycap DC9-48-60-24-8C-EV_CCIV2 146.00 0.0160 341.06 0.0013 0.0096 0.0034 tower mounts 8' x 2" Mount Pipe 146.00 0.0290 618.16 0.0023 0.0174 0.0061 tower mounts 8' x 2" Mount Pipe 146.00 0.0290 618.16 0.0023 0.0174 0.0061 tower mounts 8' x 2" Mount Pipe 146.00 0.0290 618.16 0.0023 0.0174 0.0061 tower mounts 5' x 2'' Pipe Mount 146.00 0.0180 383.69 0.0015 0.0108 0.0038 tower mounts 5' x 2'' Pipe Mount 146.00 0.0180 383.69 0.0015 0.0108 0.0038 tower mounts 5' x 2'' Pipe Mount 146.00 0.0180 383.69 0.0015 0.0108 0.0038 tower mounts Platform Mount [LP 713-1]146.00 1.5100 32187.16 0.1219 0.9071 0.3194 kmw communications ET-X-WM-18-65-8P w/ Mount Pipe 121.00 0.0586 858.55 0.0033 0.0242 0.0124 kmw communications ET-X-WM-18-65-8P w/ Mount Pipe 121.00 0.0586 858.55 0.0033 0.0242 0.0124 kmw communications ET-X-WM-18-65-8P w/ Mount Pipe 121.00 0.0586 858.55 0.0033 0.0242 0.0124 kmw communications ETCR-654L12H6 w/ Mount Pipe 121.00 0.1050 1537.16 0.0058 0.0433 0.0222 kmw communications ETCR-654L12H6 w/ Mount Pipe 121.00 0.1050 1537.16 0.0058 0.0433 0.0222 kmw communications ETCR-654L12H6 w/ Mount Pipe 121.00 0.1050 1537.16 0.0058 0.0433 0.0222 samsung telecommunications POWER JUNCTION CYLINDER 121.00 0.0030 43.92 0.0002 0.0012 0.0006 samsung telecommunications POWER JUNCTION CYLINDER 121.00 0.0030 43.92 0.0002 0.0012 0.0006 samsung telecommunications POWER JUNCTION CYLINDER 121.00 0.0030 43.92 0.0002 0.0012 0.0006 samsung telecommunications OPTIC FIBER JUNCTION CYLINDER 121.00 0.0020 29.28 0.0001 0.0008 0.0004 samsung telecommunications OPTIC FIBER JUNCTION CYLINDER 121.00 0.0020 29.28 0.0001 0.0008 0.0004 samsung telecommunications OPTIC FIBER JUNCTION CYLINDER 121.00 0.0020 29.28 0.0001 0.0008 0.0004 samsung telecommunications 2.5GHz RRH-V3 121.00 0.0600 878.46 0.0033 0.0248 0.0127 samsung telecommunications 2.5GHz RRH-V3 121.00 0.0600 878.46 0.0033 0.0248 0.0127 samsung telecommunications 2.5GHz RRH-V3 121.00 0.0600 878.46 0.0033 0.0248 0.0127 samsung telecommunications 2.5G 8T8R RADAR FILTER 121.00 0.0220 322.10 0.0012 0.0091 0.0047 samsung telecommunications RRH-P4 121.00 0.0600 878.46 0.0033 0.0248 0.0127 samsung telecommunications RRH-P4 121.00 0.0600 878.46 0.0033 0.0248 0.0127 samsung telecommunications RRH-P4 121.00 0.0600 878.46 0.0033 0.0248 0.0127 (2) samsung telecommunications RRH-C2A W/ EXT FILTER_CCIV2 121.00 0.1280 1874.05 0.0071 0.0528 0.0271 (2) samsung telecommunications RRH-C2A W/ EXT FILTER_CCIV2 121.00 0.1280 1874.05 0.0071 0.0528 0.0271 (2) samsung telecommunications RRH-C2A W/ EXT FILTER_CCIV2 121.00 0.1280 1874.05 0.0071 0.0528 0.0271 dragonwave HORIZON QUANTUM 121.00 0.0070 102.49 0.0004 0.0029 0.0015 (2) tower mounts 8' x 2" Mount Pipe 121.00 0.0580 849.18 0.0032 0.0239 0.0123 (2) tower mounts 8' x 2" Mount Pipe 121.00 0.0580 849.18 0.0032 0.0239 0.0123 (2) tower mounts 8' x 2" Mount Pipe 121.00 0.0580 849.18 0.0032 0.0239 0.0123 tower mounts Sector Mount [SM 411-3]121.00 1.0691 15651.96 0.0593 0.4411 0.2261 kathrein 800-10080 w/ Mount Pipe 119.00 0.0140 198.25 0.0008 0.0056 0.0030 kathrein 800-10080 w/ Mount Pipe 119.00 0.0140 198.25 0.0008 0.0056 0.0030 Andrew VHLP2-18 121.00 0.0310 453.87 0.0017 0.0128 0.0066 Sum 6.3950 118833.27 Discrete Loads CCISeismic 3.3.9 Page 4 Analysis Date: 03-05-2022 RECEIVED BY DCD 7/5/22 