HomeMy WebLinkAboutLog099
Jefferson County Fire Protection District #3
Commissioner Eugene Carmody
Chairman of the Board
Commissioner David Wheeler
Wayne E. Kier, Sr., Fire Chief
Commissioner Robert Pontius
Arlene F. Obtinario
Chief Financial OfficerlDist. Secretary
Commissioner William E. Hansen
Commissioner Mike Porter
101 South Point Road, Port Ludlow, Washington 98365 (360) 437-2899 Fax (360) 437-0117
PORT LUDLOW FIRE & RESCUE
May 4, 2004
Michelle Farfan, Planner
Jefferson County Department of Community Development
621 Sheridan Street
Port Townsend, W A. 98368
MY 17 200;
JEFFERSON COUNTY OeD
Dear Michelle:
LOG rrE\Vt
# ere\ __--
Page _ \ of...::8- ,
RE: ZON03-000444
Marina Expansion Mitigation
1.
For any proposal, a new dry-line fire suppression system installed at developer's expense
into any permanent over-water feature ("dock" "slip" "tie-up" "float" "breakwater")
where vessels, boat or ships of any type that are temporarily or permanently moored.
2.
Install a connection between B-Dock and C-dock to increase access to the floats to and
from land, for any proposal except no action.
3.
Fire hydrants located no more than 100 feet from dry-line fire suppression fire
department connection. Sufficient emergency access provided to docks for emergency
responses.
4.
Fire call boxes installed on any permanent over the water feature("dock" "slip" "tie-up"
"float" "breakwater") and central walkway.
I
".r
c' "
5.
Assurances the fire district has access to key/codes that are simple and quick to use on
access gates.
6.
The fire chief has final approval of the fire suppression system, scope and design.
7.
What will happen to the existing fire pumps and if retained as fire suppression system,
who will maintain and test the fire pumps?
Port Ludlow Resort Mitigation
1.
Living units over the water completely limiting access to one side of the waterside units,
how will the FD have access? Mitigation suggests a man way, I would like to review the
system that is proposed.
2.
All living units have approved fire sprinkler system. Living units over the water have
exposed underside. There is no way for FD to suppress a fire under the waterside units.
Install additional a dry fire sprinkler system underside of the buildings over the water for
any option. Fire District agrees with the sprinkler mitigation measure.
3.
Fire hydrants no more than 300 feet from any new structure with a maximum of 600 feet
between fire hydrants. Include 4-inch sexless adapters installed on large steamer ports as
specified by the fire District.
4.
Access roads designated permanent fire lane (s) and no curbside parking allowed at any
time. The curbs painted and stenciled "fire lane" using high visibility permanent paint
along with signage.
5.
Retail, restaurant and club have approved fire sprinkler system for any option selected.
I1:t ~urs i /t----
wa~er, Fire Chief
M 17 214
JEFFERSON COUNTY OeD