Name Start Height End Height hx wx wxhx k Cvx Fxh Fxv (12) andrew LDF7-50A(1-5/8) From 0 to 146 140.00 146.00 143.00 0.0590 1207.31 0.0046 0.0340 0.0125 (12) andrew LDF7-50A(1-5/8) From 0 to 146 130.00 140.00 135.00 0.0984 1793.34 0.0068 0.0505 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 120.00 130.00 125.00 0.0984 1537.50 0.0058 0.0433 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 110.00 120.00 115.00 0.0984 1301.34 0.0049 0.0367 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 100.00 110.00 105.00 0.0984 1084.86 0.0041 0.0306 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 90.00 100.00 95.00 0.0984 888.06 0.0034 0.0250 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 80.00 90.00 85.00 0.0984 710.94 0.0027 0.0200 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 70.00 80.00 75.00 0.0984 553.50 0.0021 0.0156 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 60.00 70.00 65.00 0.0984 415.74 0.0016 0.0117 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 50.00 60.00 55.00 0.0984 297.66 0.0011 0.0084 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 40.00 50.00 45.00 0.0984 199.26 0.0008 0.0056 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 30.00 40.00 35.00 0.0984 120.54 0.0005 0.0034 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 20.00 30.00 25.00 0.0984 61.50 0.0002 0.0017 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 10.00 20.00 15.00 0.0984 22.14 0.0001 0.0006 0.0208 (12) andrew LDF7-50A(1-5/8) From 0 to 146 0.00 10.00 5.00 0.0984 2.46 0.0000 0.0001 0.0208 (3) andrew LDF7-50A(1-5/8) From 0 to 146 140.00 146.00 143.00 0.0148 301.83 0.0011 0.0085 0.0031 (3) andrew LDF7-50A(1-5/8) From 0 to 146 130.00 140.00 135.00 0.0246 448.34 0.0017 0.0126 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 120.00 130.00 125.00 0.0246 384.38 0.0015 0.0108 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 110.00 120.00 115.00 0.0246 325.34 0.0012 0.0092 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 100.00 110.00 105.00 0.0246 271.22 0.0010 0.0076 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 90.00 100.00 95.00 0.0246 222.02 0.0008 0.0063 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 80.00 90.00 85.00 0.0246 177.74 0.0007 0.0050 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 70.00 80.00 75.00 0.0246 138.38 0.0005 0.0039 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 60.00 70.00 65.00 0.0246 103.94 0.0004 0.0029 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 50.00 60.00 55.00 0.0246 74.42 0.0003 0.0021 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 40.00 50.00 45.00 0.0246 49.82 0.0002 0.0014 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 30.00 40.00 35.00 0.0246 30.14 0.0001 0.0008 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 20.00 30.00 25.00 0.0246 15.38 0.0001 0.0004 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 10.00 20.00 15.00 0.0246 5.54 0.0000 0.0002 0.0052 (3) andrew LDF7-50A(1-5/8) From 0 to 146 0.00 10.00 5.00 0.0246 0.62 0.0000 0.0000 0.0052 general cable CATEGORY 5E(13/64) From 0 to 146 140.00 146.00 143.00 0.0001 2.58 0.0000 0.0001 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 130.00 140.00 135.00 0.0002 3.83 0.0000 0.0001 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 120.00 130.00 125.00 0.0002 3.28 0.0000 0.0001 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 110.00 120.00 115.00 0.0002 2.78 0.0000 0.0001 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 100.00 110.00 105.00 0.0002 2.32 0.0000 0.0001 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 90.00 100.00 95.00 0.0002 1.90 0.0000 0.0001 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 80.00 90.00 85.00 0.0002 1.52 0.0000 0.0000 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 70.00 80.00 75.00 0.0002 1.18 0.0000 0.0000 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 60.00 70.00 65.00 0.0002 0.89 0.0000 0.0000 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 50.00 60.00 55.00 0.0002 0.64 0.0000 0.0000 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 40.00 50.00 45.00 0.0002 0.43 0.0000 0.0000 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 30.00 40.00 35.00 0.0002 0.26 0.0000 0.0000 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 20.00 30.00 25.00 0.0002 0.13 0.0000 0.0000 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 10.00 20.00 15.00 0.0002 0.05 0.0000 0.0000 0.0000 general cable CATEGORY 5E(13/64) From 0 to 146 0.00 10.00 5.00 0.0002 0.01 0.0000 0.0000 0.0000 (2) belden 9776(5/8) From 0 to 146 140.00 146.00 143.00 0.0033 67.48 0.0003 0.0019 0.0007 (2) belden 9776(5/8) From 0 to 146 130.00 140.00 135.00 0.0055 100.24 0.0004 0.0028 0.0012 (2) belden 9776(5/8) From 0 to 146 120.00 130.00 125.00 0.0055 85.94 0.0003 0.0024 0.0012 (2) belden 9776(5/8) From 0 to 146 110.00 120.00 115.00 0.0055 72.74 0.0003 0.0020 0.0012 (2) belden 9776(5/8) From 0 to 146 100.00 110.00 105.00 0.0055 60.64 0.0002 0.0017 0.0012 (2) belden 9776(5/8) From 0 to 146 90.00 100.00 95.00 0.0055 49.64 0.0002 0.0014 0.0012 (2) belden 9776(5/8) From 0 to 146 80.00 90.00 85.00 0.0055 39.74 0.0002 0.0011 0.0012 (2) belden 9776(5/8) From 0 to 146 70.00 80.00 75.00 0.0055 30.94 0.0001 0.0009 0.0012 (2) belden 9776(5/8) From 0 to 146 60.00 70.00 65.00 0.0055 23.24 0.0001 0.0007 0.0012 (2) belden 9776(5/8) From 0 to 146 50.00 60.00 55.00 0.0055 16.64 0.0001 0.0005 0.0012 (2) belden 9776(5/8) From 0 to 146 40.00 50.00 45.00 0.0055 11.14 0.0000 0.0003 0.0012 (2) belden 9776(5/8) From 0 to 146 30.00 40.00 35.00 0.0055 6.74 0.0000 0.0002 0.0012 (2) belden 9776(5/8) From 0 to 146 20.00 30.00 25.00 0.0055 3.44 0.0000 0.0001 0.0012 (2) belden 9776(5/8) From 0 to 146 10.00 20.00 15.00 0.0055 1.24 0.0000 0.0000 0.0012 (2) belden 9776(5/8) From 0 to 146 0.00 10.00 5.00 0.0055 0.14 0.0000 0.0000 0.0012 andrew LDF2-50(3/8) From 0 to 146 140.00 146.00 143.00 0.0005 9.82 0.0000 0.0003 0.0001 andrew LDF2-50(3/8) From 0 to 146 130.00 140.00 135.00 0.0008 14.58 0.0001 0.0004 0.0002 andrew LDF2-50(3/8) From 0 to 146 120.00 130.00 125.00 0.0008 12.50 0.0000 0.0004 0.0002 andrew LDF2-50(3/8) From 0 to 146 110.00 120.00 115.00 0.0008 10.58 0.0000 0.0003 0.0002 andrew LDF2-50(3/8) From 0 to 146 100.00 110.00 105.00 0.0008 8.82 0.0000 0.0002 0.0002 andrew LDF2-50(3/8) From 0 to 146 90.00 100.00 95.00 0.0008 7.22 0.0000 0.0002 0.0002 andrew LDF2-50(3/8) From 0 to 146 80.00 90.00 85.00 0.0008 5.78 0.0000 0.0002 0.0002 andrew LDF2-50(3/8) From 0 to 146 70.00 80.00 75.00 0.0008 4.50 0.0000 0.0001 0.0002 andrew LDF2-50(3/8) From 0 to 146 60.00 70.00 65.00 0.0008 3.38 0.0000 0.0001 0.0002 andrew LDF2-50(3/8) From 0 to 146 50.00 60.00 55.00 0.0008 2.42 0.0000 0.0001 0.0002 andrew LDF2-50(3/8) From 0 to 146 40.00 50.00 45.00 0.0008 1.62 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 146 30.00 40.00 35.00 0.0008 0.98 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 146 20.00 30.00 25.00 0.0008 0.50 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 146 10.00 20.00 15.00 0.0008 0.18 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 146 0.00 10.00 5.00 0.0008 0.02 0.0000 0.0000 0.0002 miscl 2-1/2" Rigid Conduit From 0 to 146 140.00 146.00 143.00 0.0180 368.08 0.0014 0.0104 0.0038 miscl 2-1/2" Rigid Conduit From 0 to 146 130.00 140.00 135.00 0.0300 546.75 0.0021 0.0154 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 120.00 130.00 125.00 0.0300 468.75 0.0018 0.0132 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 110.00 120.00 115.00 0.0300 396.75 0.0015 0.0112 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 100.00 110.00 105.00 0.0300 330.75 0.0013 0.0093 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 90.00 100.00 95.00 0.0300 270.75 0.0010 0.0076 0.0063 Linear Loads CCISeismic 3.3.9 Page 5 Analysis Date: 03-05-2022 RECEIVED BY DCD 7/5/22 miscl 2-1/2" Rigid Conduit From 0 to 146 80.00 90.00 85.00 0.0300 216.75 0.0008 0.0061 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 70.00 80.00 75.00 0.0300 168.75 0.0006 0.0048 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 60.00 70.00 65.00 0.0300 126.75 0.0005 0.0036 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 50.00 60.00 55.00 0.0300 90.75 0.0003 0.0026 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 40.00 50.00 45.00 0.0300 60.75 0.0002 0.0017 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 30.00 40.00 35.00 0.0300 36.75 0.0001 0.0010 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 20.00 30.00 25.00 0.0300 18.75 0.0001 0.0005 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 10.00 20.00 15.00 0.0300 6.75 0.0000 0.0002 0.0063 miscl 2-1/2" Rigid Conduit From 0 to 146 0.00 10.00 5.00 0.0300 0.75 0.0000 0.0000 0.0063 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 120.00 121.00 120.50 0.0015 21.78 0.0001 0.0006 0.0003 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 110.00 120.00 115.00 0.0150 198.38 0.0008 0.0056 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 100.00 110.00 105.00 0.0150 165.38 0.0006 0.0047 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 90.00 100.00 95.00 0.0150 135.38 0.0005 0.0038 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 80.00 90.00 85.00 0.0150 108.38 0.0004 0.0031 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 70.00 80.00 75.00 0.0150 84.38 0.0003 0.0024 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 60.00 70.00 65.00 0.0150 63.38 0.0002 0.0018 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 50.00 60.00 55.00 0.0150 45.38 0.0002 0.0013 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 40.00 50.00 45.00 0.0150 30.38 0.0001 0.0009 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 30.00 40.00 35.00 0.0150 18.38 0.0001 0.0005 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 20.00 30.00 25.00 0.0150 9.38 0.0000 0.0003 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 10.00 20.00 15.00 0.0150 3.38 0.0000 0.0001 0.0032 (3) samsung telecommunications TYPE 1(1-1/4) From 0 to 121 0.00 10.00 5.00 0.0150 0.38 0.0000 0.0000 0.0032 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 120.00 121.00 120.50 0.0006 8.71 0.0000 0.0002 0.0001 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 110.00 120.00 115.00 0.0060 79.35 0.0003 0.0022 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 100.00 110.00 105.00 0.0060 66.15 0.0003 0.0019 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 90.00 100.00 95.00 0.0060 54.15 0.0002 0.0015 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 80.00 90.00 85.00 0.0060 43.35 0.0002 0.0012 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 70.00 80.00 75.00 0.0060 33.75 0.0001 0.0010 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 60.00 70.00 65.00 0.0060 25.35 0.0001 0.0007 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 50.00 60.00 55.00 0.0060 18.15 0.0001 0.0005 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 40.00 50.00 45.00 0.0060 12.15 0.0000 0.0003 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 30.00 40.00 35.00 0.0060 7.35 0.0000 0.0002 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 20.00 30.00 25.00 0.0060 3.75 0.0000 0.0001 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 10.00 20.00 15.00 0.0060 1.35 0.0000 0.0000 0.0013 samsung telecommunications TYPE 2(1-7/16) From 0 to 121 0.00 10.00 5.00 0.0060 0.15 0.0000 0.0000 0.0013 belkin CAT5E(1/4) From 0 to 121 120.00 121.00 120.50 0.0001 1.45 0.0000 0.0000 0.0000 belkin CAT5E(1/4) From 0 to 121 110.00 120.00 115.00 0.0010 13.23 0.0001 0.0004 0.0002 belkin CAT5E(1/4) From 0 to 121 100.00 110.00 105.00 0.0010 11.03 0.0000 0.0003 0.0002 belkin CAT5E(1/4) From 0 to 121 90.00 100.00 95.00 0.0010 9.03 0.0000 0.0003 0.0002 belkin CAT5E(1/4) From 0 to 121 80.00 90.00 85.00 0.0010 7.23 0.0000 0.0002 0.0002 belkin CAT5E(1/4) From 0 to 121 70.00 80.00 75.00 0.0010 5.63 0.0000 0.0002 0.0002 belkin CAT5E(1/4) From 0 to 121 60.00 70.00 65.00 0.0010 4.23 0.0000 0.0001 0.0002 belkin CAT5E(1/4) From 0 to 121 50.00 60.00 55.00 0.0010 3.03 0.0000 0.0001 0.0002 belkin CAT5E(1/4) From 0 to 121 40.00 50.00 45.00 0.0010 2.03 0.0000 0.0001 0.0002 belkin CAT5E(1/4) From 0 to 121 30.00 40.00 35.00 0.0010 1.23 0.0000 0.0000 0.0002 belkin CAT5E(1/4) From 0 to 121 20.00 30.00 25.00 0.0010 0.63 0.0000 0.0000 0.0002 belkin CAT5E(1/4) From 0 to 121 10.00 20.00 15.00 0.0010 0.23 0.0000 0.0000 0.0002 belkin CAT5E(1/4) From 0 to 121 0.00 10.00 5.00 0.0010 0.03 0.0000 0.0000 0.0002 (2) andrew LDF4-50A(1/2) From 0 to 119 110.00 119.00 114.50 0.0027 35.40 0.0001 0.0010 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 100.00 110.00 105.00 0.0030 33.08 0.0001 0.0009 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 90.00 100.00 95.00 0.0030 27.08 0.0001 0.0008 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 80.00 90.00 85.00 0.0030 21.68 0.0001 0.0006 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 70.00 80.00 75.00 0.0030 16.88 0.0001 0.0005 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 60.00 70.00 65.00 0.0030 12.68 0.0000 0.0004 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 50.00 60.00 55.00 0.0030 9.08 0.0000 0.0003 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 40.00 50.00 45.00 0.0030 6.08 0.0000 0.0002 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 30.00 40.00 35.00 0.0030 3.68 0.0000 0.0001 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 20.00 30.00 25.00 0.0030 1.88 0.0000 0.0001 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 10.00 20.00 15.00 0.0030 0.68 0.0000 0.0000 0.0006 (2) andrew LDF4-50A(1/2) From 0 to 119 0.00 10.00 5.00 0.0030 0.08 0.0000 0.0000 0.0006 miscl Safety Line 3/8 From 0 to 150 140.00 150.00 145.00 0.0022 46.26 0.0002 0.0013 0.0005 miscl Safety Line 3/8 From 0 to 150 130.00 140.00 135.00 0.0022 40.10 0.0002 0.0011 0.0005 miscl Safety Line 3/8 From 0 to 150 120.00 130.00 125.00 0.0022 34.38 0.0001 0.0010 0.0005 miscl Safety Line 3/8 From 0 to 150 110.00 120.00 115.00 0.0022 29.10 0.0001 0.0008 0.0005 miscl Safety Line 3/8 From 0 to 150 100.00 110.00 105.00 0.0022 24.26 0.0001 0.0007 0.0005 miscl Safety Line 3/8 From 0 to 150 90.00 100.00 95.00 0.0022 19.86 0.0001 0.0006 0.0005 miscl Safety Line 3/8 From 0 to 150 80.00 90.00 85.00 0.0022 15.90 0.0001 0.0004 0.0005 miscl Safety Line 3/8 From 0 to 150 70.00 80.00 75.00 0.0022 12.38 0.0000 0.0003 0.0005 miscl Safety Line 3/8 From 0 to 150 60.00 70.00 65.00 0.0022 9.30 0.0000 0.0003 0.0005 miscl Safety Line 3/8 From 0 to 150 50.00 60.00 55.00 0.0022 6.66 0.0000 0.0002 0.0005 miscl Safety Line 3/8 From 0 to 150 40.00 50.00 45.00 0.0022 4.46 0.0000 0.0001 0.0005 miscl Safety Line 3/8 From 0 to 150 30.00 40.00 35.00 0.0022 2.70 0.0000 0.0001 0.0005 miscl Safety Line 3/8 From 0 to 150 20.00 30.00 25.00 0.0022 1.38 0.0000 0.0000 0.0005 miscl Safety Line 3/8 From 0 to 150 10.00 20.00 15.00 0.0022 0.50 0.0000 0.0000 0.0005 miscl Safety Line 3/8 From 0 to 150 0.00 10.00 5.00 0.0022 0.06 0.0000 0.0000 0.0005 andrew LDF2-50(3/8) From 0 to 78 70.00 78.00 74.00 0.0006 3.50 0.0000 0.0001 0.0001 andrew LDF2-50(3/8) From 0 to 78 60.00 70.00 65.00 0.0008 3.38 0.0000 0.0001 0.0002 andrew LDF2-50(3/8) From 0 to 78 50.00 60.00 55.00 0.0008 2.42 0.0000 0.0001 0.0002 andrew LDF2-50(3/8) From 0 to 78 40.00 50.00 45.00 0.0008 1.62 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 78 30.00 40.00 35.00 0.0008 0.98 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 78 20.00 30.00 25.00 0.0008 0.50 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 78 10.00 20.00 15.00 0.0008 0.18 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 78 0.00 10.00 5.00 0.0008 0.02 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 150 140.00 150.00 145.00 0.0008 16.82 0.0001 0.0005 0.0002 andrew LDF2-50(3/8) From 0 to 150 130.00 140.00 135.00 0.0008 14.58 0.0001 0.0004 0.0002 CCISeismic 3.3.9 Page 6 Analysis Date: 03-05-2022 RECEIVED BY DCD 7/5/22 andrew LDF2-50(3/8) From 0 to 150 120.00 130.00 125.00 0.0008 12.50 0.0000 0.0004 0.0002 andrew LDF2-50(3/8) From 0 to 150 110.00 120.00 115.00 0.0008 10.58 0.0000 0.0003 0.0002 andrew LDF2-50(3/8) From 0 to 150 100.00 110.00 105.00 0.0008 8.82 0.0000 0.0002 0.0002 andrew LDF2-50(3/8) From 0 to 150 90.00 100.00 95.00 0.0008 7.22 0.0000 0.0002 0.0002 andrew LDF2-50(3/8) From 0 to 150 80.00 90.00 85.00 0.0008 5.78 0.0000 0.0002 0.0002 andrew LDF2-50(3/8) From 0 to 150 70.00 80.00 75.00 0.0008 4.50 0.0000 0.0001 0.0002 andrew LDF2-50(3/8) From 0 to 150 60.00 70.00 65.00 0.0008 3.38 0.0000 0.0001 0.0002 andrew LDF2-50(3/8) From 0 to 150 50.00 60.00 55.00 0.0008 2.42 0.0000 0.0001 0.0002 andrew LDF2-50(3/8) From 0 to 150 40.00 50.00 45.00 0.0008 1.62 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 150 30.00 40.00 35.00 0.0008 0.98 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 150 20.00 30.00 25.00 0.0008 0.50 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 150 10.00 20.00 15.00 0.0008 0.18 0.0000 0.0000 0.0002 andrew LDF2-50(3/8) From 0 to 150 0.00 10.00 5.00 0.0008 0.02 0.0000 0.0000 0.0002 Sum 2.6820 18343.23 CCISeismic 3.3.9 Page 7 Analysis Date: 03-05-2022 RECEIVED BY DCD 7/5/22 B+T Group 1717 S. Boulder, Suite 300 Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265 Job: 163554.001.01 - ANDERSON LAKE, WA (BU# 846384 Project: Client: Crown Castle Drawn by: R AITHAL App'd: Code: TIA-222-H Date: 05/03/22 Scale: NTS Path: G:\SA jobs\03-05-2022--\163554_846384_Anderson lake----Ranjith-----Akshaykumar--\163554_001_01_Seismic\163554_001_01_ANDERSON LAKE_WA CCISeismic 3.3.9 Wind And Seismic Analysis.eri Dwg No. E-1 150.0 ft 95.9 ft 46.6 ft 0.0 ft REACTIONS - 97 mph WIND TORQUE 1 kip-ft 35 K SHEAR 3380 kip-ft MOMENT 43 K AXIAL SEISMIC 7 K SHEAR 904 kip-ft MOMENT 50 K AXIAL ARE FACTORED ALL REACTIONS S e c t i o n 1 2 3 L e n g t h ( f t ) 54 . 0 8 3 54 . 4 1 7 53 . 0 0 0 N u m b e r o f S i d e s 12 12 12 T h i c k n e s s ( i n ) 0. 2 8 1 0. 3 7 5 0. 4 6 9 S o c k e t L e n g t h ( f t ) 5. 0 8 3 6. 4 1 7 T o p D i a ( i n ) 21 . 3 1 3 32 . 5 0 8 43 . 2 8 1 B o t D i a ( i n ) 34 . 2 9 0 45 . 5 7 1 56 . 0 0 0 G r a d e A5 7 2 - 6 5 W e i g h t ( K ) 4. 6 8. 6 13 . 4 26 . 6 MATERIAL STRENGTH GRADE GRADEFy FyFu Fu A572-65 65 ksi 80 ksi TOWER DESIGN NOTES 1. Tower is located in Jefferson County, Washington. 2. Tower designed for Exposure D to the TIA-222-H Standard. 3. Tower designed for a 97 mph basic wind in accordance with the TIA-222-H Standard. 4. Deflections are based upon a 60 mph wind. 5. Tower Risk Category II. 6. Topographic Category 5 with Crest Height of 324.000 ft 7. TIA-222-H Annex S 8. CCISeismic Note: Seismic loads generated by CCISeismic 3.3.9 9. CCISeismic Note: Seismic calculations are in accordance with TIA-222-H-1 10. TOWER RATING: 56.1% RECEIVED BY DCD 7/5/22 Monopole Base Plate Connection - Seismic *TIA-222-H Section 15.5 Applied *1.5 Overstrength Factor Applied #VALUE! Anchor Rod Data Anchor Rod Summary (units of kips, kip-in) (16) 2-1/4" ø bolts (A615-75 N; Fy=75 ksi, Fu=100 ksi) on 64" BC Pu_c = 66.7 φPn_c = 268.39 Stress Rating Vu = 0.7 φVn = 120.77 23.7% Base Plate Data Mu = n/a φMn = n/a Pass 70" OD x 2.75" Plate (S-128; Fy=60 ksi, Fu=80 ksi) Base Plate Summary Stiffener Data Max Stress (ksi):5.37 (Flexural) N/A Allowable Stress (ksi):54 Stress Rating:9.5%Pass Pole Data 56" x 0.46875" 12-sided pole (A572-65; Fy=65 ksi, Fu=80 ksi) Site Info BU # 846384 Site Name ANDERSON LAKE, WA Moment (kip-ft) 904.24 Order # 591705, Rev# 0 Analysis Considerations TIA-222 Revision H Grout Considered:No Iar (in) 1.375 Applied Loads Analysis Results Axial Force (kips) 50.38 Shear Force (kips) 7.44 Adjusted Pole Reactions Moment (kip-ft) 0.00 Axial Force (kips) 42.81 Shear Force (kips) 34.81 Connection Properties Analysis Date: 03-05-2022CCIplate - Version 4.1.2 RECEIVED BY DCD 7/5/22